The heating load determination of low energy buildings in northern climate.
Venckus, Nerijus ; Bliudzius, Raimondas ; Poderyte, Jurga 等
1. Introduction
The lowest outdoor temperatures reached during the heating season
are used for the calculation of heating load of conventional building.
The heat source power of more substantial buildings (the weight of their
envelopes does not exceed 100 kg/[m.sup.2]) is estimated according to
the temperature of the coldest five-day period, whereas for lightweight
buildings the coldest daily temperature is used (STR 2.09.04:2008,
Appendix 3, Table 3.1). Considering the purpose of the building and the
desired level of comfort, these temperatures may differ as normative
documents present them on a different level of reliability (RSN 156-94
1995). When the power of the heat sources used for heating buildings is
calculated according to the lowest outdoor temperatures, constant indoor
temperature is ensured in the buildings. However, the installation of
high-power heating systems increases the costs of construction and at
the same time reduce the economical load of the under-loaded boiler
(Gimbutis et al. 1993; Ramesh, Dusan 2003; Svencianas, Adomavicius
2011).
Heat loss through the envelopes in low energy buildings is much
lesser than in conventional buildings: the former ones are tight and for
this reason no heat is lost due to over-infiltration (Juodis et al.
2009). A great amount of thermal energy used for heating the ventilation
air is restored having installed a heat recovery system (Chlela et al.
2009). As the outdoor temperature is varied, the change of indoor
temperature of low energy buildings is slower (Ghiaus, Hazyuk 2010; Hens
et al. 2010). Therefore, most probably the use of heating systems based
on the lowest temperatures of the heating season is not required in
order to ensure indoor microclimate conditions (Yang et al. 2011). This
could reduce the costs of heating system installation and increase the
efficiency of the system in operation without worsening the indoor
microclimate conditions in the buildings. Some of the researchers made
studies in determining heating load for the residential buildings by
selecting optimal thickness of the buildings thermal envelope (Daouas
2011), developing complex heating load determination programs using
standard calculations (Petersen, Svendsen 2010; Ogonowski 2010) but also
there is lack of the outdoor temperature determination used in heating
load calculations in Lithuanian climate. For this purpose a research on
the indoor temperature variation of a low energy building was carried
out seeking to develop a heating load calculation method of the heating
systems in such buildings.
2. Factors affecting heating load demand of low energy buildings
One of the advantages of low energy buildings is the stability of
indoor microclimate conditions (Feist et al. 2005). This index depends
on the following: thermal inertia of partitions (Catalina et al. 2008),
the level of thermal insulation of envelopes, tightness of the building,
an efficiency of heating and ventilation systems, indoor temperature and
allowable limits of its variation, as well as the lowest outdoor
temperatures and their periodical duration. The lesser are the heat
losses through the envelopes, the greater is the impact of internal and
solar heat gains on the thermal balance of the whole building; this is
why the gains should not be left out from the calculation of the heating
load of buildings (Oliveti et al. 2011). Having evaluated these gains
and the properties of low energy buildings, both the overall demand for
thermal energy for heating and the demand for the highest heating load,
calculated according to the lowest outdoor temperatures, are diminished.
2.1. Technical properties of low energy buildings
Design documentation of a low energy (passive) building constructed
in 2009 is employed for the present research. The article (Venckus et
al. 2010) provides a detailed discussion on constructional and energy
properties of the building, whereas Table 1 presents geometrical and
Table 2--energy properties of the analyzed building. For the
construction of envelopes, ceramic blocks, concrete and reinforced
concrete as well as thermal insulation layers on the outside were used.
In order to calculate the heating load of this building following STR
2.09.04:2008 (2008), the selected temperature must not exceed the
temperature of the coldest five-day period. This is because the
envelopes of the building belong to the group having external walls
which weight > 100 kg/[m.sup.2], internal partitions--50/ 100
kg/[m.sup.2], floors and ceilings [right arrow] 150 kg/[m.sup.2] (STR
2.09.04:2008; Appendix 3, Table 3.1). Following the methodology in STR
2.09.04:2008 (2008), this building should be equipped with a heating
source of 7.81 kW power.
