CFD predictions of indoor air movement induced by cold window surfaces/Vesiu langu pavirsiu sukeliamo oro judejimo tyrimai pasitelkiant kompiuterinio modeliavimo metodus.
Jurelionis, Andrius ; Isevicius, Edmundas
Abstract. During the past decades, large windows and glazed facades
have become an important part of modern architecture and they are
designed frequently in both public and residential buildings. However,
besides the positive effect of such a design on building occupants,
large windows may cause thermal discomfort. Cold inner window surface
may generate draught in the occupied zone. Thermal comfort in rooms is
usually assessed by measuring air temperature, relative humidity, air
velocity and heat transfer due to radiation. In this study computational
fluid dynamics (CFD) methods have been used to investigate these
phenomena. Air movement caused by cold vertical window surfaces was
evaluated and its impact on thermal comfort conditions in rooms have
been outlined. Windows of different constructions and having different
heat transmission coefficients were modelled (2.4, 1.6 and 1.0 W/mK).
CFD predictions showed that even in cases of low window thermal
transmittance coefficient (U value), thermal discomfort conditions may
appear in the room if the height of the window is more than 2.0 meters.
Keywords: thermal comfort, air movement, window, downdraught, CFD
modelling.
Santrauka
Dideli langai ir stiklo fasadai tapo neatsiejama siuolaikiskos
architekturos dalis. Jie projektuojami ne tik visuomeniniuose, bet ir
individualiuose namuose. Nekalbant apie teigiamus tokios architekturos
aspektus, dideliu matmenu langai gali tapti siluminio diskomforto
priezastis. Uz patalpos ora vesesnis vidinis stiklo pavirsius sukelia
zemyn nukreipta oro srauta, kuris tam tikru greieiu patenka i zmoniu
gyvenamaja arba darbo zona. Vesiu stiklo pavirsiu sukeltu oro sroviu
intensyvumas priklauso nuo lango siluminiu savybiu, jo konstrukcijos bei
sildymo prietaisu irengimo vietu. Dazniausiai mikroklimato salygos
patalpose vertinamos matuojant oro temperatura, santykini dregni, oro
judruma ir silumos mainus spinduliavimu. Straipsnyje pristatomas
tyrimas, kuriam buvo pasitelktas kompiuterinis oro judejimo modeliavimas
(skaitiniai skysciu ir duju dinamikos metodai). Buvo tiriama oro
judejimo patalpose priklausomybe nuo langu bei stiklo fasadu
konstrukciju ir siluminiu savybiu. Modeliuojant ivertinti trys langu
tipai, kuriu silumos perdavimo koeficientu vertes: 2,4; 1,6 ir 1,0
W/[m.sup.2]K. Rezultatai parode, kad net ir maziausiai silumai laidus
langai gali sukelti neleistina oro judejima patalpose, jei ju aukstis
virsija 2 metrus.
Reiksminiai zodziai: siluminis komfortas, oro judejimas, langai,
skersvejis, kompiuterinis modeliavimas.
1. Introduction
Human thermal comfort is influenced by a combination of physical,
physiological and psychological factors. It is usually assessed by
measuring air temperature, relative humidity, air velocity and heat
transfer due to radiation. Occupants' clothing and activity levels
are taken into account as well. It is documented that unsatisfactory
thermal conditions lead to a reduced performance of office work by
adults and to decreased children productivity in schools (Wargocki et
al. 2005). Even a 1% increase in productivity in commercial buildings
gives a considerable financial benefit (Olesen 2005).
Glazed part of a building envelope has a significant effect on
microclimate and building energy consumption. Windows may cause both
local and overall body thermal discomfort leading to occupants'
dissatisfaction and health problems. As it is well known, window
replacement is a key action solving building refurbishment problems
(Pikutis and Seduikyte 2006). However, large windows and glazed facades
are a part of the modern architecture and they are designed not only in
commercial and public buildings, but in residential buildings as well.
Window induced thermal discomfort can be caused by radiation from
the warmer body to the colder glass as well as by direct solar radiation
through the glazed part of the window. In this paper only thermal
conditions and air movement caused by natural convection were
considered. Such factors as solar radiation and air leakage of the
window are neglected.
