Experimental investigation into fire resistance of HC-FST columns under axial compression.
Blazevicius, Zygimantas ; Kvedaras, Audronis Kazimieras
Abstract. A certain amount of analytical methods for determining
fire resistance of concrete filled steel tubular columns are developed.
Mostly those methods refer to or have as an origin the data about the
results of real experiments. The research work on this kind of composite
column behaviour under fire conditions with a wide range of different
parameters measuring was performed. The behaviour of 16 axially loaded
HC-FST (hollow concrete filled steel tubular) columns without fire
protection under conditions similar to ISO-834 fire and under normal
conditions was experimentally investigated and the results are presented
in this paper. The experimental values of fire resistance were measured
and the failure mode was determined for 4 axially loaded columns. And
for the comparison of test parameters, 4 axially loaded HC-FST columns
were tested under normal conditions. In addition, 8 hollow
concrete-filled steel tubular stub columns and 4 hollow concrete tubular
stub columns under normal conditions were tested. The final objective
was to prepare experimental data for analysis and to find some
analytical dependence between test parameters with the most significant
influence on the fire results of HC-FST columns.
Keywords: experimental investigation, axial loading,
concrete-filled steel tubular columns, load bearing capacity, fire
resistance.
1. Introduction
The use of HC-FST (Hollow Concrete-Filled Steel Tubular) columns
has become widespread in the countries, where it is used for building
tall buildings. The presence of load bearing concrete within a hollow
steel column has a beneficial effect on the fire resistance of the steel
section. In many cases the required period of fire resistance can be
obtained by concrete filling without the need for external protection.
Some researches [1, 2] were performed to find assumptions or
initial data necessary for creating methods to determine the fire
resistance of C-FST columns. Some information about this kind of
experiments--testing course and the results is given in [3, 4]. The
comparison [5] of the results obtained using different analytical
calculation methods shows quite a significant difference. The simple
empirical expression for determination of HC-FST column compressive resistance under fire conditions is given in [6]. Some analytical
expressions for analysing HC-FST column work under fire conditions is
given in [7]. The method for prediction of fire resistance of HCFST
columns and based on the results of laboratory tests is presented in
[8].
There is still a need for right and real experiments to collect
more experimental research data and to develop more accurate calculation
methods for the fire design of composite structures. Thus, the main
objectives of the experimental program and this paper are threefold: 1)
to describe a series of tests on composite columns exposed to standard
fire and subjected to axial load, 2) to develop a mechanics model for
HC-FST columns exposed to standard fire, 3) to prepare experimental data
for analysis of the influence of the changing sectional dimension of
column--thickness of the hollow concrete core on the fire resistance of
structure.
2. The object of experimental studies
Experiments intended for determining the resistance of structures
to mechanical effects under heat conditions, and heat-involving in-place
experiments in general are specific and require special equipment,
preparation and methods. Due to their complexity, similar studies
(involving natural-size building constructions) in Lithuania and the
neighbouring countries are carried out but seldom.
The object of the experimental studies is loadcarrying capacity
under axial compression and the behaviour of HC-FST elements with a
hollow centrifugal concrete core under ambient conditions and at
elevated temperatures. Thus two types of tests were carried out:
"I"--determination of compressive resistance of an HCFST or HC
specimen loaded with axial load under normal ambient conditions,
"II"--determination of HC-FST specimen fire resistance under
axial load and elevated temperature conditions. In pursuance of the
study programme 20 HC-FST and HC (hollow concrete) specimens were tested
under ambient and elevated temperatures. The specimens were manufactured
by cutting long columns. These columns consisted of steel pipes welded
with a spiral weld, inside which a hollow concrete core was formed by
centrifuging. The outer diameter of the steel pipe was 219 mm, and the
wall thickness was about 1,6 mm. The centrifuged concrete core of the
columns from which the HC-FST and HC specimens were cut, was of variable
thickness: at the opposite ends of the column the thickness of the
concrete core varied between 46 and 17 mm. The initial length of the
elements was up to 5,5 m, their age was approx 15 years by keeping them
under outdoor conditions without additional protective measures against
steel corrosion and concrete erosion.