2.2. Indoor temperature and allowable limits of its variation in
the modeled building
According to the Lithuanian standard HN 42:2009 "Microclimate
in dwellings and public buildings" (2009) and international (ISO
7730:2005) requirements, the conditions of thermal comfort in dwellings
correspond to 20/24 [degrees]C temperature variation interval, while
sufficient conditions are 18/26 [degrees]C during the cold season of the
year. The document CR 1752 of the European Committee for Standardization
(1998) states that the temperature in the premises fulfilling B
conditions has to reach 22[+ or -]2 [degrees]C. Taking into account the
mentioned requirements, a normative temperature of +22 [degrees]C was
selected for the research. The allowable decline of this temperature is
no more than 2 [degrees]C to preserve the required comfort conditions in
the premises.
2.3. Lithuanian climate data
Lithuania belongs to the cold climate zone. Although the average
outdoor temperatures during the heating season only slightly differ in
Lithuania and Central Europe, the periods with the lowest temperatures
possible in Lithuania have the greatest impact on the choice of heating
system power. The climate data recorded by meteorological station of
Kaunas University of Technology Institute of Architecture and
Construction (KTU ASI) show that the lowest temperatures usually occur
in fine weather (Figs 1--4). For this reason, greater heat losses
through the envelopes are partially compensated by solar heat gains,
while in cloudy weather when the intensity of solar radiation decreases,
outdoor temperature does not reach the lowest level. Since no
generalized data on the intensity of solar radiation depending on
outdoor temperatures has been collected yet, the research makes use of
the climate data recorded by KTU ASI meteorological station in 2009 and
2010, namely: the outdoor temperature and intensity of solar radiation.
To compare the obtained results with the results of the currently-used
standard method, a temperature period was composed using the lowest
standardized temperatures for calculation together with the impact of
solar radiation.
The periods of the lowest temperatures composed on the grounds of
KTU ASI meteorological station data:
1. Medium-cold days and period with the least solar radiation in
2009-2010: from 15/12/2009 to 05/01/2010, the lowest recorded outdoor
temperature: -14.6 [degrees]C, duration: 21 days (Fig. 1);
[FIGURE 1 OMITTED]
2. The lowest temperature in 2009. Period 04/01/2009-06/01/2009,
the lowest recorded outdoor temperature: -18.1[degrees]C, duration: 3
days (Fig.2);
[FIGURE 2 OMITTED]
3. The lowest temperatures in 2010. Period: 15/01/2010-02/02/2010;
the lowest recorded outdoor temperature: -23.2[degrees]C, duration: 18
days (Fig. 3);
[FIGURE 3 OMITTED]
4. Theoretically framed period: the coldest theoretically possible
five-day period in Kaunas. Average outdoor temperature: -23.0
[degrees]C; for the modeled period, solar radiation was estimated
according to the data of KTU ASI meteorological station collected on
15/01/2010-02/02/2010, when the minimal temperature of 2010 was reached
(-23.2 [degrees]C). Duration of the period: 5 days (Fig. 4).
[FIGURE 4 OMITTED]
Having analyzed the climate data and established possible variation
limits of indoor temperature in the researched building, a predictive
model of indoor temperature variation of substantially low energy
buildings was developed. The model is used for estimating the efficient
power of the heating system.
3. Modeling the heat-up and cool down processes of the low energy
building
3.1. Calculation method
There were used calculation program to determine the dynamics of
indoor air temperatures change in respect of variation of outdoor
temperature, solar heat gains, thermal inertia of building envelope and
internal mass (partitions, ceiling, floor and furniture). The change of
internal air temperature [DELTA][T.sub.air] after receiving of amount of
thermal energy [DELTA]Q is determined as:
[DELTA][T.sub.air] = [DELTA] Q/[c.sub.p] x [rho] x V (1)
where: [DELTA][T.sub.air]--change of air temperature, K;
[DELTA]Q--thermal balance of indoor space per each time step, J;
[c.sub.p]--specific thermal capacity of air, J/(kg K); [rho]--air
density, kg/[m.sup.3]; V--volume of indoor air, [m.sup.3]. Thermal
balance [DELTA]Q is determined as:
[DELTA]Q = [Q.sub.eXt] + [Q.sub.int] + [Q.sub.wd] + [Q.sub.fl] +
[Q.sub.inf] + [Q.sub.vent] + [Q.sub.ihg] + [Q.sub.shg] + [Q.sub.hs], (2)
where: [Q.sub.ext]--amount of thermal energy from (through)
surfaces of non-transparent areas of envelope (excluding floor), J;
[Q.sub.int]--amount of thermal energy from surfaces of internal
partitions and furniture, J; [Q.sub.wd]--amount of thermal energy from
(through) transparent areas of the envelope, J; [Q.sub.fl]--amount of
thermal energy though the ground, (are taken as stable during one month
period, calculated according to STR 2.05.01:2005 2005), J;
[Q.sub.inf]--amount of thermal energy for air heating due to
infiltration through the envelope, J; [Q.sub.vent]--amount of thermal
energy for heating the air supplied through heat recovery system, J;
[Q.sub.ihg]--amount of thermal energy from internal heat gains (are
taken as stable during whole calculation period), J; [Q.sub.shg]--amount
of thermal energy from solar heat gains, J; [Q.sub.hs]--amount of
thermal energy from heating system, J.