In cold periods, temperature of the inner window surface is always
lower than air temperature in the room. Therefore, cold vertical surface
generates downward airflow. Ge and Fazio (2004) found that large tall
windows may generate air speed up to 1 m/s (close to the surface). This
problem is usually solved by installing heating devices below the
windows. Airflow, caused by buoyancy forces, in such cases suppresses
the downdraught effect. Given that the thermal transmission coefficient
of modern windows is quite low (sometimes 1.0 W/[m.sup.2]K and less),
the main objective of this study was to evaluate the scale of
downdraught generated by windows of different constructions. The further
task was to determine if it is necessary to install heating equipment
below windows if its U value is lower than 1.0 W/[m.sup.2]K.
Additionally, an analysis was carried out in several cases with high
rooms having glazed facades (up to 5 m height) with and without
convector heaters below the windows.
2. Factors having major influence on downdraught
The basic factors determining air speed close to the window are the
height of the cold surface and the temperature difference between the
surface and the air in the room. Heiselberg (1994) presented an
empirical equation to calculate maximum air speed (close to the floor
surface). It depends on the distance from the external wall or window (x
value):
[v.sub.max] = 0.055 x [square root of [DELTA][theta] x H], if x
< 0.4 m, (1)
[v.sub.max] = 0.095/x + 1.32 x [square root of [DELTA][theta] x H],
if 0.4 m [less than or equal to] x [less than or equal to] 2.0m, (2)
[v.sub.max] = 0.028 x [square root of [DELTA][theta] x H], if x
> 2.0 m, (3)
where [DELTA][theta] is the temperature difference between the
inner surface of the window or wall and the air temperature in the room,
H--the window or wall height.
The temperature of the inner window surface depends on the outside
air temperature and window heat transmittance coefficient. In this study
it was calculated as follows:
[[theta].sub.si] = [[theta].sub.i] U x ([[theta].sub.i] -
[[theta].sub.e])/[h.sub.si], (4)
where [[theta].sub.i] and [[theta].sub.e] are respectively internal
and external air temperatures, U is thermal transmittance coefficient of
the window glazing and [h.sub.si]--the heat transfer coefficient at the
inner surface of a glazing (considered 7.7 W/[m.sup.2]K).
Three types of window glazing and two cases of external conditions
were analysed in this paper. Old fashioned, modern and well-insulated
window glazing was selected and outside temperatures were set according
to extreme conditions (-20[degrees]C) and average conditions of the
coldest month in Lithuania (-6[degrees]C). Results of the internal
surface temperature calculations for these cases are in Table 1.
The other important factor for air movement induced by cold windows
is window sill or window bay construction. Larsson, Moshfegh (2002)
examined different cases of window installation and came to a conclusion
that the window bay width affects the downdraught in two different ways:
by deflection of the flow and loss of the momentum. The authors also
concluded that although window frame construction is one of the weak
points in terms of heat loss, it has a minor effect on the total
downdraught. Therefore in this work windows were modelled as whole
glazed surfaces without frames.
Manz and Frank (2004) observed that Heiselberg's equations do
not take into account the influence of furniture or of a heating system
or buoyancy flows at heat sources in the room. They concluded that
experiments performed in empty rooms tend to underestimate the maximum
air speed that occurs in real furnished rooms with heat loads.
Consequently, they suggested modifying Heiselberg's correlations by
a factor of 1.5. However, these suggestions were made according to CFD
predictions only. Authors used k-[epsilon] turbulence model for their
study. And although the set of k-a equations are mostly used in room
airflow predictions, it has some limitations in predicting a three
dimensional wall jets as it was described by Schalin and Nielsen (2004).
Accordingly, in this work both correlations presented by Heiselberg and
Manz&Frank are taken into account.
3. Thermal comfort parameters used in this study
In order to evaluate window generated downdraught, air speed
profiles were drawn for the cut planes close to the floor. According to
CEN Report 1752 (1998) and Lithuanian construction regulation standard
STR 2.09.02:2005 (2005), air speed in the occupied zone should be no
more than 0.15 m/s.
Air temperatures were analysed as well as a vertical temperature
gradient. Heat sources in the room were modelled to keep air temperature
at +20 - +24degrees]C. Thermal comfort conditions according to vertical
temperature difference between head and ankles (1.1 m and 0.1 m above
the floor) were considered up to 3[degrees]C.
Thermal comfort indices such as PMV and PPD (both presented by
Fanger, 1972) were calculated using CFD software in this study.
Descriptions of the indices are presented in ISO 7730 (1994) standard.
