  • 标题:The Effect of Refrigerant Charge on the Performance of a Split-Unit Type Air Conditioner Using R22 Refrigerant
  • 本地全文:下载
  • 作者:Mohd Hazwan Yusof ; Sulaiman Mohd Muslim ; Muhammad Fadhli Suhaimi
  • 期刊名称:MATEC Web of Conferences
  • 电子版ISSN:2261-236X
  • 出版年度:2018
  • 卷号:225
  • 页码:1-7
  • DOI:10.1051/matecconf/201822502011
  • 语种:English
  • 出版社:EDP Sciences
  • 摘要:Numerous air conditioners are running without a proper refrigerant charge due to leakage and improper charging during installation. Therefore, there is a need to understand the performance of the air conditioner if it is not properly charged for the means of optimal operation and cost saving. This study is focusing on the usage of a used small capacity split-unit type air conditioner using R-22 refrigerant. The objective is to study the condenser performance over a variation of refrigerant charges. From the results, it is clear that the optimum refrigerant charge is 100%. The highest cooling capacity and COP were 3,330 J/s and 3.05 respectively.