12 short (300 mm) and 12 long (2000 mm) HC-FST elements were
fabricated by cutting them from the initial length elements. It was
intended to test 4 long (2000 mm) HC-FST specimens for compressive
resistance under ambient conditions and 4 long HC-FST specimens for fire
resistance. Also 8 short HC-FST specimens of 12 were used to determine
their resistance to axial compression, whereas 4 of them were used to
produce concrete rings, which were also tested to define concrete
resistance to axial compression. HC-FST and HC specimens under
consideration are shown in Fig 1.
[FIGURE 1 OMITTED]
3. Preparation of specimens
The cutting machine with a special abrasive discs was used for
cutting the initial length HC-FST elements to shorter ones. During
cutting, the initial-length HC-FST elements were laid on cylindrical guides, which rotated the tubular element round its axis in respect to
the rotating cutting disc. The above-mentioned equipment ensured the
perpendicularity of the ending cross-section. For cutting the steel
shell and the concrete core, cutting discs designed for cutting steel
and concrete of the same thickness respectively were used. Disparities
on the specimen edges remaining after cutting were removed by grinding
with an abrasive disc until even bearing surfaces (with a tolerance of
0,2 mm) were formed. The column cutting machine is shown in Fig 2.
[FIGURE 2 OMITTED]
In order to determine the mechanical characteristics of steel, 16
standard steel specimens were prepared and tested for draught
resistance. The specimens were produced from the steel shell of the
parts of HC-FST. The manufacturing and testing the specimens were
carried out in compliance with the requirements applicable to such tests
according to a standard [9]. In order to determine the mechanical
characteristics of concrete, 4 short HC specimens were manufactured by
removing the steel shell from HC-FST elements and cutting them to the
foreseen length. The geometrical parameters of HC-FST and HC specimens
and intended type of testing are in Table 1.
4. Test equipment and procedures
All the specimens for the experiment were prepared, and the tests
were carried out in the laboratories of the Faculty of Civil Engineering
of Vilnius Gediminas Technical University in accordance with the
requirements [10, 11], as it was possible to do. The longitudinal load
of the HC-FST and HC specimens was created by a hydraulic jack with a
capacity of 500 tons and with a 3-ton measuring scale. The heat
conditions were created by the electrical furnace "Utena"
designed and manufactured specifically for tests for combustibility and
fire resistance of building constructions with natural geometrical
parameters. The furnace chamber has a floor area of 400 mm x 400 mm and
is of 1400 mm high. The interior faces of the chamber are lined with an
insulating material-caolin wool plates. And the electric spiral collars
are embedded in vertical plates of caolin with the interval of 5 cm
beside the surface, closer to the furnace chamber. The furnace
temperature is measured by three inner platinum-rhodium thermocouples
that were also embedded in the kaolin insulation of chamber. According
to the defined programme and the indications of inner thermocouples, the
temperature regime is maintained and automatically adjusted with the aid
of heating controller PROTERM 100. This controller can regulate
temperature in three levels of the furnace chamber: top, middle height
and bottom levels. The temperatures measured by three inner
thermocouples were averaged automatically and the average temperature
was used as the criterion for controlling the furnace temperature.
4.1. Test under normal conditions--type I test
Equipment for type I test. 4 short HC, 4 short HC-FST and 4 long
HC-FST specimens were prepared for type I test. The specimens ends were
rested against rigid steel press plates of 50 mm thickness, fixed in the
press body via a hinged support. Between the ends of the specimen and
press plates, aluminium spacers were placed (they were cut from
medium-hard aluminium sheet of 1 mm thickness). The fixing scheme of the
specimen ensured the articulating the support and uniform application of
the pressure to the relatively even ground (with a tolerance of 0,2 mm)
bearing cross-section of the element.
For strain measuring of the specimens, 8 PKB-type, 50-mm basis
length strain-gauge transducers each were attached to the outer surface
of the HC and HC-FST elements in the middle part of the height. 4
transducers were attached to the specimen in the vertical direction for
measuring longitudinal deformations, and 4 transducers--in the
horizontal direction for measuring transversal deformations. The
transducers were connected with the universal data acquisition system
ALMEMO 5590-2.
For measuring horizontal displacements of the middle part of the
HC-FST specimens, electronic displacement indicators were used. They
were also connected to the universal data acquisition system ALMEMO
5590-2 and fixed independently of the specimen and the press. The
specimen fixing scheme is given in Fig 3.
