摘要:Sharing corridors between high voltage alternating current (HVAC) powerlines and metallic pipelines has become quite common. Voltages can be induced onpipelines from HV power lines, which may cause a risk of electric shock to the operatorand serious corrosion damage on metallic pipelines. This paper aims to examine thecapacitive coupling between aerial metallic pipelines and HV power lines in perfectparallelism case and in general situation which is formed by parallelism, approachesand crossings, using a combination of charge simulation method and Artificial BeeColony (ABC) algorithm. The electric field at the pipeline's surface and the inducedvoltage on the pipeline are strongly affected by the pipeline separation distance. Thepresented simulation results are compared with those obtained from the admittancematrix analysis, a good agreement has been obtained.