期刊名称:Vojnotehnicki glasnik / Military Technical Courier
印刷版ISSN:0042-8469
电子版ISSN:2217-4753
出版年度:2013
期号:6930
页码:182-199
语种:
出版社:Ministry of defence of the Republic of Serbia: University of defence in Belgrade
摘要:Infrared (IR) thermography, as a diagnostic technique, is used to find anomalies in the thermal signature of the Military museum building in Belgrade, to identify irregularities or deficiencies, such as wet materials, voids, or missing insulation and to inspect energy efficiency of the museum building and microclimatic indoor conditions. It is very important to perform preventative maintenance and stop undesirable environment influences that induce structural damage, modification of materials and agglomeration of pollutants and microorganisms on the cultural heritage artifacts, stored in the museum depot or exhibited in the galleries. The main causes for corrosion in historical buildings and museum artifacts are moisture and changeable temperature conditions. This paper deals with the results obtained in the application of IR thermography in determination of these conditions in the Military museum building, where very important metal artifacts are exhibited and deposed. The results show poor thermal insulation, wet walls and, generally, low energy efficiency.