[FIGURE 3 OMITTED]
The process and measuring of type I test. In respect of every
specimen, the concentricity of the load was checked before applying a
breaking load to the specimen. The specimens centring was effected by
applying a load equal to up to 30 % of the expected load-bearing
capacity and by comparing the readings of the strain-gauge transducers
measuring strain. In case of large differences in the readings of
strain-gauge transducers attached to the opposite sides of the element,
the specimen supporting point was adjusted accordingly. After centring
the specimen, the load was increased and the measuring was carried out
from the beginning (at the load value of 0-0,5 ton). The average speed
of load application was 2,0 kN/min. The load was increased gradually in
3-ton stages, whereas the readings of the strain-gauge transducers and
displacement measuring devices were recorded at every stage of the load.
Under the conditions of a load next to the strength limit of the
specimen, the readings of the strain-gauge transducers and the shear measuring devices were recorded every 0,5-1,0 ton. All specimens were
subjected to testing until they collapsed.
The standard steel specimens were tested by a 250 kN-capacity
traction machine available at the laboratory of the Dept of Steel and
Timber structures of the VGTU. The compressive resistance of concrete
was determined on the basis of the test results of 4 short HC specimens.
Experimental results and specimens behaviour during the test under
ambient conditions. The HC specimen failure occurs after developing
longitudinal cracks in the hollow concrete core. The failure mode of
both short and long HC-FST type specimens is quite similar. The
specimens lost their load-bearing capacity upon local buckling of the
thin-walled steel shell and the hollow concrete core at the ends of the
specimen at one of the press plates. The specimens 5T2 (with parameters
L / [t.sub.c] / [t.sub.s]--296 mm / 24,4 mm / 1,63 mm), 4T1 (with
parameters L / [t.sub.c] / [t.sub.s]--298 mm / 19,1 mm / 1,63 mm) and
1I1 (with parameters L / [t.sub.c] / [t.sub.s]--2004 mm / 20,1 mm / 1,65
mm) are selected to demonstrate a typical failure mode of the specimens
tested under ambient conditions (shown in Fig 4). Measuring the
horizontal displacement of long HC-FST specimens in their middle height
results in a very insufficient displacement, which cannot be related to
the beginning of the overall buckling of the specimen. The values of the
longitudinal and transversal strains measured at the surface of the
steel shell of the HC-FTS specimens in relation to [N.sub.tr]/[N.sub.u]
are given in Fig 5. The main parameters of the test are presented in
Table 2. The recorded mean values of normal ultimate stresses of the HC
specimens--[[sigma].sub.u.m] = 45,44 MPa. The mean normal ultimate
stresses were calculated according to the formula:
[[sigma].sub.cr] = [N.sub.cr] / [A.sub.c], (1)
where: [N.sub.cr]--critical experimental load applied to the
specimen; [A.sub.c]--the cross-section area of the concrete core of the
specimen. According to [12, 13], the ring strength of the concrete can
be equated with specific compressive prism strength of
concrete-[f'.sub.c.m].
[FIGURES 4-5 OMITTED]
The mean trial limit value of steel yield was [f.sub.y.m] = 318,3
MPa, whereas the mean trial limit value of steel strength was
[f.sub.u.m] = 358,3 MPa.
4.2. Fire resistance determination--fire resistance test
The equipment for fire resistance test. 4 long HCFST specimens were
prepared for testing. The specimens were tested under compressive axial
load, and simultaneously supplying heat to them (simulated working of
the building structure under the fire conditions). An electric
"Utena 1" heating furnace was used for heating. The specimen
and the furnace were placed on the lower support plate of the press. For
avoiding additional heat losses through non-insulated points of the
specimen and obtaining a more uniform distribution of temperature along
the construction, the specimen ends protruding from the heating chamber
of the furnace (at the top and bottom) were covered with a mineral wool
mat of 50 mm thick. At one end of the specimens notches were made, which
formed openings with the cross-section area--0,25 [cm.sup.2]. The
openings function was to let water steam that got formed in the inner
cavity of the specimen and the concrete of the core during the heating
escape. The furnace temperature was measured by stationary
platinum-rhodium thermocouples and by using a portable furnace
thermocouple connected to the universal data acquisition system ALMEMO
5590-1. Three stationary furnace thermocouples were installed in the
heat-insulating layer of kaolin wool in one of the walls of the heating
chamber (at the upper, middle and lower zones of the heating chamber).
