首页    期刊浏览 2024年11月13日 星期三
登录注册

文章基本信息

  • 标题:Statistical survey of the pathology, diagnosis and rehabilitation of etics in walls.
  • 作者:Amaro, Barbara ; Saraiva, Diogo ; de Brito, Jorge
  • 期刊名称:Journal of Civil Engineering and Management
  • 印刷版ISSN:1392-3730
  • 出版年度:2014
  • 期号:August
  • 语种:English
  • 出版社:Vilnius Gediminas Technical University
  • 摘要:Besides being an innovative system, ETICS (external thermal insulation composite system) constitutes an excellent solution from the energy and constructive points of view for the rehabilitation of buildings with insufficient thermal insulation, leakage problems or degraded aspect. Initially this system was used almost exclusively in services buildings but as its market importance grew the price fell to the point when it became common in residential buildings. Over time the system was used widely in Portugal, as reflected in an increase in the area of cladding installed (Fig. 1) (Duarte 2011). Relative to other countries in Europe the application of ETICS (in relative area) in Portugal is still very small, as seen in Figure 2 (Duarte 2011). The components of this insulation system may vary and they are chosen according to the level of insulation, mechanical resistance and surface finishing required. Presently much of the energy from heating systems is wasted by leakage through passages that can easily be insulated, and it is therefore crucial that thermal insulation is installed to reduce such waste. The integrity and proper performance of insulation is fundamental to its efficiency, which leads to the issue of its inspection, maintenance and preservation.
  • 关键词:Building materials;Walls

Statistical survey of the pathology, diagnosis and rehabilitation of etics in walls.


Amaro, Barbara ; Saraiva, Diogo ; de Brito, Jorge 等


Introduction

Besides being an innovative system, ETICS (external thermal insulation composite system) constitutes an excellent solution from the energy and constructive points of view for the rehabilitation of buildings with insufficient thermal insulation, leakage problems or degraded aspect. Initially this system was used almost exclusively in services buildings but as its market importance grew the price fell to the point when it became common in residential buildings. Over time the system was used widely in Portugal, as reflected in an increase in the area of cladding installed (Fig. 1) (Duarte 2011). Relative to other countries in Europe the application of ETICS (in relative area) in Portugal is still very small, as seen in Figure 2 (Duarte 2011). The components of this insulation system may vary and they are chosen according to the level of insulation, mechanical resistance and surface finishing required. Presently much of the energy from heating systems is wasted by leakage through passages that can easily be insulated, and it is therefore crucial that thermal insulation is installed to reduce such waste. The integrity and proper performance of insulation is fundamental to its efficiency, which leads to the issue of its inspection, maintenance and preservation.

The main problem with ETICS is that they are still a relatively modern solution where long-term experience has not been gathered and published. The relevance of this problem is illustrated by the potential impacts of ETICS in buildings: positive impacts in energy savings and improvement of the thermal comfort; negative impacts in terms of unfulfilled expectations in terms of efficiency, architectural integration and durability. This paper focuses especially in this last aspect.

The aim of this research is to implement a methodology for the inspection, diagnosis and repair of ETICS to monitor their performance in walls. The system was validated through the inspection of a sample of 146 facades (14 buildings/sets of buildings) where various anomalies were observed, causes identified, in situ diagnosis tests recommended and repair techniques proposed, all designed to eliminate the root causes of pathologies.

The pathological survey of ETICS has been studied elsewhere with a view to analysing their applicability in new and rehabilitated construction (Duarte et al. 2011; Fernandes, de Brito 2012; Freitas 2002) and evaluating their degradation (Barreira, Freitas 2008; Kiinzel et al. 2006; Stazi et al. 2009; Daniotti, Paolini 2008).

The whole expert system is described in detail in another paper by the same authors (Amaro et al. 2013) and is included in a series of works (classification lists and correlation matrices) based on initial research by de Brito (2009). This methodology has thus been tested and implemented in various cladding systems/construction elements (Silvestre, de Brito 2009; Pereira et al. 2011; Neto, de Brito 2011; Sa et al. 2011).

[FIGURE 1 OMITTED]

Besides the proposed innovative expert-knowledge management system specifically tailored for ETICS in walls, this paper presents the statistical evaluation of the results of an inspection program of ETICS, that is unprecedented in the literature in terms of size of the sample analysed, scope of the analysis (pathology, diagnosis and rehabilitation) and systemic approach to data collection and analysis. It provides valuable information to building authorities, designers, contractors, owners and maintenance/rehabilitation management firms.

1. Sample characterisation

The field work was done between April and June 2011 and data was collected by visual inspection to validate the expert knowledge-based tools used to detect any pathology in, and implement a diagnosis and repair system on ETICS. It was initially based on a literature review. The sample consisted of 14 buildings/sets of buildings comprising 146 facades coated with ETICS aged from 3 to 22 years, in which 476 anomalies were registered. 1098 causes (518 indirect and 580 direct) were associated with these anomalies, and 662 auxiliary diagnosis methods and 768 repair techniques were recommended. Table 1 shows the most important characteristics of each building/set of buildings inspected.

1.1. Geographical distribution of the sample

The buildings inspected covered a good part of the Portuguese territory, particularly the north and centre regions (Fig. 3). Since ETICS were most frequently used in Portugal to comply with buildings' thermal comfort regulations, this system is mostly found in the north, where it is cooler. That is why more buildings were inspected in Porto, approximately 19 400 [m.sup.2] of facade area, around the same as the total facade area inspected in the centre of the country (5 250 [m.sup.2] in Coimbra and 11 780 [m.sup.2] in Lisbon Metropolitan Area). No buildings in the south were inspected since there are far fewer buildings with ETICS there and the few there are, are relatively recent.

[FIGURE 3 OMITTED]

1.2. Age distribution of the sample

ETICS are a relatively novel technology in the Portuguese construction sector, having only really expanded in the 1990s. The 146 facades inspected comprise ETICS applied between 1989 and 2008, thus the data collected had a considerable range of parameters. Considering that the validation of the inspection and diagnosis system should focus on the oldest possible ETICS to show their pathology, 20 facades over 20 years old were inspected, plus 84 between 10 and 20 years old and 42 less than 10 years old. Figure 4 shows the number of facades inspected by age of application of the system, giving an average of 13 years.

2. Inspection and diagnosis

The inspection plan used to identify and characterise the anomalies observed and define their origin is presented here. The inspection and validation files used are also presented.

2.1. Inspection plan

Inspections are generally classified according to their periodicity and they are often designated as current, detailed and structural/functional evaluation (Table 2). However, in this case the main objective of the inspections was to validate the classification lists and correlation matrices within the expert system.

The inspection plan consisted of a set of visits to inspect facades with ETICS cladding and use visual criteria to identify the anomalies and their most probable causes. Auxiliary diagnosis methods are mentioned only as a recommendation since, for economy reasons, no tests were actually performed. The anomalies were mapped to identify their location and so make it easier to monitor them in post-inspection interventions.

The repair actions were prioritised on the basis of availability of funding and thus privileged the more serious anomalies, according to the quality criteria requirements. After any intervention a pro-active (predictive) monitoring plan of premature degradation or re-pathology must be kept up.

2.2. Inspection files

The inspection files' main function was to characterise the inspected building and its facades. One inspection file was sometimes created for a set of buildings where the individual buildings all had the same characteristics and had been built in the same period, as in some neighbourhoods or university campuses.

The information in the inspection files may help to characterise the anomalies or to identify causes. Sometimes difficulties in accessing the original design and reports from previous interventions may prevent all the information needed from being obtained. Table 3 shows a standard inspection file before it is filled in on site.

2.3. Validation files

The validation files complement the inspection files and register for each facade the anomalies and their characteristics, the most probable causes, the diagnosis methods and the repair techniques considered most appropriate, in order to validate the expert system proposed. Table 4 gives a standard validation file before it is filled in on site.

