摘要:The experimental investigation of subcooling effects on system COP was carried out on a residential air conditioning using R410A as working fluid, with a compressor capacity of about 0.75 kW. In the experiment, the indoor and outdoor temperatures were controlled at 24°C and 32°C. The results showed that the use of condensate water lowers the refrigerant temperature in the condenser outlet by 2.7°C. By lowering the refrigerant temperature, the cooling capacity of the air conditioning can be enhanced. The decrease in of refrigerant temperature results in COP improvement 16.4%. Besides increasing the COP, the condensate water also decreases the discharge compressor temperature by 7.6°C. The decrease in of the discharge compressor temperature resulted in the decrease in power consumption of the air conditioning system by 5.9%.