摘要:Roof cooling can be used in coffered roofs, acoustic panels, as active cooling plasterboard attached to a standard metal structure designed for lowered roofs, or as a system of cooling register under the plaster. The roof cooling system works on the principle of heat transfer through a large active area and there is no unpleasant air flow than with conventional air conditioning. For technological reasons, very often pipes with a heat transfer medium are attached to a sheet metal of various materials, the thermokinetic properties of which significantly influence the intensity of the heat flux dissipated by the cooling system. The paper presents a numerical analysis of heat transport using stainless steel and aluminium sheets as the supporting sheet, as well as the influence of different ways of installing large panels under the roof.