3. Statistical analysis

Based on the data collected by visual inspection when the system is validated, a statistical analysis of the pathological phenomena that occur in ETICS insulation systems was performed to enable assessment of the parameters the system is most sensitive to, in order to minimise the degradation process. The analysis followed the approach used for other construction elements, such as ceramic tiles, natural stone cladding and renderings (Silvestre, de Brito 2011; Neto, de Brito 2012; Sa et al. 2011).

3.1. Incidence of the anomalies

The data for this section is represented graphically in Figures 5, 6 and 7, which cope with the contribution of each anomaly and group of anomalies within the sample.

Figures 5 and 6 indicate that the commonest anomalies are A-C5--Biological growth (present on 55.5% of the fa?ades inspected), A-C6--Other colour changes (48.6%) and A-C2--Runoff marks (43.2%). All three commonest anomalies belong to group A-C--Colour/Aesthetic anomalies, which is not usually associated with dire consequences in terms of thermal capacity.

This is why this group of anomalies has a higher incidence relative to the other groups, as seen in Figure 7.

Another paper on Portuguese ETICS (Silva, Falorca 2009) corroborates these results for the prevalence of colour changes over other anomalies. In fact various authors (Barreira et al. 2013; Flores-Colen et al. 2008; Kiinzel 1998) have studied the development of stains, especially those associated with surface condensation, to try and scientifically explain their occurrence and also minimise them. Other anomalies related to wall colour occur significantly less often than those mentioned above, e.g. 8.2% for A-C4--Graffiti, half the incidence of corrosion stains (A-C3) and next to no occurrences of A-C1--Efflorescence on ETICS (of 146 facades only two showed this anomaly and its extent was considered minimum, i.e. less than 10% of the facade area).

The graphs further show that group A-M--Materials rupture anomalies is the least frequent in the sample (24% of the total). No case of loss of adherence of the whole system and only one of partial adherence loss were detected in the sample (anomalies A-M4.2 and A-M4.1, respectively). This is a positive finding since these anomalies represent the worst scenarios of ETICS' defects and have very severe consequences for the thermal behaviour of the building. However, according to French statistics based on insurance companies' reports relative to 211 anomaly examples in ETICS between 1979 and 1985 (Freitas 2002), the incidence of loss of adherence of the whole system was 12% and of partial adherence loss was also 12%, indicating much higher incidence than found in this study, even though the French study is much older (ETICS' reliability has improved over the years). It is concluded that the non-observance of loss of adherence of ETICS in this field work is linked to the implicit need of immediate corrective intervention, and so these occurrences are hidden from random inspections such as those in this work (as opposed to those that involve insurance companies that are usually expensive and extensive). The materials rupture anomalies is generally the group with the greatest probability of causing changes that hinder the normal performance of the system. Therefore the incidence found for cracking (39.7% of the sum of A-M1.1 Oriented cracking and A-M1.2--Non-oriented cracking), and for -M5--Material gap (28.8%), may be considered worrying. However, based on the characterisation of anomalies undertaken during the field work, it was found that most of these anomalies are of minimal extent (crack width less than 1 mm) and are therefore relatively easy to solve and do not yet significantly affect the system as a whole.

Still, in the same group anomalies, A-M2--Deterioration of the covering of reinforcement cantilevers and A-M3--Detachment of the finishing coat are relatively rare in ETICS, with only 5 and 6 occurrences in this sample, which corresponds to incidences of 3.4% and 4.1%, respectively.

Concerning anomalies visually associated with changes to the flatness of the wall, we can distinguish between those that are not particularly detrimental in terms of the system's thermal performance (A-P1, A-P2 and A-P3), which were registered with the purpose of determining the cause of loss of flatness and homogeneity of the wall, from the swelling anomalies (A-P4 and A-P5) which result from mechanical actions associated with incorrect use of materials or faulty system application. Anomalies A-P1--Flatness deficiency, A-P2--Surface irregularities and A-P3 Joint., between plates visible were registered 38, 48 and 23 times, respectively, in the sample, indicating a moderate incidence in walls with ETICS. The other flatness anomalies concern swelling of the finishing coat (A-P4) and swelling of the insulation plates (A-P5), whose occurrence has the direst consequences, were observed less frequently (8.6% and 4.8%, respectively). It is concluded from the analysis of these incidences that the anomaly classification list proposed enables a good understanding of the pathologies that affect ETICS.

3.2. Incidence of the causes

It was expected that the field work would make it possible to relate each anomaly to its most probable cause(s) by visual inspection, with indexes of 1 or 2 assigned to indirect and direct causes, respectively. 1098 causes were assigned in the whole sample, 518 of which were considered indirect and the rest direct.

The data that relates to the contribution of each cause to all the anomalies observed is found in Figures 8 to 13, where each figure corresponds to a group of causes. Figure 14 shows the contribution of each group to the set of anomalies in the sample. Figures 15 and 17 represent the contribution of the groups of causes, divided in terms of "initial stages" (design and application), "exposure" (environmental and external mechanical actions) and "others" (the other groups).

The cause considered to be at the root of anomaly development most often was C-H7--Dirt build-up (dust), with a grand total of 98 occurrences. In fact the accumulation of dust particles or pollution can be associated with a variety of factors, including very rough cladding, atmospheric pollution/particles driven by wind/rain, the boundaries between areas of different flatness or any situations resulting from the facades getting wet, and this cause is thus directly or indirectly related to various anomalies.

Causes C-H1 and C-H2, impacts and perforation of the system respectively, occur 85 times. This is more than all the material gap occurrences (the main consequence of these actions) put together, since they are also associated with anomaly A-P2--Surface irregularities, which results in several instances of repairing perforations of the system. This reveals one of the sensitive aspects of ETICS, which is their poor surface resistance (in particular to perforations). Also associated with these causes (and anomalies) are design and application errors in which the designers and appliers are held responsible for not strengthening the system properly in areas accessible to the public.

Figure 14 shows that group C-H--External mechanical actions, which includes the causes mentioned, accounts for the greatest proportion of all causes registered with 26% of the total. Similarly group C-A--Environmental actions represent 24% of the grand total of causes attributed. The causes within this group can be associated with the climatic conditions during application of the system and with subsequent in-service actions. The first, even though mentioned several times in the literature on this topic (Freitas 2002; Silva, Falorca 2009; Fernandes 2010), are difficult to recognise due to the limitations of visual inspection a long time after the system has been applied. Therefore causes C-A1--Strong wind when cladding is applied and C-A2--Exceptionally low temperature during application of the cement-glue or covering have been given incidences of only 0% and 0.6%, respectively. As for the remaining environmental actions, mostly in the second subgroup, they all occurred at least 20 times, which is why this group of causes makes such a big contribution to ETICS anomalies. In fact the upper left graph of Figure 15 shows that 65% of the colour anomalies are associated with the exposure of facades to environmental or external mechanical actions, the only group of anomalies that is not primarily influenced by design and application errors. Since this group of anomalies occurs most often in the sample (49% of the total), these two groups of causes together stand out from the others.

In Figure 12 causes C-A6--Surface condensation damp and C-A3--Rain action stand out, because they come second and third in terms of frequency of attribution in the whole sample. In fact these two causes are directly related to the commonest anomalies since they propitiate the development of micro-organisms, the adhesion of dirt to the wall and the formation of water runoff marks. Another sensitive aspect of this system is thus highlighted--the propensity of the facade to suffer long periods of damp, thus allowing the related anomalies to develop.

Attributing environmental actions to the triggering of anomalies requires a full understanding of their degradation paths, but they are made worse by defects in the materials or constructive errors. In fact even though the main causes were related to factors that are present throughout the service life of the system, such as environmental or external mechanical actions, the anomalies are generally indirectly related to design or application errors or materials selection.

The application errors group accounts for 16% of the overall causes in the sample, with special emphasis on cause C-E14--Deficient overlapping of the finishing coat, attributed 41 times. This is partly due to the many times that anomaly A-P1--Flatness deficiency was observed. Cause C-E15--Deficient execution of flashings was attributed 9 times less than the previous one and 14 more than the next one. In fact it was found on site that various anomalies arose directly or indirectly from a deficient execution of the flashings, even though they were correctly designed. The most notable aspect of the incidence graphs is the simultaneously high values of some causes and very low values of others. Causes C-E5, C-E6 and C-E8 (respectively coincidence of the insulation plates' joints with discontinuities of the substrate, render between the insulation plates and mechanical anchors too tight) were never related to anomalies found on site. This is probably due to their occurring within the system, which can only be confirmed with destructive tests.