Calculation of amount of thermal energy from (through) all
non-transparent surfaces ([Q.sub.ext], [Q.sub.int]) takes into account
the thermal inertia:
[Q.sub.int,eX] = [h.sub.s] * ([T.sub.s] - [T.sub.air]) *[DELTA]z *
[A.sub.s], (3)
where: [h.sub.s]--indoor surface heat transfer coefficients of
non-transparent envelope and internal partitions and furniture,
W/[m.sup.2]K; [T.sub.s]--thermodynamic indoor surface temperature, K;
[T.sub.air]--thermodynamic indoor air temperature, K;
[[DELTA].sub.z]--time period (calculation time step), s;
[A.sub.s]--surface area, [m.sup.2].
Determination of the indoor surface heat transfer coefficients of
non-transparent envelope and internal partitions and furniture
equivalent was carried out according to:
[h.sub.s] = Nu * ([lambda]/s) + 4[sigma]*[([T.sub.s] +
[T.sub.air]/2).sup.3]/ 1/[[epsilon].sub.1] + 1/[[epsilon].sub.2] - 1 (4)
where: [[epsilon].sub.i]--emissivity of surface; [sigma] =
5.67*[10.sup.-8]--Stefan--Boltzmann's constant; s--thickness of air
boundary layer, m; Nu--Nusselt number calculated according to LST EN
673:2011; [lambda]--thermal conductivity of air, W/(m*K).
Calculation of temperatures dynamics through the cross-section of
enclosure or active surface layer of internal partition and furniture by
use of finite difference calculation method is expressed:
[MATHEMATICAL EXPRESSION NOT REPRODUCIBLE IN ASCII] (5)
where: [DELTA]z--time period (calculation time step), s; [d.sub.n]
thickness of layer between "n" and "n+1" planes, m;
[c.sub.n] specific thermal capacity of the layer between "n"
and "n+1" planes, J/(kg-K); [[gamma].sub.n]--material of the
layer between "n" and "n+1" planes density,
kg/[m.sup.3]; [q.sub.n/(n-1)]--potential of heat flow density between
"n" and "n-1" planes at the time moment after time
period [DELTA]z W/[m.sup.2]; [q.sub.(n-1)/n]--heat flow density between
"n" and "n+1" planes at the initial time moment z,
i.e. the heat flow rate due to temperature difference ([t.sub.n] -
[t.sub.n+i]), W/[m.sup.2].
The amount of thermal energy from (through) transparent areas of
the envelope was calculated neglecting thermal inertia of these
elements:
[Q.sub.wd] = [U.sub.wd] * ([T.sub.air] -
[T.sub.ext)*[DELTA]z*[A.sub.wd], (6)
where: [U.sub.wd]--thermal transmittance coefficient of transparent
elements of envelope, W/[m.sup.2]K; [T.sub.ext]--thermodynamic outdoor
temperature, K; [A.sub.wd]--surface area of transparent elements of
envelope, [m.sup.2].
Thermodynamic outdoor temperature is assumed to change as a cosine
wave around its average value. Following this method, the design outdoor
temperature Text after the period [DELTA]z is expressed according to Eq.
(7) (Fokin 2006):
[T.sub.ext] = [T.sub.a] + [A.sub.e] * cos (2*[pi]/[DELTA]*t). (7)
where: [T.sub.a]--average outdoor temperature, K;
[A.sub.e]--amplitude of outdoor temperature variation, [degrees]C;
[DELTA]z--period of temperature variation, h; t--time from the beginning
of variation, h.
Amount of thermal energy due to infiltration through the envelope
was calculated according to:
[Q.sub.inf] = [C.sub.p] * [rho] * V * ([T.sub.air] - [T.sub.ext]) *
n/3600 * [DELTA]z (8)
where: n--air change rate of the building due to infiltration
through the envelope, 1/h.
