  • 标题:CFD Analysis of the Inhaled-Air Quality for the Inpatients in a Four-Bed Sickroom
  • 本地全文:下载
  • 作者:Jeong-Hoon Yang
  • 期刊名称:Journal of Asian Architecture and Building Engineering
  • 印刷版ISSN:1346-7581
  • 电子版ISSN:1347-2852
  • 出版年度:2013
  • 卷号:12
  • 期号:1
  • 页码:109-116
  • DOI:10.3130/jaabe.12.109
  • 语种:English
  • 出版社:日本建築学会、大韓建築学会、中国建築学会
  • 摘要:This study examined the effects of the position and number of the supply openings (SOs) and exhaust openings (EOs) on the inhaled-air quality of inpatients using Computational Fluid Dynamics (CFD) analysis. The positions and number of SOs and EOs were selected to create mixing ventilation, displacement ventilation for a calm indoor environment, and personal ventilation for each inpatient′s ventilation. The effect of the installation of a curtain in the sickroom on the inhaled-air quality for inpatients was also examined. The inhaled-air quality of the inpatients was evaluated using the age of air, residual life of air, contribution ratio of nostril-exhaled air, and contribution ratio of the pollution source from the sickroom floor. CFD analysis showed that displacement ventilation, which uses a large SO with a low airflow velocity, supplied better air to the inpatients than the other ventilation methods, but pollution from the sickroom floor made a significant contribution. Overall, in general sickrooms and intensive care units, low-airflow-velocity displacement ventilation can supply high-quality air to the inpatients but the sickroom floor must be cleaned thoroughly.
  • 关键词:sickroom;inpatient;inhaled-air quality;CFD