The C-C group of causes, design errors, only has five causes but they amount to a total of 14% of all the anomalies of the sample.

Figure 9 shows that cause C-C5--Inadequate design of sills, flashings or on the ground-floor has the highest incidence in the group, and has been attributed (as direct or indirect cause) to 58 anomalies in the 146 facades. As a matter of fact this error was associated several times with the development of regular water runoff paths that lead to efflorescence and the growth of microorganisms due to water accumulating on the wall. In other cases the non-existence of tail-ends led to various anomalies. The second most frequent cause in the design errrors group was C-C1--Insufficient thickness of the base coat. Even though the appropriate thickness of each coat is stated in the European technical approval guideline for commercially available ETICS (ETAG 004 2000), lower values are often specified at the design stage, especially for the base coat, which leads to an overly thin coat (1 mm). Sometimes the thickness is omitted and application criteria are dictated by the appliers. The main consequence is the subsequent susceptibility of the system to impacts and perforations that expose the inner coats. In some cases the glass fibre grid was exposed instead of being embedded in the base coat, because the latter was too thin. It is also important for the designers to strengthen the reinforcement, especially in areas subjected to tensions that cause cracking, such as window openings and corners. Cause C-C2--No reinforcement was related to 33 cases of cracking. Causes C-C3--Deficient interface between the system and other elements and C-C4 No primary coat were the least frequent within the group, with a total of 10 and 11 attributions, respectively. Figure 15 shows that design and application causes (called "initial stages") prevailed over the other groups as causes of materials rupture anomalies and flatness anomalies. This reveals the sensitivity of the system to the planning and application tasks.

Figure 8 concerns the causes related to materials selection, with an overall contribution of 9% to the grand total of causes. Though it would be reasonable to regard these defects as design errors, by setting them apart it was possible to highlight problems specific to the materials. Causes C-M2--Inadequate protection against micro-organisms of the finishing biocide (directly linked to the predominance of anomaly A-C5--Biological growth in the sample) and C-M6--Contaminated materials or ones having fabric defects stand out, which reveals the problem of incorrect use of materials, bearing in mind the characteristics required by the technical guidelines.

Finally the group of causes related to maintenance actions, mostly the lack of it and the consequences in terms of the development of existing anomalies and the emergence of new ones, accounts for 11% of all the causes in the sample. Containing only three causes, this group (and the environmental and external mechanical actions groups) clearly show the need for a correct maintenance plan, which must include the periodic inspection and diagnosis of the system, to solve the problems that arise in-service and control the degradation rate of the system.

Figure 14 shows that 39% of the anomalies in ETICS can be prevented by proper design, application and choice of materials, especially the materials rupture anomalies and the facade flatness anomalies. It is also concluded that implementing a plan of periodic inspections and maintenance helps to prevent early degradation from environmental and external mechanical actions during the service life, with special emphasis on the control of colour changes.

3.3. Incidence observed of the diagnosis methods

Figure 16 shows the number of times each test was recommended, with a grand total of 662 diagnosis methods for the 146 facades, and Figure 17 gives the incidence of each method relative to the 476 anomalies. There are more tests than there are anomalies since all except anomaly A-C4--Graffiti, to which no specific method was assigned, could need the coupling of various in situ tests for a complete diagnosis.

Among the diagnosis methods recommended, D-T1--Infrared thermography and D-E1--Contact moisture meter are important because they are associated with the diagnosis of various anomalies and the evaluation of their causes and are therefore the most useful on site, especially when used together (also because they are non-destructive). In fact they are recommended 159 and 155 times, respectively, in both cases more than the number of facades inspected (146). This proves how useful they are to help diagnose more than one anomaly or check on their severity, with an additional advantage of the contact moisture meter in terms of costs.

Since 10% of the anomalies concern oriented cracking and an extra 2% non-oriented cracking, it is natural that the recommendations of the alternative methods to measure the width of cracks, D-S1--Crack comparator and D-S2--Crack detection microscope, make 12% of the total. Diagnosis method D-S2 is recommended in only 7 of the 58 cases of cracking (12% of those cases). In other words in only 12% of the cracking anomalies was it considered necessary to resort to the millimetre accuracy of the crack detection microscope instead of the crack comparator (D-S1). The method D-S3--Crack meter, which can be used to monitor the stability of the cracks, had a similar usage frequency.

Also a part of the sensorial perception diagnosis methods group, probing (D-S4) is only recommended in 9% of cases, mostly because of the destructive nature of the method. Even though this is one of the most efficient ways to evaluate ETICS, enabling the origin of the error to be checked (application and/or design), the use of probing is only recommended when it is considered essential to the complete diagnosis of an anomaly.

Mechanical tests (D-M) showed frequencies between 2% and 5%. Recommending these tests on site aimed at evaluating the characteristics of the base coat in terms of the use of certified materials and deformability, which are paramount in case of swelling, adherence loss and evaluation of the base coat thickness or before applying a reinforcement grid when the system is particularly susceptible to shocks.

The Karsten tube test (D-H1), a liquid water permeability test, is recommended for 7% of the anomalies identified, since it is directly linked to some causes of anomalies, namely C-A4--Absorption and capillarity damp and C-H8--Splattering at the bottom of the walls. The incidence of these causes in the sample was 10.9% for C-A4 and 1.1% for C-H8, which explains why in most cases the Karsten tube test was considered the most suitable diagnosis method. Alternatively or complementarily (depending on what is to be analysed) method D-E2 - Needles moisture meter is used to measure the moisture within the system and was recommended for 6% of the anomalies in the sample.

The chemical methods, D-Q1--Colorimetric stripes and D-Q2--Field kit, for statistical purposes were always recommended simultaneously to evaluate salts, and therefore the same number of times. One test is not preferred over the other because both can be performed and the choice made between them later, in terms of salts evaluation, rather than on site. In comparative terms DQ1 are faster and cheaper but they are usually a preliminary test (with wider detection ranges). D-Q2 provides more accurate results but a spectrophotometer is needed and so it is costlier.

Additionally the mechanical action tests (D-M1 Sphere impact test--martinet baronnie, D-M2--Perforation test (perfotest) and D-M3--Pull-off test) were considered useful to diagnosing 2% to 5% of the anomalies observed. These values may be low because of their destructive nature, which makes them less likely to be chosen. However, in various situations these tests were considered indispensable, particularly to evaluate the characteristics of the materials used (e.g. A-M1 and A-M2), the adherence of the coats of the system and their tensile strength (A-M3) and the application of the system.

The diagnosis method D-U1--Ultrasonic pulse velocity meter was recommended for 10% of the anomalies, 8% of which were associated with anomaly A-P1--Flatness deficiency and its main cause C-E14--Deficient overlapping of the finishing coat, and the remaining 2% to other cases where the results were considered relevant, i.e. the identification of defects, voids or changes to the internal coats of the system.

Even though the tests are used to diagnose various anomalies there is a clear pattern in the relationship between some factors and the recommended method. In other words, each test can be strongly linked to one of the objectives of the diagnosis.

Exemplifying this concept is the finding that method D-S3--Crack meter is directly related to crack monitoring and that the causes linked to water leakages within the system are related to methods D-H1--Karsten tube test or D-E2--Needles moisture meter, and the corresponding groups of anomalies are somehow linked to these diagnosis methods. Therefore data on the relationship between each diagnosis technique recommended and the various anomaly groups were collected and analysed.