Amount of thermal energy for heating the air supplied through heat
recovery system:
[Q.sub.vent] = 1 - [eta]/100 * [c.sub.p]*[rho]*([T.sub.air] -
[T.sub.ext])*L/3600 * [DELTA]z, (9)
where: n--efficiency of heat recovery system, %; L--amount of
supplied fresh air through the heat recovery system, [m.sup.3]/h.
Amount of thermal energy from solar heat gains was calculated using
solar radiation estimated according to the data of KTU ASI
meteorological station collected on 15/01/2010-02/02/2010 (theoretically
framed period, Fig. 4), according to:
[Q.sub.shg] = [summation][q.sub.so] x [DELTA]z x g x [A.sub.gl] x a
(10)
where: [q.sub.so]--solar heat flow density, recalculated from
theoretically framed period taking into account direction of the windows
and doors, W/[m.sup.2]; g--solar heat gain coefficient of the glazing;
[A.sub.gl]--area of the glazed part of windows and doors, [m.sup.2];
a--correction due to shading.
Thermal energy from heating system was taken as necessary amount of
energy to keep the required air temperature in the premises. When amount
of heating energy to reach required temperature in the premises is
bigger than maximum heating power, then the maximum heating power energy
is taken.
3.2. Conditions for selecting of optimal peak power of heating
system in the building
When the rates of heating up and cool down (Figs 5 and 6),
geometrical and thermal characteristics (Tables 1 and 2) of the building
and climatic data on the lowest outdoor temperatures and solar radiation
(Figs 1-4) are known, the influence of the outdoor temperature variation
on the indoor temperature variation can be forecasted. Such forecasts
are invoked to determine the power of the heating system in the
building, taking into account the established microclimate requirements
of the premises. When the heat losses are lesser than the amount of heat
supplied, the premises are assumed to be heated up; conversely, when the
heat losses exceed the power supplied by the heat source, the cool down
of the premises begins.
A limitation of 22 [degrees]C as the highest temperature of
premises was established in the calculations. It can be controlled by an
automatic or mechanical temperature regulation thermostats installed in
the heating system, which prevent the indoor temperature rising above
the set-up temperature ensuring average comfort conditions in the
premises.
3.3. Selection of efficient heating load in the modeling of heating
and cooling processes of the premises
Using the combinations of outdoor temperature and solar radiation,
introduced in Section 2.3, the variation of indoor temperature was
modeled at different powers of the heating system. The modeling results
demonstrated that the greatest indoor temperature variation takes place
when the combination of the outdoor temperature of five day period and
the respective solar radiation intensity (theoretically framed period,
Fig. 4) is used. For this reason, further experiments were carried out
using only this combination of climatic parameters. At the beginning, a
certain power of the heating system was selected so that the indoor
temperature would not drop below 22 [degrees]C (Fig. 5). Next, the power
of the heating system was being reduced until the indoor temperature
declined to 20 [degrees]C (Fig. 6).
The modeling results showed that the indoor temperature of the low
energy building conforms to the limit of the lowest temperature (22
[degrees]C) when the power of the heating system is 4.74 kW (Fig. 5).
This power is 39.3% lesser than the heating load of the building
calculated according to STR 2.09.04:2008 (2008) (7.81 kW).
[FIGURE 5 OMITTED]
When the limit of the lowest allowable temperature is reduced to 20
[degrees]C, comfort microclimate conditions are ensured and the
calculated power of the heating system decreases to 1.52 kW (Fig. 6).
[FIGURE 6 OMITTED]
This power is 80% less than the one calculated according to STR
2.09.04:2008 (2008) and 67.9% less than the power of the heating system
required to ensure the temperature of 22 [degrees]C.
4. Conclusions and recommendations
The methodology presented in this paper may be applied for the
indoor temperature variation forecast of any buildings; however, the
most beneficial effect is achieved when it is used for design of heating
systems of low energy dwellings. In conventional buildings, heat losses
are notably greater than in low energy buildings since in the former,
internal and solar heat gains compensate for a smaller amount of heat
losses than in low energy buildings, which were designed to make the
maximum use of solar energy. The power of the heating system calculated
according to the presented methodology is lesser than the one obtained
applying standard methods. Therefore, there is a calculation-based
possibility of using air heating systems in low energy buildings even
under colder climate conditions. The power of such systems is limited by
technical (restricted temperature of the supplied air) and hygienic
(restricted speed of the air supplied into premises) requirements. On
the other hand, it is recommended to install reserve heat sources in low
energy buildings that would provide heating in case of a heating-cooling
system breakdown. They could also be used in case of extreme low outdoor
temperatures, low intensity of solar radiation and internal heat gains.
