首页    期刊浏览 2025年04月30日 星期三
登录注册

文章基本信息

  • 标题:Improving efficiency and lowering operating costs of evaporative cooling
  • 本地全文:下载
  • 作者:Jan Taler ; Bartosz Jagieła ; Magdalena Jaremkiewicz
  • 期刊名称:MATEC Web of Conferences
  • 电子版ISSN:2261-236X
  • 出版年度:2021
  • 卷号:338
  • 页码:1-13
  • DOI:10.1051/matecconf/202133801027
  • 语种:English
  • 出版社:EDP Sciences
  • 摘要:Cooling towers, or so-called evaporation towers, use the natural effect of water evaporation to dissipate heat in industrial and comfort installations. Water, until it changes its state of aggregation, from liquid to gas, consumes energy (2.257 kJ/kg). By consuming this energy, it lowers the air temperature to the wet-bulb temperature, thanks to which the medium can be cooled below the ambient temperature. Evaporative solutions are characterized by continuous water evaporation (approx. 1.5% of the total water flow) and low electricity consumption (high EER). Evaporative (adiabatic) cooling also has a positive effect on the reduction of electricity consumption of cooled machines. Lowering the relative humidity (RH) by approx. 2% lowers the wet-bulb temperature by approx. 0.5°C, which increases the efficiency of the tower, operating in an open circuit, expressed in kW, by approx. 5%, while reducing water consumption and treatment costs. The use of the M-Cycle (Maisotsenko cycle) to lower the temperature of the wet thermometer to the dew point temperature will reduce operating costs and increase the efficiency of cooled machines.
  • 关键词:M-Cycle;evaporation tower;cooling tower;adiabatic;IEC;Indirect Evaporative Cooling; DEC;Direct Evaporative Cooling;dew point cooling
国家哲学社会科学文献中心版权所有