A strong relationship was found between the diagnosis methods groups D-S--Sensorial perception tests and D-M--Mechanical action tests and the materials rupture anomalies, and between the group of hydrodynamic methods (D-H1--Karsten tube test) and the colour/aesthetic anomalies, which is justified by their relation to the causes associated with these anomalies. The methods D-E2--Needles moisture meter and D-U1--Ultrasonic pulse velocity equipment are essentially related to the diagnosis of flatness anomalies (A-P). More specifically, the first one relates to swellings (A-P4 and A-P5) and the second one to flatness deficiencies (A-P1) and joints between plates being visible (A-P3).

It is thus concluded that there is a direct relationship between diagnosis methods and anomalies or groups of anomalies. Knowing this relationship facilitates the recommendation of these methods during the inspection.

3.4. Incidence of the repair techniques

Figure 18 shows that 43% of the repair techniques prescribed belong to the group of surface techniques (TR-A1 and TR-A2). They can be seen as maintenance and are directly related to the colour/aesthetic anomalies that represent around half of all the anomalies detected. On the other hand, the repair techniques concerning deeper interventions make up 24% of the universe, coinciding with the 24% of the materials rupture anomalies group, even though some of the techniques are prescribed for other anomalies, i.e. those concerning flatness deficiencies.

Figure 18 also shows that the technique TR-A1--Cleaning was the most often recommended because of the large number of colour/aesthetic anomalies, in particular leakage and biological growth. This has to do with the usually light colour of the system and lack of periodic maintenance as well as with the incorrect handling of singularities in the walls, such as sill drip edges and parapet capping, which allow biological organisms and other stains to build up on the facade.

Technique TR-A2--Application of surface protection had quite a high incidence since it is generally implemented with cleaning.

Technique TR-B2--Partial/whole replacement of the finishing coat was the second most often recommended since it remedies several anomalies at the level of the finishing, viz., surface gaps and irregularities and even flatness deficiencies.

Technique TR-C5--Correction of geometrical constructive features is one of the most relevant techniques. Runoff marks (A-C2) mostly result from the careless handling of some singularities on the facade. The correction of these problems may require the application/replacement of drip edges, flashings and other constructive details, which eliminate or prevent the occurrence of this anomaly.

Technique TR-B3--Application of a new finishing on top of the existing coat/paint layer is another of the most often recommended. This is partly due to its versatility at repairing anomalies. It tends to be recommended in situations of extreme soiling, when cleaning by itself is not enough, or when there are surface colour changes.

Technique TR-B1--Filling/clogging of cracks is the best option in a great number of oriented cracking cases. For non-oriented cracking (mapped), which usually occurs in the finishing and is of considerable extent, technique TR-B2 would be preferable.

The partial/whole replacement of the system (TR-C6) appears with a non-negligible incidence, in circumstances when surface repair would not be sufficient and deeper intervention is required.

Technique TR-C2--Filling of material gaps/perforations, however, did not fulfil the initial expectations, even though 9% of the anomalies detected were material gaps. Because of the mechanical fragility of the system more damage caused by impacts and perforations was expected, even though some gaps between materials had already been repaired (usually incorrectly) leading to anomaly A-P2--Surface irregularities.

Techniques TR-C1--Protection of protruding edges and TR-C3--Joint repair show lower incidence because they are intended for more specific repairs. TR-C1 targets the correction of damage to protruding edges, either cracks or material gaps. Furthermore, and even though it covers various methods of repairing joints, TR-C3 was suggested as a solution for anomalies other than cracking near expansion joints. This technique was considered when the ETICS needed to be separated from other construction elements or when the joints between plates were visible, where there was a possibility of the insulation material becoming dimensionally unstable and the creation of an expansion joint could solve the problem.

Finally technique TR-C4--Application of new adhesive material and/or mechanical anchors is relatively rare compared with the other techniques, with only 9 recommendations. This low incidence is due to the specific nature of the technique, which is used only in situations of loss of adherence of the system or swelling of the plates. In the only situation of partial loss of adherence of the system replacement of that area was recommended. Therefore TR-C4 was recommended only to solve problems of swelling of the plates.

3.5. Relationship between repair techniques and anomalies

Based on the data collected during the inspection campaign the frequencies of each repair technique were correlated with the various anomalies, as seen in Figure 19. The techniques aimed at repairing the anomalies and/or eliminating their causes.

Oriented cracking (A-M1.1) was mostly solved by technique TR-B1--Filling/clogging of cracks, and in some cases by partial/whole replacement of the system (TR-C6), usually when plates coincided with the profiles' joints. Non-oriented cracking (A-M1.2) was usually handled by technique TR-B2--Partial/whole replacement of the finishing coat, given the superficial nature of the anomaly, though techniques TR-C6 or TR-C5--Correction of geometrical constructive features were occasionally chosen if the anomaly was considerably extensive or resulted from an incorrectly fitted construction element (Fig. 20).

[FIGURE 20 OMITTED]

[FIGURE 21 OMITTED]

[FIGURE 22 OMITTED]

The best technique for the deterioration of the covering of reinforcement cantilevers (A-M2) was TR-C1--Protection of protruding edges, as expected, given its specificity. For slight deterioration of the finishing technique TR-B2--Partial/whole replacement of the finishing coat was recommended. The same technique was prescribed 75% of the times to remedy anomaly A-M.3--Detachment of the finishing even though it was sometimes complemented by technique TR-C5--Correction of geometrical constructive features, since replacing the finishing solves the anomaly and correcting the tail-end elements eliminates the possible cause (Fig. 20).

To finish the materials rupture anomalies, the only case of partial loss of adherence of the system (A-M4.1) was solved by partial/whole replacement of the system (TR-C6), complemented with technique TR-C5, in this case resorting to back wrapping and replacement/installation of the bottom profile. The material gaps (A-M5) observed were mostly handled using technique TR-C2--Filling of material gaps/perforations, whenever the perforation gap reached the insulation plate or the substrate (51% of cases). For more superficial gaps that only reached the reinforced mortar but did not damage the grid, partial/whole replacement of the finishing coat (TR-B2) proved to be sufficient. Technique TR-C1 was prescribed locally to treat protruding edges when the location of the material gap near the edges justified the treatment of that area and the installation of corner profiles was not considered (Fig. 20).

In the colour/aesthetic anomalies group there is a high incidence of cleaning (TR-A1) and in most cases application of surface protection (TR-A2). Anomalies A-C1--Efflorescence and A-C3--Corrosion stains were rare in the sample analysed, representing less than 2% in total. With the exception of a single case of efflorescence, where no deeper intervention was deemed necessary, both anomalies were solved by surface cleaning (TR-A1), in both cases over a small area, and correction of geometrical constructive features (TR-C5) (Fig. 21).

Runoff marks (A-C2) and biological growth (A-C5) represent 61% of the colour/aesthetic anomalies and 30% of all anomalies. In the first case, cleaning (TR-A1) was most often prescribed to eliminate the marks. But to eliminate the causes, correction of geometrical constructive features (TR-C5) became fundamental. As for the manifestation of micro-organisms on the system's surface, cleaning (TR-A1) and complementary application of surface protection (TR-A2) were the techniques chosen to eliminate the anomaly and prevent its recurrence. In both cases, more severe problems were repaired by painting the wall, thus justifying the incidence of technique TR-B3 in both cases (Fig. 21).

Graffiti (A-C4) strongly affects the aesthetics of a facade and is not always easy to remove. Consequently, combining cleaning (TR-A1) and the application of an anti-graffiti barrier (TR-A2), repainting the wall (TR-B3) was deemed necessary in 50% of the situations when this anomaly was detected. Depending on the characteristics, damp and dirt stains, surface decolouration, and other problems within anomaly A-C.6--Other colour changes, were solved through simple cleaning (TR-A1). In the case of dirt stains (e.g. due to atmospheric pollution), cleaning plus the application of water repellent (TR-A2) was the technique used for runoff marks, and the application of a new finishing/painting (TR-B3) for other colour changes, especially those caused by incorrect surface repairs (Fig. 21).

