摘要:This paper presents the effect of outlet window location and surface absorptivity inside an enclosure on temperature, external surfaces subjected to variable heat flux boundary condition. For analysis, scaled down size of a typical room has been considered, the enclosure has inner dimension 50cm x 40cm x 30cm (LxBxH), with the longer side oriented along east-west direction. The walls and roof of the enclosure are made of 10mm thick asbestos sheet. A door of 10 cm height from the floor is considered as inlet. Experiments were conducted for outlet window of 10 cm height located at 10cm, 15 cm, 20 c measured from the floor. The external surfaces roof, east wall and west walls were heated using electrical heating coil strips. For each window configuration, temperatures of the air inside the room were recorded using data acquisition system at fifteen locations for every five minutes. From the results, it was observed that for higher surface absorptivity, lower temperature index was observed when outlet window is at mid height (h = 0.5) of the west wall. It was also observed that as the surface absorptivity at the external surfaces decreases, window at location h = 0.33 provides lower temperature index.