The measuring accuracy of the stationary furnace thermocouples was 5
[degrees]C within the measuring range over 300 [degrees]C. The measuring
accuracy of the portable thermocouple was 0,1 [degrees]C within the
measuring range 0 to 1200 [degrees]C.
The trial temperature regime of the furnace was maintained using a
3-channel programmable temperature controller "PROTERM-100".
The function of the temperature controller is to maintain the trial
temperature regime uniform within all the levels of the furnace (lower,
middle and upper). During the test all the efforts were made to maintain
the temperature regime as close as possible to the standard fire regime
stated in ISO-834. The scheme of the specimen installation is in Fig 6.
[FIGURE 6 OMITTED]
The process and measuring of type II test. The purpose was to
determine the fire-resistance of the specimen, ie the time within which
the construction reaches its ultimate state under the fire temperature
conditions. For three of the four HC-FST specimens, the selected
compressive load value was 25 ton, ie approx 40 % of the mean
load-bearing capacity of the specimens tested under normal conditions,
whereas for one of 4 specimens an 18-ton axial load was applied.
Following the specimen centring procedure, the specified load was
applied to the specimens, and then the heating procedure was commenced,
ie the time relay of the furnace temperature controller started. The
preliminary compression of a specimen was carried out by raising it with
the lower press plate, onto which the furnace body and the specimen
rested.
The furnace temperature controller was programmed in such a manner
that the mean temperature of the furnace was close to the standard
(according to ISO-834) temperature--time curve, the analytical
expression of which is given in formula 2.
t = 345 [log.sub.10] x (8T + 1) + 20, (2)
where t--the mean temperature of the furnace in degrees Celsius;
T--time in min.
The standard temperature-time curve (according to ISO-834) and the
curves of the temperature regime created during the test in the most
heated point of the furnace are given in Fig 7.
[FIGURE 7 OMITTED]
Due to a high temperature, it was not possible to carry out
measuring the deformations of the specimens on the steel shell surface.
However, the behaviour of the specimen and the abundance of the
production of the water steam were monitored throughout the test. The
temperature measured by stationary thermocouples was recorded every 5
min and by the portable thermocouple was recorded every 30 sec. Most of
the time, the portable thermocouple was inserted into the test chamber
at its middle. The curves with code descriptions of the specimens were
obtained on the basis of furnace (in the most heated chambers place)
temperature measuring readings during the testing of corresponding
specimens. At a later time, the local buckling of the specimen would
occur at this place or in its vicinity. The curves given in the diagram
show that after 7 min from the start of testing the temperature in the
most heated zone of the furnace was higher than the temperature
according to the standard fire curve.
Experimental results and the failure mode after the test at
elevated temperatures. As an experimental fire resistance of the
specimen, the time from the start of the test to the specimen failure
moment was taken. As the failure criterion for the fire resistance test,
the moment at which the irreversible decreasing of load carrying
capacity of the specimens began was taken.
Abundant production of water steam would start 7 min on average
from the commencement of the test (when the mean temperature of the
heating chamber of the furnace would reach 550 [degrees]C), and it would
cease approx 30 min on average after the test commencement.
Insignificant production of water vapour continued throughout the test.
In the most heated zone of the furnace, the steel shell of some
specimens would buckle locally within 25-45 min from the start of the
test. Due to this factor, the redistribution of stresses in the
cross-section of the composite element occurs. Upon the reduction of
longitudinal stresses in the steel shell, the longitudinal deformation of the element increased considerably. The same phenomenon was recorded
evidently due to a visibly increased stroke of the press required to
maintain a load of the same quantity. In certain cases, the sound of the
buckling steel shell could be heard.
The maximum temperature in the heating chamber of the furnace
during the test was as high as 1240 [degrees]C. The failure mode of the
specimens was not a typical failure mode of overall buckling of long
elements, viz columns. The failure mode of the specimens can be
described as the loss of load-bearing capacity following the local
buckling of the thick-walled steel shell and the concrete core, at the
most heated point of the specimen or in its vicinity. The principal
recorded parameters of the test are given in Table 2.