Flatness anomalies are mostly due to incorrect characteristics or application of the finishing coat or damage to it. Apart from swelling of the insulation plates (A-P5) which implies another level of intervention, the first four anomalies of the group require an intervention to the finishing coat, usually by partial/whole replacement (TR-B2). In fact anomaly A-P1--Flatness deficiency was dealt with solely by this technique, which was considered sufficient given the causes established. This anomaly has a sizeable incidence (8%) and in almost all instances its origin was a deficient overlapping of the finishing coat (86%) during the system's application. Depending on the height of the scaffolding when the system was installed, it could have been applied in horizontal coats. The transition between a new coat and the previous one must ensure the greatest possible homogeneity at the level of overlapping of the finishing coat. Surface irregularities (A-P2) come from uneven texture of the finishing coat, from incorrect interventions or from small superficial material gaps. The replacement of the finishing coat (TR-B2) and the application of a new finishing on top of the existing coat (TR-B3) were the preferred techniques to rectify this anomaly (Fig. 22).

Joints between plates visible (A-P3) is caused mostly by incoherencies in terms of the base coat or the dimensional stability of the insulation plates. Deficiencies of the base coat are solved by the partial/whole replacement of the finishing coat (TR-B2). However, the dimensional instability of the plates requires the creation of an expansion joint (TR-C3) to allow movement of the system, or, as a last resort, its replacement (TR-C6). Swelling of the finishing coat (A-P4) necessarily requires its replacement. The correction of geometrical constructive features (TR-C5) was prescribed to eliminate the causes of this anomaly, in this case essentially by capping the parapets, areas where water can infiltrate the system, thereby boosting this and other types of anomalies (Fig. 22).

As with the previous anomaly, so swelling of the insulation plates (A.P5) may also derive from seepages into the system, which justifies the frequent prescription of technique TR-C5 to eliminate its causes. But to deal with the anomaly itself, which generally results from deficient anchoring of the plates to the substrate as well as faulty preparation of the latter, technique TR-C4--Application of new adhesive material and/or mechanical anchors seems like the natural choice (Fig. 22).

Conclusion

There are pathology, diagnosis and repair systems for a variety of construction elements, but in the literature survey performed none was found concerning the evaluation of ETICS.

That was the main objective of this research, aiming at monitoring the performance of ETICS on walls. Furthermore it is expected that some of the difficulties inherent to the need for specialized labour may be eased by creating a plain, concise and innovative document.

Both the system itself and all the assumptions made in its creation (Amaro et al. 2013) were validated and calibrated after field work and statistical post-treatment of the data collected on 146 facades where ETICS had been applied. These statistics concern the performance of the system and made it possible to perfect the process of evaluating and intervening in the system.

The following conclusions can be drawn:

--The commonest anomalies of ETICS in walls (approximately once every two cases) are biological growth, other colour changes and runoff marks, all included in the colour/aesthetic anomalies group; flatness and materials rupture anomalies come second and third respectively (approximately a quarter of the occurrences each);

--The most frequent causes of the anomalies (approximately once every six anomalies) are dirt build-up (dust), surface condensation damp and rain action, and the most prolific groups of causes are external mechanical actions and environmental actions;

--Around two out of five of the anomalies in ETICS can be prevented by proper design, application and choice of materials, which shows the importance of these stages in the service life of ETICS;

--Infrared thermography and contact moisture measurements account each for around one third of all diagnosis methods recommended in the event of an anomaly being found in ETICS;

--The most frequent repair techniques prescribed are those that act on the surface of the system (cleaning and application of surface protection), followed by those that act on the finishing coat (with emphasis on the partial/whole replacement) and only about one fifth of the times does the system core need to be intervened upon (with emphasis on the correction of geometrical constructive features).

References

Amaro, B.; Saraiva, D.; de Brito, J. de; Flores-Colen, I. 2013. Inspection and diagnosis system of ETICS in walls, Construction and Building Materials 47: 1257-1267. http://dx.doi.org/10.1016/j.conbuildmat.2013.06.024

Barreira, E.; Freitas, V. P. 2008. Defacement of ETICS cladding due to hygrothermal behaviour, in Proc. of the 11th International Conference on Durability of Building Materials and Components, Istanbul, Turkey, paper T 24.

Barreira, E.; Delgado, J. M. P. Q.; Ramos, N. M. M.; Freitas, V. P. 2013. Exterior condensations on facades: numerical simulation of the undercooling phenomenon, Journal of Building Performance Simulation 6(5): 337-345. http://dx.doi.org/10.1080/19401493.2011.560685

Daniotti, B.; Paolini, R. 2008. Evolution of degradation and decay in performance of ETICS, in Proc. of the 11th International Conference on Durability of Building Materials and Components, Istanbul, Turkey, paper T 42.

De Brito, J. 2009. Sistemas de inspeccao e diagnostico em edificios [Inspection and diagnosis systems in buildings], in Proc. of the 3rd National Meeting on Pathology and Rehabilitation of Buildings, Porto, Portugal, 13-23.

Duarte, C. 2011. A Europa das argamassas e dos ETICS. Tend?ncias, perspectivas e oportunidades [The Europe of mortars and ETICS. Trends, perspectives and opportunities], in Proc. of the IX SBTA--Brazilian Symposium on Mortars Technology, Belo Horizonte, Brazil, 7-16.

ETAG 004 2000. Guideline for European technical approval of external thermal insulation composite systems with rendering, Brussels, Belgium.

Fernandes, C.; de Brito J. 2012. Solucoes para integracao arquitectonica do sistema ETICS em reabilita?ao [Solutions for architectural integration of the ETICS system in rehabilitation], in 4 Congress on Construction and ETICS, Coimbra, Portugal, 39/2012.

Flores-Colen, I.; de Brito, J.; Freitas, V. P. 2008. Stains in facades' rendering--diagnosis and maintenance technique classification inspection, Construction and Building Materials 22(3): 211-221.

http://dx.doi.org/10.1016/j.conbuildmat.2006.08.023 Freitas, V. P. 2002. Isolamento termico de fachadas pelo exterior--reboco delgado armado sobre poliestireno expandido --ETICS [Thin reinforced render over expanded polystyrene--ETICS], in Report HT 191A/02, MAXIT--Construction and Renovation Technologies, Ltd, Porto, Portugal.

Kunzel, H. M. 1998. Effect of interior and exterior insulation on the hygrothermal behavior of exposed walls, Materials and Structures 31(2): 99-103. http://dx.doi.org/10.1007/BF02486471

Kunzel, H.; Kiinzel, H. M.; Sedlbauer, K. 2006. Long term performance of external thermal insulation systems (ETICS), Acta Scientiarum Polonorum Architectura 5(1): 11-24.

Neto, N.; de Brito, J. 2011. Inspection and defect diagnosis system for natural stone cladding (NSC), Journal of Materials in Civil Engineering 23(10): 1433-1443. http://dx.doi.org/10.1061/(ASCE)MT.1943-5533.0000314

Neto, N.; de Brito, J. 2012. Validation of an inspection and diagnosis system for anomalies in natural stone cladding (NSC), Construction and Building Materials 30(1): 224-236. http://dx.doi.org/10.1016/j.conbuildmat.2011.12.032

Pereira, A.; Palha, F.; de Brito, J.; Silvestre, J. D. 2011. Inspection and diagnosis system for gypsum plasters in partition walls and ceilings, Construction and Building Materials 25(4): 2146-2156. http://dx.doi.org/10.1016/j.conbuildmat.2010.11.015

Sa, G.; Sa, J.; de Brito, J., Amaro, B. 2013. Inspection and diagnosis system for rendered walls, Journal of Civil Engineering (approved for publication).