PMV (Predicted Mean Vote) index indicates the mean response of a
large group of people according to the thermal sensation scale (+3--hot,
+2--warm, +1--slightly warm, 0--neutral, -1--slightly cool, -2--cool,
-3--cold).
Mathematically, PMV index is expressed as follows:
PMV = (0.303 x [e.sup.-0.036 x M] + 0.028) x L, (5)
where M is metabolic rate, L--thermal load defined as the
difference between the internal heat production and the heat loss to the
actual environment for a person hypothetically kept at comfort values of
skin temperature and evaporative heat loss by sweating at the actual
activity level.
The PMV value should be in the range from -0.5 to +0.5.
The PPD (Predicted Percentage of Dissatisfied) value predicts the
number of thermally dissatisfied persons among the large group of people
and is defined as a function of predicted mean vote (PMV):
[MATHEMATICAL EXPRESSION NOT REPRODUCIBLE IN ASCII]. (6)
In order that thermal conditions were kept within comfort limits in
the occupied zone, the PPD value should be less than 10%. It corresponds
to PMV value limits of -0.5 - +0.5.
4. Creating a CFD model
The CFD (Computational Fluid Dynamics) allows solving a set of
partial differential equations to predict fluid velocities,
temperatures, contaminant dispersion etc. The k-[epsilon] turbulence
model with the first order upwind scheme for momentum, turbulence
kinetic energy and turbulence dissipation rate was chosen for this
study. As it was mentioned before, this turbulence model is not very
precise in predicting wall jets. However, the main goal of this study
was to compare environmental conditions in the room in cases of
different window properties. Therefore, k-[epsilon] turbulence model was
considered to be a sufficient one to observe these differences.
[FIGURE 1 OMITTED]
A room with one external wall was created and the heat source was
designed in the centre of this room to cover the heat losses. Air supply
and exhaust openings were modelled on the opposite corners of the room.
The airflow was selected according to air exchange rate requirements for
offices. Three basic models were created (Fig. 1):
1) window installed throughout the whole wall height with no
heating equipment below (heat source imitates person, computer and other
possible heat emitting equipment);
2) the window height is 2.0 m, with a windowsill below it and no
heating equipment under the sill;
3) model similar to the case 2, but radiator is designed below the
window to cover most of heat losses.
All these cases were modelled with three types of previously
mentioned window types (A, B and C) and two external conditions.
The above-mentioned geometries and conditions are relevant to
residential or office buildings. Yet, the results may not be precise for
high glazed facades. Therefore, several cases with high windows (up to 5
m height) and a room twice as big as the previous cases, was also
examined in this work. Fig. 2 shows the view of the analyzed room with
external glazed facade (case 4). Window dimensions were selected 8.0 x
5.0 m. Several heat sources were modelled in order to avoid air movement
created by one powerful source and several cases with or without heating
equipment were modelled. In the case with no heating equipment below the
window, all heat losses were covered by heat sources in the room.
[FIGURE 2 OMITTED]
5. Quality control and validation of CFD model
A hexahedral grid was selected for simulations in this study and
the optimal number of grid cells was defined from 110.000 to 600.000
thousands depending on the case. It was selected considering results of
several simulations with different number of grid cells. The size of the
cells was decreased close to the surfaces (maximum cell height close to
the window was selected 2 cm).
In order to check if the CFD prediction results reflects the nature
of the physical phenomenon, the study performed by Ge and Fazio (2004)
was used. As the authors presented experimental data of the comparable
model, CFD simulations were performed with the same boundary conditions
as were used by Ge&Fazio. U value of the window was selected equal
to 1.53 W/mK, external temperature was set at -18degrees]C. The
geometries of the model were equated to the experimental chamber used by
the authors. Fig. 3 shows the differences between experimental data
performed by Ge&Fazio and CFD prediction results. Air speed values
obtained during the experiment and predicted by CFD differs in the zone
close to the window bay. CFD simulation gives about 15% lower values
close to the window bay. Yet, the shape of the air speed profiles is
analogous. Differences might be caused both by inequalities of the
boundary conditions and prediction errors (limitations of k-[epsilon]
turbulence model). Air velocity vectors and contours at the same and
most critical section is presented in Fig. 4.
[FIGURE 3 OMITTED]
Heiselberg's equation was used in order to check reliability
of the prediction results in the occupied zone.
Fig. 5 shows maximum air speed in the zone close to the floor
calculated according to Heiselberg's equation, Manz & Frank
corrected Heiselberg's equation compared to the simulation results.
