首页    期刊浏览 2024年09月29日 星期日
登录注册

文章基本信息

  • 标题:Experimental Study On Operating Characteristic For Combined Radiant Floor And Fan Coil Cooling System In Under Low Temperature And High Humidity
  • 本地全文:下载
  • 作者:Xuwei Zhu ; Jing Ren ; Farun An
  • 期刊名称:E3S Web of Conferences
  • 印刷版ISSN:2267-1242
  • 电子版ISSN:2267-1242
  • 出版年度:2022
  • 卷号:356
  • 页码:1-4
  • DOI:10.1051/e3sconf/202235603042
  • 语种:English
  • 出版社:EDP Sciences
  • 摘要:The combined radiant floor and fan coil cooling (RFCAFC) system is widely used due to its high comfort and large energy saving potential. In this study, as an example, the combined RFCAFC system was studied in a high humidity environment in Jinan, Shandong Province, China. Days with similar outdoor meteorological conditions were grouped, and the comfort level and other evaluation indicators. The RFCAFC had good energy efficiency and comfort when the room was in a high humidity environment. This study showed that the radiant floor surface temperature uniformity coefficient (S) fluctuated between 0.7 and 1.0. The proportion of the total cooling capacity contributed by fan coil cooling under low temperature and high humidity (LH) is 68.0%. The combined cooling system used the LH operating strategy, the PMV value fluctuated from 0.12 to 0.49. Based on this study, the following recommendations for the combined cooling system can be made: (1) When the outdoor humidity is high, the radiant floor system should be turned on early to provide cooling capacity. (2) The operation strategy of the combined cooling system must be able to respond in real time to changes in outdoor meteorological conditions to prevent discomfort in times of extreme heat or humidity.
国家哲学社会科学文献中心版权所有