Silva, J. A. R. M.; Falorca, J. 2009. A model plan for buildings maintenance with application in the performance analysis of a composite facade cover, Construction and Building Materials 23(10): 3248-3257. http://dx.doi.org/10.1016/j.conbuildmat.2009.05.008

Silvestre, J. D.; de Brito, J. 2009. Ceramic tiling inspection system, Construction and Building Materials 23(2): 653-668. http://dx.doi.org/10.1016/j.conbuildmat.2008.02.007

Silvestre, J. D.; de Brito, J. 2011. Ceramic tiling in building facades: inspection and pathological characterization using an expert system, Construction and Building Materials 25(4): 1560-1571. http://dx.doi.org/10.1016/j.conbuildmat.2010.09.039

Stazi, F.; di Perna, C.; Munafo, P. 2009. Durability of 20-yearold external insulation and assessment of various types of retrofitting to meet new energy regulations, Energy and Buildings 41(7): 721-731. http://dx.doi.org/10.1016/j.enbuild.2009.02.008

LIST OF ACRONYMS

A-M--Materials rupture anomalies

A-M1.1--Oriented cracking

A-M1.2--Non-oriented cracking

A-M2--Deterioration of the covering of reinforcement cantilevers

A-M3--Detachment of the finishing coat

A-M4.1--Partial loss of adherence

A-M4.2--Loss of adherence of the whole system

A-M5--Material gap

A-C--Colour/Aesthetic anomalies

A-C1--Efflorescence

A-C2--Runoff marks

A-C3--Corrosion stains

A-C4--Graffiti

A-C5--Biological growth (lichens, fungi, algae, plants)

A-C6--Other colour changes

A-P--Flatness anomalies

A-P1--Flatness deficiency

A-P2--Surface irregularities

A-P3--Joints between plates visible

A-P4--Swelling of the finishing coat

A-P5--Swelling of the insulation plates

C-M--Materials selection

C-M1--Insufficient dimensional stability of the insulation material

C-M2--Inadequate protection against micro-organisms of the finishing biocide

C-M3--Dark or greatly contrasting coatings

C-M4--Metal elements with no protection against corrosion

C-M5--Finishing coat of insufficient permeability

C-M6--Contaminated materials or ones having fabric defects

C-M7--Plates of non-uniform thickness

C-M8--Shrinkage of the base coat

C-C--Design

C-C1--Insufficient thickness of the base coat C-C2--No reinforcement

C-C3--Deficient interface between the system and other elements

C-C4--No primary coat

C-C5--Inadequate design of sills, flashings or on the ground-floor

C-E--Application

C-E1--Inadequate preparation of the substrate

C-E2--Deficient anchoring of the insulation to the substrate

C-E3--Absence of joints between adjacent strengthening profiles

C-E4--Coincidence between the joints of the strengthening profiles and the insulation plates

C-E5--Coincidence of the insulation plates' joints with discontinuities of the substrate

C-E6--Render between the insulation plates

C-E7--Incorrect alignment of the insulation plates

C-E8--Mechanical anchors too tight

C-E9--Deficient treatment of singularities

C-E10--Insufficient overlapping of the reinforcement splices

C-E11--Deficient application of the coating

C-E12--Incorrect application of constructive elements

C-E13--Disregard of the dosages and manufacturers recommendations

C-E14--Deficient overlapping of the finishing coat

C-E15--Deficient execution of flashings

C-E16--Absence of reinforcement cantilever

C-E17--Joints between plates wider than 2 mm

C-A--Environmental actions

C-A1--Strong wind when cladding is applied

C-A2--Exceptionally low temperature during application of the cement-glue or covering

C-A3--Rain

C-A4--Absorption and capillarity damp

C-A5--Infiltration damp

C-A6--Surface condensation damp

C-A7--Atmospheric pollution

C-A8--Low solar exposure

C-H--External mechanical actions

C-H1--Impacts

C-H2--Perforation of the system

C-H3--Human action

C-H4--Anchoring of equipment or scaffolding

C-H5--Substrate settlements

C-H6--Undue boring of the wall

C-H7--Dirt build-up (dust)

C-H8--Splattering at the bottom of the walls

C-H9--Parasitic plants near the facade

C-H10--Parasitic plant growth in the system

C-U--Maintenance

C-U1--Insufficient maintenance

C-U2--Undue intervention

C-U3--Repair

D-S--Sensorial perception tests

D-S1--Crack comparator

D-S2--Crack detection microscope

D-S3--Crack meter

D-S4--Probing

D-M--Mechanical action tests

D-M1--Sphere impact test--martinet baronnie

D-M2--Perforation test (perfotest)

D-M3--Pull-off test

D-H--Hydrodynamic methods

D-H1--Karsten tube test

D-T--Thermal methods

D-T1--Infrared thermography

D-E--Electric methods

D-E1--Contact moisture meter

D-E2--Needles moisture meter

D-U--Ultrasonic methods

D-U1--Ultrasonic pulse velocity equipment

D-Q--Chemical methods

D-Q1--Colorimetric stripes

D-Q2--Field kit

TR-A--Surface

TR-A1--Cleaning

TR-A2--Application of surface protection (water repellent, fungicide, biocide)

TR-B--Finishing coat

TR-B1--Filling/clogging of cracks

TR-B2--Partial/whole replacement of the finishing coat

TR-B3--Application of a new finishing on top of the existing coat/painting

TR-B--System

TR-C1--Protection of protruding edges

TR-C2--Filling of material gaps/perforations

TR-C3--Joint repair

TR-C4--Application of new adhesive material and/or mechanical anchors

TR-C5--Correction of geometrical constructive features

TR-C6--Partial/whole replacement of the system

Barbara AMARO, Diogo SARAIVA, Jorge de BRITO, Ines FLORES-COLEN

Department of Civil Engineering, Architecture and Georesources, Instituto Superior Tecnico, Technical University of Lisbon, Av. Rovisco Pais, 1049-001 Lisbon, Portugal

Received 17 April 2012; accepted 25 May 2012

Corresponding author: Jorge de Brito

E-mail: jb@civil.ist.utl.pt

Barbara AMARO holds a Master's degree in Civil Engineering from Instituto Superior Tecnico, Technical University of Lisbon, Portugal. Her research interests include the life cycle of construction elements.

Diogo SARAIVA holds a Master's degree in Civil Engineering from Instituto Superior Tecnico, Technical University of Lisbon, Portugal. His research interests include the life cycle of construction elements.

Jorge de BRITO is a Full Professor at Instituto Superior Tecnico, Technical University of Lisbon, Portugal. He is a member of CIB W80, W86 and W115. His research interests include the performance, pathology, in situ testing, diagnosis, maintenance, rehabilitation and service life prediction of buildings and construction elements and sustainable construction.

Ines FLORES-COLEN is an Assistant Professor at Instituto Superior Tecnico, Technical University of Lisbon, Portugal. She is a member of CIB W86 and W70. Her research interests include the performance, pathology, in situ testing, diagnosis, maintenance, rehabilitation and service life prediction of buildings and construction elements.
Table 1. Main characteristics of the buildings inspected in the field
work

                              Type        Year of       No. of
                              of use      application   facades

Ed 1--Bairro Alto da Eira

St. Mouzinho de               Housing     2003          12
Albuquerque, Lisbon

Ed 2--Tagus Park--Siza Vieira

Tagus Park, Oeiras            Offices     2008          6

Ed 3--Housing cooperative of Massarelos

Housing cooperative of        Housing     1994          16
Massarelos, St. de
Salgueiro Maia, Porto

Ed 4--FAUP

FAUP, Via Panoramica Porto    Services    1989          20

Ed 5--Outeiro neighbourhood

Bairro do Outeiro/St. do      Housing     2007          15
Mondego, Porto

Ed 6--FEUP--Departments of Engineering

FEUP, St. Dr. Placido         Services    1999          24
da Costa 91, Porto

Ed 7--FEUP--Canteen

FEUP, St. Dr. Placido         Services    2001          2
da Costa, Porto

Ed 8--FEUP--INESC

FEUP--IESCP, St. Dr.          Services    2002          4
Roberto Frias, Porto

Ed 9--FCTUC--Department of Informatics

                              Engineering
FCTUC, Polo II, St.           Services    1994          10
Silvio Lima, Coimbra

