摘要:The Hilbert-Huang transform (HHT) is an adaptive data analysis method that can accommodate the variety of data generated by nonlinear and nonstationary processes in nature. In this paper, we focus on the small geomagnetically induced current (GIC) at the local substations in low-latitude power grid of China, responding to a moderate storm on 14–18 July 2012. The HHT is applied to analyze the neutral point currents (NPCs) of transformers measured at different substations, and the GIC indices converted from local geomagnetic field measurements. The original data are decomposed into intrinsic mode functions (IMFs) using the ensemble empirical mode decomposition. After removal of the quasi-diurnal components related with the solar quiet variation, the IMFs representing storm disturbances are transformed into Hilbert energy spectra. The results show that some transformers have more or less responses to the moderate storm in the form of Hilbert energy spectra with the frequency around 2–3 mHz. A comparison on the amplitude changes of the spectra total energy of NPCs' perturbation during storm time intervals at different sites suggests that a shell type of three-phase single transformer group seems to be more vulnerable in the storm. Although the low-latitude power grids usually show very small GIC, these can be used to investigate the potential risk of space weather to the system.