The specimens 4I2 (with parameters L / [t.sub.b] / [t.sub.s]--2000
mm / 33,7 mm / 1,63 mm) and 0I1 (with parameters L / [t.sub.b] /
[t.sub.s]--1000 mm / 27,2 mm / 1,60 mm) are selected to demonstrate the
typical failure mode of the specimens tested under fire conditions (Fig
8).
[FIGURE 8 OMITTED]
It is not dimensional parameters, but it was apparently seen that
the colour of the steel shell had a rosy shade and the weight of the
specimens decreased significantly after testing.
5. Estimation of the study results
The following in-place tests of round thick-walled steel columns
with a hollow thick-walled concrete core were carried out: determination
of specimen resistance to axial compression under ambient (t = 20
[degrees]C) conditions and determination of fire resistance of specimens
(time until collapse under heat conditions). The behaviour of the
specimens observed during the tests coincides with data supplied by a
number of other researchers. Not all the results of the experiment are
suitable for statistical procession; however, they make it possible to
carry out analytical comparison of certain parameters and formulate
corresponding conclusions.
The mean trial fire resistance of HC-FST columns tested by loading
them with 40 % of their mean trial load-bearing capacity under normal
conditions and heated according to a temperature curve close to the
standard temperature curve was 44,3 min. The maximum fire resistance
observed during the test was 59,4 min. The maximum temperature reached
inside the heating chamber of the furnace was 1240 [degrees]C.
The comparison of the fire resistance calculation results with the
results of experimental research presented in this paper is given in
[14]. Three times less load bearing capacity was received using a simple
calculation model accordingly [15] than it was obtained during the
experimental investigation.
During the test under normal and heating conditions both--short and
long HC-FST elements lost their load-bearing capacity following a local
buckling of the steel shell and the concrete core. During the type I
test, the observed failure mode was predetermined by the thin walls of
the steel and concrete parts of the cross-section, as well as the forces
of friction between the supporting plate of the press and the end of the
specimen. During the type II test, the observed failure mode was
predetermined by the thin walls of the steel and concrete parts of the
cross-section, as well as the uneven temperature of the specimens along
the central axis. The failure of the specimen was observed in all
instances at the zones of the specimens that were the most heated,
during the test. The measured longitudinal and transversal strain values
cannot be compared directly because specimens with unequal geometrical
indices for the cross-sections, at which the strain-gauge transducers
were attached to the surface of the steel shell were used. A relatively
wide dispersion of the other test results can be accounted for: by a
great number of the parameters that influence the results, due to
imperfections of the test equipment, due to inaccuracies of the
maintenance of the programmed temperature regime of the furnace, due to
potentially different moisture of the concrete of the specimen core, due
to regular dispersion of mechanical strength indices of the materials,
ie steel and concrete and some other factors.
The calculation of temperature distribution in the section of the
column under testing presented in [14] showed the temperature magnitude
of a concrete core 10-15 % less than temperature inside the furnace
chamber during heating. It is seen that the calculated value of the
temperature distribution (neglecting the water existence within the
concrete core) is not adequate to the experimental data as the water
steam was clearly observed for 30 min from the beginning of the heating.
The temperature distribution in the cross-section of HC-FST column after
45 min from the beginning of the standard fire [16] calculated by FEM modelling shown in Fig 9.
[FIGURE 9 OMITTED]
It is given in [17] that the design compressive strength of
concrete heated to 800 [degrees]C may amount to its 16 % of initial
strength, and the strength of the steel heated to 900 [degrees]C may
amount to its 6 % of initial strength. Compressive resistance of the CHS columns (with the mean geometrical and mechanical properties of steel
shell of the tested HC-FST specimens) under ambient conditions was
determined from calculations according to [17, 18] and makes up--302,6
kN.
The analysis of the compressive resistance of the same CHS column
under fire conditions was made as well. Compressive resistance of the
CHS column under fire conditions after 45 min of heating was obtained as
the result of calculation according to [19] and makes up only 18,02 kN.
The compressive resistance of the HC-FST column with geometrical
parameters of the tested specimens (from Table 1) in ambient
temperatures calculated according to [20] makes up 635 kN and it is
quite close to an experimental mean value 696 kN.
By the analysis of experimental results and calculation results it
can be stated that the greater portion of the load applied to the CH-FST
column is taken by a concrete core in a fire situation.