CFD model did not show exactly the same results in the zone close to the
window. But 0.5 m distance is usually marked as a border of the occupied
zone. And within this zone the simulation results coincides with
Heiselberg's correlation results quite well.
[FIGURE 4 OMITTED]
[FIGURE 5 OMITTED]
6. CFD prediction results
6.1. Air movement in rooms with glazed facades (up to 3 m height)
CFD predictions showed that even in cases of low window U value
(1.0 W/[m.sup.2]K) thermal discomfort conditions may appear in the room,
if the height of the window is more than 2.0 metres. It is not possible
to avoid cold downdraught if external temperature is -20[degrees]C (Fig.
7). Fig. 6 gives a more detail view of cold air jet development in the
occupied zone.
In cases when a window with the U values up to 1.6 W/[m.sup.2]K is
used, air velocity in the occupied zone exceeds 0.3 m/s. In the 1.5 m
distance from the cold surface, maximum velocity is decreased and the
value is above 0.15 m/s.
[FIGURE 6 OMITTED]
Isosurfaces shown in Fig. 8 reveals that the radius of zone of the
high velocities is quite large. If workplaces would be installed in this
area, occupants would feel draught at the ankle level (0.1 m above the
floor).
These conditions appear also in the case where the outside
temperature is around -6[degrees]C (Fig. 9). In this case the air speed
in the occupied zone is lower, but still it is over 0.15 m/s. Therefore
a window U factor equal to 1.0 W/mK is not a sufficient value to prevent
the draught in the occupied zone.
6.2. Air movement in rooms with traditional window installation
Window height of 2.0 metres was selected for this case and window
sill together with window bay forms a plane obstacle for the dropdown
air jet. Fig. 8 shows the air speed values in the centre plane of the
room in cases with different window heat transmittance coefficients.
Both in case when U value is 2.4 W/[m.sup.2]K and 1.6 W/[m.sup.2]K,
air speed in the occupied zone exceed 0.15 m/s. But in case when well
insulated window glazing is used (U = 1.0 W/[m.sup.2]K), the draught
appears only in the zone close to the windowsill.
0.5 m from the edge of the windowsill is the safe distance for
workplace set up. The maximum air speed in the occupied zone, when
highly insulated windows are used, is around 0.12 m/s. And this speed
will appear only in case of extreme outside conditions (external
temperature was set at -20[degrees]C).
6.3. The effect of heating equipment on air movement in rooms
Installation of heating equipment has a significant impact on
thermal comfort conditions in rooms. It depends on thermal properties of
the window, heat load emitted by the heating device as well as the
geometry of the windowsill. Fig. 10 shows an isosurface where air speed
is equal to 0.15 m/s in the room with radiator below the sill.
[FIGURE 7 OMITTED]
[FIGURE 8 OMITTED]
[FIGURE 9 OMITTED]
[FIGURE 10 OMITTED]
[FIGURE 11 OMITTED]
In case when the sill covers fully the width of the radiator and
conventional (U = 1.6 W/[m.sup.2]K) window is installed, air speed in
the occupied zone is distinctly above 0.15 m/s. Besides, it does not
drop directly to the floor area, but moves straight to the occupied
zone. Fig. 12 shows the air speed vectors determined by the air
temperatures and windowsill geometry.
In order to neutralise dropdown of the cold air, less extensive
sill design was chosen but the prediction results were quite similar to
the ones presented in Figs 11 and 12. Therefore openings or a grill
should be made in the windowsill to prevent the formation of the jet.
This solution was examined by Ruegg et al. (2001). Authors described the
possibilities to use grills and openings in order to avoid draughts in
the occupied zone as well.
[FIGURE 12 OMITTED]
6.4. Thermal comfort conditions in buildings with traditional
window installation and glazed facades (up to 3 m height)
CFD predictions showed that even in cases of low window U value
(1.0 W/[m.sup.2]K), thermal discomfort conditions may appear in the room
if the height of the window is more than 2.0 m. Fig. 13 shows simulation
results for two cases with well insulated windows. This study revealed
that heating devices are needed to prevent the downdraught in rooms of
buildings with glass facades. Otherwise, percentage of persons
dissatisfied with thermal comfort conditions (PPD value) will be much
higher than recommended 10% limit.