Ed 10--FCTUC--Department of Civil Engineering

FCTUC, Polo II, St.           Services    2000          5
Silvio Lima, Coimbra

Ed 11--FCTUC--Department of Electrical and Computers Engineering

FCTUC, Polo II, St.           Services    1996          9
Silvio Lima, Coimbra

Ed 12--Hotel IBIS

Av. Jose Malhoa, Lisbon       Services    2002          1

Ed 13--Museum of Neo-realism

St. Alves Redol, Vila         Services    2007          3
Franca de Xira

Ed 14--Urbanization Quinta Verde

Quinta Verde, Sao Martinho,   Housing     1996          19
Massarelos, Sintra

                              Characterization of
                              the surroundings

Ed 1--Bairro Alto da Eira

St. Mouzinho de               Social neighbourhood with
Albuquerque, Lisbon           some propensity to vandalism

Ed 2--Tagus Park--Siza Vieira

Tagus Park, Oeiras            Detached office building
                              in the Tagus Park complex

Ed 3--Housing cooperative of Massarelos

Housing cooperative of        Housing neighbourhood in a
Massarelos, St. de            very busy urban area
Salgueiro Maia, Porto

Ed 4--FAUP

FAUP, Via Panoramica Porto    University complex in an urban
                              surrounding, with considerable
                              number of trees around it

Ed 5--Outeiro neighbourhood

Bairro do Outeiro/St. do     Housing neighbourhood in a
Mondego, Porto               very busy urban area

Ed 6--FEUP--Departments of Engineering

FEUP, St. Dr. Placido         University complex in an urban
da Costa 91, Porto            surrounding, with considerable
                              movement of people and vehicles

Ed 7--FEUP--Canteen

FEUP, St. Dr. Placido         Canteen of FEUP, protected from
da Costa, Porto               direct human contact. Facades
                              inspected exposed to a
                              watering system

Ed 8--FEUP--INESC

FEUP--IESCP, St. Dr.          Detached building with major
Roberto Frias, Porto          vegetation near one of the facades

Ed 9--FCTUC--Department of Informatics Engineering

FCTUC, Polo II, St.           University complex in a rural
Silvio Lima, Coimbra          surrounding with considerable
                              number of trees around it

Ed 10--FCTUC--Department of Civil Engineering

FCTUC, Polo II, St.           University complex in a rural
Silvio Lima, Coimbra          surrounding with considerable
                              number of trees around it and
                              some movement of people and
                              vehicles

Ed 11--FCTUC--Department of Electrical and Computers Engineering

FCTUC, Polo II, St.           University complex in a rural
Silvio Lima, Coimbra          surrounding with considerable
                              number of trees around it

Ed 12--Hotel IBIS

Av. Jose Malhoa, Lisbon       Hotel in Lisbon in a street with
                              considerable traffic

Ed 13--Museum of Neo-realism

St. Alves Redol, Vila         Museum in Vila Franca de Xira in an
Franca de Xira                urban area with considerable
                              car traffic

Ed 14--Urbanization Quinta Verde

Quinta Verde, Sao Martinho,   Urban development of houses in a
Massarelos, Sintra            rural area with a lot of trees

                              Area
                              ([m.sup.2])

Ed 1--Bairro Alto da Eira

St. Mouzinho de               6080
Albuquerque, Lisbon

             Ed 2--Tagus Park--Siza Vieira

Tagus Park, Oeiras            2750

Ed 3--Housing cooperative of Massarelos

Housing cooperative of        4350
Massarelos, St. de
Salgueiro Maia, Porto

Ed 4--FAUP

FAUP, Via Panoramica Porto    2700

Ed 5--Outeiro neighbourhood

Bairro do Outeiro/St. do      4200
Mondego, Porto

Ed 6--FEUP--Departments of Engineering

FEUP, St. Dr. Placido         6250
da Costa 91, Porto

Ed 7--FEUP--Canteen

FEUP, St. Dr. Placido         150
da Costa, Porto

Ed 8--FEUP--INESC

FEUP--IESCP, St. Dr.          1750
oberto Frias, Porto

Ed 9--FCTUC--Department of Informatics Engineering

FCTUC, Polo II, St.           2850
Silvio Lima, Coimbra

Ed 10--FCTUC--Department of Civil Engineering

FCTUC, Polo II, St.           650
Silvio Lima, Coimbra

Ed 11--FCTUC--Department of Electrical and Computers Engineering

FCTUC, Polo II, St.           1750
Silvio Lima, Coimbra

Ed 12--Hotel IBIS

Av. Jose Malhoa, Lisbon       1000

Ed 13--Museum of Neo-realism

St. Alves Redol, Vila         700
Franca de Xira

Ed 14--Urbanization Quinta Verde
Quinta Verde, Sao Martinho,   1250
Massarelos, Sintra

Table 2. Characterisation of the types of inspection plans

Type of          Periodicity   Minimum/
inspection                     maximum
                               periodicity

Current          Periodic      12 to 24
                                 months

Detailed                       5 to 10
                                 years

Post-            Non-          --
  intervention     periodic

Type of          Objective
inspection

Current          Detect fast-developing
                   anomalies, monitor
                   anomalies detected in
                   previous inspections
Detailed         Monitor anomalies detected
                   in previous inspections,
                   determine their extent,
                   severity and causes
Post-            Verify early degradation
  intervention     due to application errors
                   of the repair techniques

Type of          Method
inspection

Current          Visual observation of ETICS;
                   little equipment needed

Detailed         Visual observation, nondestructive
                   in situ tests, considerable backing
                   in terms of personnel and material

Post-            Visual observation of ETICS;
  intervention     reduced need of equipment

Table 3. Standard inspection file

FILE INSPECTION No.
Person in charge / role:
Objective of the inspection:
Temperature:                     < 5[degrees]   Between 5[degrees]
                                                  and 15[degrees]
Rainfall:                        Nil            Showers
Humidity:                        Low            Medium
I--BUILDING:
I.1--Location:
I.2--Type of use:                               Housing
I.3--Year of construction:
I.5--No. of floors
  above the ground:
I.7--Building configuration:
I.8--Climatic zone:                             Winter:
II.A--INSPECTED ENVELOPE
ETICS:
Type of facade:                                 Front
Facade orientation:
Type of cladding:                               Traditional
Type of finishing:
Exposure to pollution:                          Nil
Type of surroundings:                           Rural
Characterisation of                             Concrete
  the substrate:
Elements within the facade:                     Hanger
Lower tail-end:
III--MAINTENANCE
III.1--Periodicity of
  inspections and/or
   interventions:
III.2--Previous interventions:   Yes   No       III.3--Date
III.4--Technique used:
III.5--Materials applied:
III.6--Means of access for
  inspection/intervention:
OBSERVATIONS:

FILE INSPECTION No.                                    DATE:
Person in charge / role:
Objective of the inspection:
Temperature:                                           > 15[degrees]
Rainfall:                                              Heavy rain
Humidity:                                              High
I--BUILDING:
I.1--Location:
I.2--Type of use:                Commerce              Services
I.3--Year of construction:       I.4--Year of last intervention:
I.5--No. of floors               I.6--No. of facades inspected:
  above the ground:
I.7--Building configuration:
I.8--Climatic zone:              I                     II
II.A--INSPECTED ENVELOPE
ETICS:                           Area of facade:
Type of facade:                  Side                  Back
Facade orientation:
Type of cladding:                Reinforced            Ceramic
Type of finishing:
Exposure to pollution:           Low                   Medium
Type of surroundings:            Urban                 Coastal
Characterisation of              Masonry               Other
  the substrate:
Elements within the facade:      Ventilation system    Lighting system
Lower tail-end:
III--MAINTENANCE
III.1--Periodicity of
  inspections and/or
   interventions:
III.2--Previous interventions:
III.4--Technique used:
III.5--Materials applied:
III.6--Means of access for
  inspection/intervention:
OBSERVATIONS:

FILE INSPECTION No.
Person in charge / role:
Objective of the inspection:
Temperature:
Rainfall:
Humidity:
I--BUILDING:
I.1--Location:
I.2--Type of use:                Other
I.3--Year of construction:
I.5--No. of floors
  above the ground:
I.7--Building configuration:
I.8--Climatic zone:              III
II.A--INSPECTED ENVELOPE
ETICS:
Type of facade:
Facade orientation:
Type of cladding:                Other
Type of finishing:
Exposure to pollution:           High
Type of surroundings:            Other
Characterisation of
  the substrate:
Elements within the facade:      Other
Lower tail-end:
III--MAINTENANCE
III.1--Periodicity of
  inspections and/or
   interventions:
III.2--Previous interventions:
III.4--Technique used:
III.5--Materials applied:
III.6--Means of access for
  inspection/intervention:
OBSERVATIONS:

Table 4. Standard validation file

VALIDATION FILE No.                                        DATE:
Code of each ETICS                                         Hour:
Temperature:         < 5          Between 5[degrees]       > 15
                      [degrees]     and 15[degrees]          [degrees]
Rainfall:            Nil          Showers                  Heavy rain
Humidity:            Low          Medium                   High
                     ANOMALIES DETECTED

NOTES:
CHARACTERISATION OF THE ANOMALIES                          ANOMALIES
(fill only the field that applies to the anomaly)
Location: accessible area1 (AA), non-accessible area (NAA),
  edges (E), near an opening (NO)
Extent: minimum, < 10% (M); low, 10-30 % (L); considerable,
  30-60% (C); high, > 60% (H)
Thickness: thin, < 1 mm (T); medium, 1-2 mm (M); high,
  > 2 mm (H)
Depth: reinforcement (R), insulation (I), substrate (S)
Type of cracking: horizontal (H), vertical (V), diagonal
  (D), reticulated (R), mapped (M)
Aesthetic impact on the fa?ade: low (L), medium (M), high (H)
Coats affected: reinforced coat (R), system (S)
Type of organisms: fungi, (F), lichens (L),
  algae (A), plants (P)
Severity level: (0,1,2)
                     MOST PROBABLE CAUSES                  ANOMALIES

NOTES:
                     AUXILIARY DIAGNOSIS METHODS           ANOMALIES

NOTES:
                     REPAIR TECHNIQUES                     ANOMALIES

NOTES:

Fig. 2. Application of ETICS (in relative area) in Europe in 2008
(Duarte 2011)

Germany          30%
Poland           29%
Czech Republic   12%
Italy            7%
Austria          6%
Slovakia         5%
France           2%
Portugal         1%
Others           8%

Note: Table made from pie chart.

Fig. 4. Age distribution of the sample

1989   20
199    21
1994   26
1996   28
1999   24
2000    5
2001    2
2002    4
2003   12
2007   18
2008    6

Note: Table made from bar graph.

Fig. 5. Anomalies within the sample

A-M1.1   47
A-M1.2   11
A-M2     5
A-M3     6
A-M4.1   1
A-M4.2   0
A-M5     42
A-C1     2
A-C2     63
A-C3     6
A-C4     12
A-C5     81
A-C6     71
A-P1     38
A-P2     48
A-P3     23
A-P4     13
A-P5     7

Note: Table made from bar graph.

Fig. 6. Incidence of the anomalies in terms of probability of
occurring in a facade

A-M1.1   32.2%
A-M1.2   7.5%
A-M2     3.4%
A-M3     4.1%
A-M4.1   0.7%
A-M4.2   0.0%
A-M5     28.8%
A-Cl     1.4%
A-C2     43.2%
A-C3     4.1%
A-C4     8.2%
A-C5     55.5%
A-C6     48.6%
A-PI     26.0%
A-P2     32.9%
A-P3     15.8%
A-P4     8.9%
A-P5     4.8%

Note: Table made from bar graph

Fig. 7. Contribution of each anomaly group to the grand total of
anomalies detected

Flatness anomalies            27%
Materials rupture anomalies   24%
Colour/aesthetic anomalies    49%

Note: Table made from pie chart.

Fig. 8. Absolute and relative incidence of materials selection errors

       Absolute frequency    Relative frequency

C-Ml   15                    3.2%
C-M2   38                    8.0%
C-M3   0                     0.0%
C-M4   5                     1.1%
C-M5   9                     1.9%
C-M6   26                    5.5%
C-M7   0                     0.0%
C-M8   5                     1.1%

Note: Table made from bar graph

Fig. 9. Absolute and relative incidence of design errors

       Absolute frequency   relative frequency

C-Cl   42                   8.8%
C-C2   33                   l6.9%
C-C3   10                   2.1%
C-C4   11                   2.3%
C-C5   58                   12.2%

Note: Table made from bar graph

Fig. 10. Absolute and relative incidence of application errors

        Absolute frequency   Relative frequency

C-El    7                    1.5%
C-E2    4                    0.8%
C-E3    3                    10.6%
C-E4    7
C-E5    0                    0.0%
C-E6    0                    0.0%
C-E7    1                    O.2%
C-E8    0                    0.0%
C-E9    16                   3.4%
C-E10   9                    1.9%
C-Ell   18                   3.8%
C-E12   13                   2.7%
C-E13   15                   3.2%
C-E14   41                   8.6%
C-E15   32                   6.7%
C-E16   2                    0.4%
C-E17   9                    1.9%

Fig. 11. Absolute and relative incidence of maintenance errors

       Absolute frequency   Relative frequency

C-U1   43                   9.0%
C-U2   18                   3.8%
C-U3   64                   13.4%

Note: Table made from bar graph

Fig. 12. Absolute and relative incidence of environmental actions

       Absolute frequency   Relative frequency

C-Al   0                    0.0%
C-A2   3                    0.6%
C-A3   66                   13.9%
C-A4   52                   10.9%
C-A5   23                   4.8%
C-A6   75                   15.8%
C-A7   20                   4.2%
C-A8   21                   4.4%

Note: Table made from bar graph

Fig. 13. Absolute and relative incidence of external mechanical
actions

        Absolute frequency   Relative frequency

C-Hl    41                   8.6%
C-H2    44                   9.2%
C-H3    38                   8.0%
C-H4    18                   3.8%
C-H5    1                    0.2%
C-H6    2                    0.4%
C-H7    98                   20.6%
C-H8    5                    1.1%
C-H9    33                   6'9%
C-H10   4                    0.8%

Note: Table made from bar graph

Fig. 14. Contribution of each cause group to the grand total of
causes attributed

Design                        26%
Maintenance                   14%
Materials selection           16%
Application                   11%
Environmental actions         24%
External mechanical actions   9%

Note: Table made from pie chart.

Fig. 15. Contribution of each cause to each anomaly group

                              Initial stages   Exposure
                              (C+E)            (A+E)

Materials rupture anomalies   57%              33%
Colour/aesthetic anomalies    14%              65%
Flatness anomalies            44%              24%

                              Others
                              (U+M)

Materials rupture anomalies   10%
Colour/aesthetic anomalies    21%
Flatness anomalies            32%

Note: Table made from pie chart.

Fig. 16. Recommended diagnosis methods within the sample

D-S1   52
D-S2   7
D-S3   50
D-S4   45
D-M1   26
D-M2   21
D-M3   10
D-H1   34
D-T1   159
D-E1   155
D-E2   28
D-U1   49
D-Q1   13
D-Q2   13

Note: Table made from bar graph

Fig. 17. Contribution of each method to the anomalies diagnosed

D-S1   11%
D-S2   1%
D-S3   11%
D-S4   9%
D-M1   5%
D-M2   4%
D-M3   2%
D-H1   7%
D0T1   33%
D-E1   33%
D-E2   6%
D-U1   10%
D-Q1   3%
D-Q2   3%

Note: Table made from bar graph

Fig. 18. Contribution of each repair technique group to the grand
total of techniques prescribed

Surface           43%
Finishing layer   34%
System            23%

Note: Table made from pie chart.

Fig. 19. Incidence of the repair techniques prescribed

TR-A1   26.5%
TR-A2   16.1%
TR-B1   5.3%
TR-B2   16.5%
TR-B3   11.9%
TR-C1   1.3%
TR-C2   3.2%
TR-C3   1.6%
TR-C4   0.6%
TR-C5   12.6%
TR-C6   4.0%

Note: Table made from bar graph
联系我们|关于我们|网站声明
国家哲学社会科学文献中心版权所有