5. Conclusions
1. In substantial low energy buildings, the heating load can be
40-80% less than the load calculated following standard methods; such
load would still ensure the established requirements for the thermal
comfort of the building.
2. Lower -power heating systems would operate in nearly-optimal
regime during the major part of the heating season; as a result, a
higher efficiency of the system would be achieved and the total energy
input of the building would decrease.
3. The lowest power of the heating system of the building, ensuring
the established indoor microclimate requirements and verified by the
calculations according to the presented methodology, allow the efficient
use of air and heat recovery systems for heating and cooling, which also
contribute to the reduction of total energy consumption of the building.
doi: 10.3846/13923730.2012.720938
References
Catalina, T.; Virgone, J.; Blanco, E. 2008. Development and
validation of regression models to predict monthly heating demand for
residential buildings, Energy and Buildings 40(10): 1825-1832.
http://dx.doi.org/10.1016/j.enbuild.2008.04.001
Chlela, F.; Husaunndee, A.; Inard, C.; Riederer, P. 2009. A new
methodology for the design of low energy buildings, Energy and Buildings
41(9): 982-990. http://dx.doi.org/10.1016/j.enbuild.2009.05.001 CR 1752
Ventilation for Buildings: Design Criteria for the Indoor Environment.
CEN, 1998. 76 p.
Daouas, N. 2011. A study on optimum insulation thickness in walls
and energy savings in Tunisian buildings based on analytical calculation
of cooling and heating transmission loads, Applied Energy 88(1):
156-164. http://dx.doi.org/10.1016/j.apenergy.2010.07.030
Feist, W.; Schnieders, J.; Dorer, V.; Haas, A. 2005. Reinventing
air heating: convenient and comfortable within the frame of the Passive
House concept, Energy and Buildings 37(11): 1186-1203.
http://dx.doi.org/10.1016rj.enbuild.2005.06.020
Fokin, K. F. 2006. Stroitelnaia teplotekhnika ograzhdaiushchikh
chastej zdanij. Moskva: AVOK:PRES. 287 s.
Ghiaus, C.; Hazyuk, I. 2010. Calculation of optimal thermal load of
intermittently heated buildings, Energy and Buildings 42(8): 1248-1258.
http://dx.doi.org/10.1016Zj.enbuild.2010.02.017
Gimbutis, G.; Kajutis, K.; Krokunis, V.; Pranckunas, A.;
Svenciakas, P. 1993. Silumine technika [Thermotechnics]. Vilnius:
Mokslas. 333 p.
Hens, H.; Parijs, W.; Deurinck, M. 2010. Energy consumption for
heating and rebound effects, Energy and Buildings 42(1): 105-110.
http://dx.doi.org/10.1016/j.enbuild.2009.07.017 HN 42:2009 Gyvenamijii
ir visuomeniniii pastatii patalpi mikroklimatas [Microclimate in
dwellings and public buildings]. Vilnius, 2009. 4 p. ISO EN 7730:2005
Moderate thermal environments -- Determination of the PMV and PPD
indices and specification of the conditions for thermal comfort.
International Standards Organisation, Geneva, 2005. 54 p.
Juodis, E.; Jaraminiene, E.; Dudkiewicz, E. 2009. Inherent
variability of heat consumption in residential buildings, Energy and
Buildings 41(11): 1188-1194.
http://dx.doi.org/10.1016/j.enbuild.2009.06.007 LST EN 673:2011 Glass in
building--Determination of thermal transmittance (U value)--Calculation
method. Lithuanian Standardization Department, 2011. 18 p.
Ogonowski, S. 2010. Modeling of the heating system in small
building for control, Energy and Buildings 42(9): 15101516.
http://dx.doi.org/10.1016/j.enbuild.2010.03.021
Oliveti, G.; Arcuri, N.; Bruno, R.; De Simone, M. 2011. An accurate
calculation model of solar heat gain through gla zed surfaces, Energy
and Buildings 43(2-3): 269-274.
http://dx.doi.org/10.1016/j.enbuild.2010.11.009
Petersen, S.; Svendsen, S. 2010. Method and simulation program
informed decisions in the early stages of building design, Energy and
Buildings 42(7): 1113-1119.
http://dx.doi.org/10.1016/j.enbuild.2010.02.002
Ramesh, K. S.; Dusan, P. S. 2003. Fundamentals of heat exchanger
design. New Jersey: John Wiley & Sons. 976 p. RSN156-94 Statybine
klimatologija [Climatology of buildings]. Vilnius, 1995. 33 p.