However, using of highly insulated glazing seems very reasonable in
case with traditional window installation. Such decision improves
thermal conditions in the room significantly and PPD value does not
exceed 10%.
6.5. Air movement in rooms with large and tall glazed facades (up
to 5 m height)
Previously presented data gives the view of window induced air
movement in rooms of lower height than 3 metres. Therefore in this work
we also included several simulations in order to predict the influence
of cold window surface on thermal comfort in high rooms (up to 5 m). As
a result, it is possible to make conclusions about the corresponding
conditions in public buildings such as shopping centres, exposition
halls, swimming pools etc.
A room with glazed facade was modelled for that (Fig. 2) and three
cases were analysed. Firstly, a well insulated window (U = 1.0
W/[m.sup.2]K) was simulated without any heating equipment below it. All
heat losses were covered by heat sources in the room. CFD prediction
results showed that speed of the cold air jet reaches up to 0.3 m/s in
the occupied zone. Afterwards a case with heating convector device below
the window was simulated with anticipation that the cold air dropdown
problem will be solved this way. Yet, CFD modelling results showed that
in case of such window height, air jet caused by buoyancy forces is
insufficient to suppress the draught in the room.
[FIGURE 13 OMITTED]
Examined the most distinctive section in the rooms seems to be the
section close to the floor. Fig. 14 shows air speed in the 0.1 m height
above the floor in these two cases. Air temperature contours and air
speed vectors presented in Fig. 15 shows that if heating equipment is
installed in the typical 10 cm height above the floor, cold air effuses
below the air heater and the draught zone forms.
[FIGURE 14 OMITTED]
[FIGURE 15 OMITTED]
[FIGURE 16 OMITTED]
The best method to solve this problem in high rooms seems to be
creating a warm air jet directed against the cold window air dropdown.
Such heating equipment as floor convectors with fans or other mechanical
air supply devices should be used (Fig. 16).
Fig. 17 shows air speed contours in previously described cases with
or without heating equipment below the high glazed facade compared to
the case when room heating is implemented by means of floor heater
equipped with fan.
Warm air is supplied against the cold air jet at the speed of 1.0
m/s. This speed is sufficient to suppress the cold air dropdown (window
U value is 1.0 W/[m.sup.2]K and external temperature was selected
-20[degrees]C) (Fig. 14).
In this case it is important to install extensive heating equipment
below the window. In the presented case floor convector with a smaller
width compared to the window width was modelled. Therefore two zones of
thermal discomfort emerged in the window border regions.
7. Conclusions
According to the results of CFD simulations the following
conclusions were drawn.
1. Thermal discomfort conditions may appear in rooms even in cases
when well insulated windows are used (U value is 1.0 W/[m.sup.2]K), if
the height of the window is more than 2.0 metres. Whereas high glazed
facades (up to 5.0 metres) may cause significant draught in the larger
half of the occupied zone. Therefore modern windows whose thermal
transmission coefficient equals 1.0 W/[m.sup.2]K should be considered as
potential draught generators as well, if external temperature is lower
than -5[degrees]C. However, well insulated windows showed good results
in case of traditional residential window installation. In this case
heating equipment is not necessary to prevent draught in the occupied
zone (U value is 1.0 W/[m.sup.2]K and window height is about 1.5 m).
2. Installation of heating equipment below the windowsill can have
a crucial effect on air movement. It might create two air jets (warm jet
and cold jet) which mix and flow directly into the occupied zone. In
order to avoid this phenomenon, openings or grills should be installed
in the windowsills.
[FIGURE 17 OMITTED]
3. Free standing heating convectors do not suppress the dropdown
air jet if the height of the glazed facade is about 5 m or higher even
in case when well-insulated windows (U value is 1.0 W/[m.sup.2]K) are
used. As these units are usually installed at 10 cm height above the
floor (mounted on the stalks), cold air effuses below the air heaters
and still it causes draught in the occupied zone. The best heating
equipment to solve this problem seems to be floor heaters with fans.
Surely there are more factors which should be taken into account in
order to draw the final conclusions. Air leakage should be considered as
well as effects of ventilation system performance (air distribution
method, supply air temperature etc). In this study, some limitations of
k-[epsilon] turbulence model were experienced in the zone close to the
window surface. Field measurements and experiments are needed to get
more precise results and to analyse the combinations of the factors
mentioned above. Some of the errors might be eliminated by precise
definition of the [h.sub.si] value, which represents heat transfer
coefficient at the inner surface of a glazing. As it is directly
influenced by air movement on the surface of the window, it may be
defined in the CFD according to the experimental data obtained in
accordance to different window constructions and thermal properties.
