摘要:It is beneficial for designers to identify the most important design parameters of building envelopes. This study undertook sensitivity analysis integrated with EnergyPlus to assess the impacts of envelope design parameters for naturally ventilated industrial buildings. Sensitivity coefficients of six envelope design parameters for different internal heat intensities were analyzed and compared for buildings in the city of Xi’an, located in the cold climate zone of China. Our results showed that the heat transfer coefficient of the roofs had the most significant impact on indoor temperature. The weights were 32.29%, 33.71% and 30.71%, and the heat intensities were 5, 10 and 15 W/msup3/sup, respectively. The effect of the skylight-to-roof ratio was the second most sensitive. The impact of the solar absorptances of the walls and roof on the total number of hours was not sensitive. The results could be helpful for designers to efficiently form alternative design solutions in the design of new and retrofitting industrial buildings.