6. Conclusions
1. The influence of temperature on the compressive resistance of
HC-FST specimens is immense. However, the necessary fire resistance of
concrete filled hollow steel section columns can generally be achieved
without any fire protection covers.
2. The mean trial fire resistance of HC-FST columns tested by
loading them with 40 % of their mean trial load-bearing capacity under
normal conditions and heated according to the temperature curve close to
the standard temperature curve was 44,3 min. On the basis of the
analysis of test results and by taking into account that according to
[21] the calculating load of the constructions of the most civil
buildings under fire conditions makes up approx 40 % of the calculating
load under normal (t = 20 [degrees]C) conditions, it can be stated that
HC-FST elements designed for the use at ambient temperature always meet
construction fire resistance class RE30, and in some cases--fire
resistance class RE45.
3. The observation of the behaviour of the HC-FST specimens in fire
under axial compression allows to expect not a sudden failure mode via
the overall buckling of HC-FST columns but the failure mode that could
be described as local buckling of the thin-walled steel shell and local
failure of the hollow concrete core.
4. From the water steam emission observation it can be stated that
the temperature distribution in the section of columns during testing is
substantially influenced by the availability of free and chemically
combined water in the concrete core of HC-FST element. Water inside the
concrete should be always taken into account when calculating the
temperature distribution in the cross-section of the HC-FST column under
heat conditions.
5. The concrete core takes the greater part of the axial load
applied to the CH-FST column during the fire but the steel shell is not
very well resisting the normal stresses under fire.
Received 1 June 2006; accepted 2 Oct 2006
References
[1.] SAPALAS, A. Composite and interaction effect in steel-concrete
structures for higher fire resistance. Journal of Civil Engineering and
Management, 10(3), 2004, p. 241-245.
[2.] COLINA, H.; MOREAU, G. and CINTRA, D. Experimental study of
transient thermal creep and other phenomena of concrete at high
temperature. Journal of Civil Engineering and Management, 10(4), 2004,
p. 255-260.
[3.] HAN, L.-H.; ZHAO, X.-L.; YANG, Y-F. and FENG, J.-B.
Experimental study and calculation of fire resistance of concrete-filled
hollow steel columns. Journal of Structural Engineering, 129(3), 2003,
p. 346-356.
[4.] SHAKIR-KHALIL, H. and AL-RAWDAN, A. Experimental behaviour and
numerical modelling of concrete-filled rectangular hollow section
tubular columns. In Proc of an engineering foundation conference
composite construction in steel & concrete III, Irsee, Germany, June
9-14, 1996. Ed C. D. Buckner and B. M. Shahrooz, American Society of
Civil Engineers, 1997, p. 222-235.
[5.] BLAZEVICIUS, Z. and KVEDARAS, A. K. Comparison of the fire
design calculation for composite concrete filled CHS columns. In Proc of
the 8th International Conference ,Modern Building Materials, Structures
and Techniques", Vilnius, Lithuania, May 19-22 2004. Selected
papers, ed E. K. Zavadskas, P. Vainiunas and F. M. Mazzolani. Vilnius:
Technika, 2004, p. 357-362.
[6.] KODUR, V. Achieving fire resistance in steel columns through
concrete filling. Concrete Engineering International, 8(4), 2004, p.
50-53.
[7.] TAN, K-H. and TANG, C.-Y. Interaction model for unprotected
concrete filled steel columns under standard fire conditions. Journal of
Structural Engineering, 130(9), 2004, p. 1405-1413.
[8.] AL-KHALEEFI, A. M.; TERRO, M. J.; ALEX, A. P. and WANG, Y.
Prediction of fire resistance of concrete filled tubular steel columns
using neural networks. Fire Safety Journal, 37(4), 2002, p. 339-352.
[9.] LST EN 10002-1:2003--Metallic materials. Tensile testing. Part
1: Method of test at ambient temperature. Lithuanian Standards Board.
Vilnius, 2003. 56 p.
[10.] LST EN 1363-1:2000. Fire resistance tests. Part 1: General
requirements. Lithuanian Standards Board. Vilnius, 2000. 49 p.
[11.] LST EN 1363-1:2000. Fire resistance test of load bearing
elements. Part 4: Columns. Lithuanian Standards Board. Vilnius, 2000. 10
p.
