期刊名称:Journal of Asian Architecture and Building Engineering
印刷版ISSN:1346-7581
电子版ISSN:1347-2852
出版年度:2014
卷号:13
期号:1
页码:239-246
DOI:10.3130/jaabe.13.239
语种:English
出版社:日本建築学会、大韓建築学会、中国建築学会
摘要:Terminal boxes are critical components of variable air volume (VAV) systems. The minimum airflow of terminal boxes is a key factor for comfort, indoor air quality (IAQ) and energy cost. If the minimum airflow is higher than needed, terminal boxes will have significantly more simultaneous heating and cooling, and air-handling units (AHUs) will consume more fan power. Buildings will have IAQ problems if the minimum airflow is less than required. A dynamic building simulation and field experiment were carried out to evaluate the impact of minimum airflow on the energy consumption of single duct VAV terminal boxes. A comparison of the simulation data with the existing constant setpoint revealed 20% annual energy savings in the improved minimum airflow setpoint. The experiment showed that the room air temperature can be maintained stably and the vertical difference in the room air temperature is lower than the comfort value when the improved minimum airflow setpoint is applied. Measurements of the CO2 levels also revealed no indoor air quality problems.