STR 2.01.09:2005 Pastatii energinis naudingumas. Energinio
naudingumo sertifikavimas [Energy performance of buildings. Energy
performance certification]. Vilnius: Ministry of Environment of the
Republic of Lithuania, 2005. STR 2.05.01:2005 Pastatii atitvarii
silumine technika [Thermal technique of building envelopes]. Vilnius:
Ministry of Environment of the Republic of Lithuania, 2005.
STR 2.09.04:2008. Pastato sildymo sistemos galia. Silumos poreikis
sildymui [Power of the building heating system. Energy consumption for
the heating]. Vilnius: Ministry of Environment of the Republic of
Lithuania, 2008.
Svencianas, P.; Adomavicius, A. 2011. Inzinerine termodinamika
[Engineering Thermodynamics]. Kaunas: Technologija. 310 p.
http://dx.doi.org/10.5755/e01.9786090200858
Venckus, N.; Bliudzius, R.; Endriukaityte, A.; Parasonis, J. 2010.
Research of low energy house design and construction opportunities in
Lithuania, Technological and Economic Development of Economy 16(3):
541-554. http://dx.doi.org/10.3846/tede.2010.33
Yang, L.; Wan, K. K. W.; Li, D. H. W.; Lam, J. C. 2011. A new
method to develop typical weather years in different climates for
building energy use studies, Energy 36(10): 6121-6129.
http://dx.doi.org/10.1016/j.energy.2011.07.053
Nerijus Venckus (1), Raimondas Bliudzius (2), Jurga Poderyte (3),
Arunas Burlingis (4)
(1,3) Department of Civil Engineering and Architecture, Kaunas
University of Technology, Studentu g. 48, LT-51367 Kaunas, Lithuania
(2,4) Institute of Architecture and Construction, Kaunas University
of Technology, Tunelio g. 60, LT-44405 Kaunas, Lithuania
E-mails: (1) venckus.nerijus@gmail.com; (2)
raimondas.bliudzius@ktu.lt (corresponding author);
(3) jurga.poderyte@ktu.lt; (4) arunas.burlingis@asi.lt
Received 03 Jan. 2012; accepted 01 Jun. 2012
Nerijus VENCKUS. A PhD student of Civil Engineering, researcher at
the Laboratory of Thermal Building Physics of the Institute of
Architecture and Construction, Kaunas University of Technology. Research
interests: unsteady heat transfer, thermal energy balance of buildings.
Raimondas BLIUDZIUS. Doctor, Head at the Laboratory of Thermal
Building Physics at the Institute of Architecture and Construction,
Kaunas University of Technology. Research interests: thermal processes
in buildings, thermal and hydro properties of building materials and
elements.
Jurga PODERYTE. A PhD student of Civil Engineering at Faculty of
Civil Engineering and Architecture, Department of Building Materials,
Kaunas University of Technology, Lithuania. Research interests: heating,
ventilating and air conditioning.
Arunas BURLINGIS. Doctor, Senior research worker of the Laboratory
of Thermal Building Physics at the Institute of Architecture and
Construction, Kaunas University of Technology. Research interests:
thermal techniques in buildings.
Table 1. Geometrical properties of the building used
for modeling of dynamics of indoor temperature
Areas of construction surfaces of the building, [m.sup.2]
Area of external walls 262.8 Area of floor 96.2
Area of partitions 178.6 Area of ceiling 96.2
Area of transparent 59.5 Area of furniture surface 0.5 *
fenestrations
Area of the roof 130.6 for square unit of the
floor, [m.sup.2]/[m.sup.2]
* --for the calculation of active thermal capacity
of internal surface area of the heated premises,
the area of the furniture surface is established
according to STR 2.01.09:2005 (2005).
Table 2. Energy properties of the building
Average thermal transmittance 0.115 Thermal capacity 17.84
of non-transparent areas of external walls,
of envelope, W/[m.sup.2]K MJ/K
Average thermal transmittance 0.79 Thermal capacity 34.29
of transparent areas of of internal
envelope, W/[m.sup.2]K partitions, MJ/K
Air change rate of the 0.39 Time constant of 277
building at 50 Pa pressure active internal
difference, [h.sup.1] surfaces, h
Internal heat gains, 2.1
W/[m.sup.2](Feist et
al. 2005) 2.1