In order to analyse local thermal discomfort close to the windows,
draught rate (DR) index should be calculated as well. This would allow
assessment of thermal conditions including evaluation of air turbulence
intensity.
Received 11 Apr. 2007; accepted 7 Feb. 2008
References
Ge, H.; Fazio, P. 2004. Experimental investigation of cold draft
induced by two different types of glazing panels in metal curtain walls,
Building and Environment 39: 115-125.
Heiselberg, P. 1994. Draught risk from cold vertical surfaces,
Building and Environment 29: 297-301.
Larsson, U.; Moshfegh, B. 2002. Experimental investigation of
downdraught from well-insulated windows, Building and Environment 37:
1073-1082.
Manz, H.; Frank, T. 2004. Analysis of thermal comfort near cold
vertical surfaces by means of computational fluid dynamics, Indoor Built
Environment 13: 233-242.
Olesen, B. W. 2005. Indoor Environment--Health--Comfort and
Productivity, in Proc of the 8th REHVA World Congress CLIMA 2005,
Lausanne, Switzerland, 9-12 October, 1-17.
Pikutis, R.; Seduikyte, L. 2006. Estimation of the effectiveness of
renovation work in Lithuanian schools, Journal of Civil Engineering and
Management 12(2): 163-168.
Ruegg, T.; Dorer, V.; Steinemann, U. 2001. Must cold air down
draughts be compensated when using highly insulating windows? Energy and
Buildings 33: 489-493.
Schalin, A.; Nielsen, P. V. 2004. Impact of turbulence anisotropy near walls in room airflow, Indoor Air 10.1111 1600-0668.
Wargocki, P.; Wyon, D. P.; Matysiak, B.; Irgens, S. 2005. The
Effects of Classroom Air Temperature and Outdoor Air Supply Rate on the
Performance of School Work by Children, in Proc. of the 10th
International Conference on Indoor Air Quality and Climate, Indoor Air,
Beijing, China, 4-9 September, 2005, 368-372.
CEN Report CR 1752:1998 Ventilation for Buildings--Design criteria
for the indoor environment. Brussels, 1998. 11 p.
ISO 7730:1994(E) International Standard. Moderate thermal
environments--determination of the PMV and PPD indices and specification
of the conditions for thermal comfort. Geneve, 1994. 29 p.
STR 2.09.02:2005 Heating, ventilation and air conditioning.
Construction regulation. Vilnius, 2005. 31 p.
Andrius Jurelionis (1), Edmundas Isevieius (2)
Kaunas University of Technology, Faculty of Civil Engineering and
Architecture, Studentu g. 48, 51367 Kaunas, Lithuania. E-mail: (1)
andrius.jurelionis@ktu.lt; (2) edmundas.isevicius@ktu.lt
Andrius JURELIONIS. Lecturer of the Dept of Geotechnical
Engineering at Faculty of Civil Engineering and Architecture, Kaunas
University of Technology. Member of International Society of Indoor Air
Quality and Climate (ISIAQ). His research interests include development
of efficient heating and ventilation systems, evaluation and improvement
of thermal comfort and indoor air quality conditions in buildings.
Edmundas ISEVIEIUS. Associated Professor and Head of the Dept of
Geotechnical Engineering in Faculty of Civil Engineering and
Architecture, Kaunas University of Technology with over 30 years of
experience in research and design of air conditioning systems in
buildings, author of the book "Air Conditioning" (in
Lithuanian). His research interests include investigations of heat and
moisture processes and control methods in buildings, development of
energy efficient ventilation and air conditioning systems.
Table 1. Calculated inner window surface temperatures
that were used as the boundary conditions in CFD
(subscripts indicates temperature difference between the
inside air and the outside air)
Inner Inner
surface surface
U value, temperature temperature
Window type W/ [[theta].sub.si] [[theta].sub.si]
[m.sup.2]K 40, [degrees]C 26, [degrees]C
A Old fashioned, 2.40 +7.5 +11.9
double glazed
B Conventional, 1.60 +11.7 +14.6
double glazed
with argon gas
between the
panes and
emissive
layer coating
C Well insulated, 1.00 +14.8 +16.6
triple glazed
with krypton
gas between the
panes and
emissive layer
coating