[12.] VADLUGA, R. and KUDZYS, A. On the compressive strength of the
centrifuged concrete. Researches on Reinforced Concrete Structures
([TEXT NOT REPRODUCIBLE IN ANSCII.]), Vol 1, Vilnius: Mintis, 1966, p.
111-116 (in Russian).
[13.] KUDZYS, A. Reinforced concrete structures of annular cross-section ([TEXT NOT REPRODUCIBLE IN ANSCII.]). Vilnius: Mintis,
1975. 224 p. (in Russian).
[14.] BLAZEVICIUS, Z. and SAUCIUVENAS, G. The course of an
experimental research on the fire resistance of HCFST columns and the
results of their calculation. In Proc of National Conference Building
Structures--Development of building structures during integration in the
space of Eurocodes, on 3rd of March 2006. Vilnius: Technika, 2006, p.
42-50 (in Lithuanian).
[15.] LST EN 1994-1-2:2006. Eurocode 4--Design of composite steel
and concrete structures--Part 1-2: General rules--Structural fire
design. Lithunanian Standards Board. Vilnius, 2006. 109 p.
[16.] EN 1991-1-2:2002. Eurocode 1--Actions on structures. Part
1-2: General actions. Actions on structures exposed to fire. European
Committee for Standardization. Brussels, Jan 2002. 59 p.
[17.] STR 2.05.08:2005. Desing of steel structures. General rules
(Plieniniu konstrukciju projektavimas. Pagrindines nuostatos). Vilnius:
Rekona, 2005. 95 p. (in Lithuanian).
[18.] EN 1993-1-1. Eurocode 3: Design of steel structures--Part
1-1: General rules and rules of buildings. European Committee for
Standardization. Brussels, May 2005. 91 p.
[19.] EN 1993-1-2. Eurocode 3: Design of steel structures--Part
1-2: General rules--Structural fire design. European Committee for
Standardization. Brussels, Apr 2005. 78 p.
[20.] LST EN 1994-1-1:2005. Eurocode 4--Design of composite steel
and concrete structures--Part 1-1: General rules and rules for
buildings. Lithuanian Standards Board. Vilnius, 2005. 118 p.
[21.] LST ENV 1991-1:2000. Eurocode 1--Basis of design and action
on structures--Part 1: Basis of design. Lithuanian Standards Board.
Vilnius, 2000. 85 p.
CENTRISKAI GNIUZDOMU HC-FST KOLONU ATSPARUMO UGNIAI EKSPERIMENTINIS
TYRIMAS
Z. Blazevicius, A. K. Kvedaras
Santrauka
Yra sukurta keletas analitiniu metodu vamzdiniu plieno kolonu su
betono serdimi atsparumui kaitros salygomis nustatyti. Didziuma siu
analitiniu metodu yra paremti arba buvo kuriami analizuojant
eksperimentiniu kaitriniu tyrimu duomenis. Buvo atlikti vamzdiniu plieno
kolonu su tusciavidure betono serdimi elgsenos kaitros salygomis
eksperimentiniai tyrimai, matuojant skirtingus bandymo parametrus.
Eksperimentiskai istirta 16-kos centriskai gniuzdomu HC-FST
(centrifuguotu tusciaviduriu betonserdziu plieniniu vamzdiniu) kolonu,
nepadengtu apsauginemis (atsparuma kaitrai didinanciomis) dangomis,
elgsena kaitros salygomis (panasiomis i ISO-834 standartini gaisra), ir
tyrimo rezultatai yra pateikti siame straipsnyje. Nustatytos 4-iu
centriskai gniuzdomu HC-FST kolonu atsparumo kaitrai eksperimentines
reiksmes ir suirimo pobudis. Bandymu parametrams palyginti buvo
isbandytos 4-ios centriskai gniuzdomos HC-FST kolonos normaliomis
salygomis, taip pat centrisku gniuzdymu buvo isbandyti 8 HC-FST trumpi
elementai ir 4 betoniniai ziedai normaliomis salygomis. Pagrindiniai
straipsnyje aprasyto tyrimo tikslai--gauti eksperimentiniu duomenu
analizei ir priklausomybems tarp bandymo parametru, daranciu didziausia
itaka HC-FST kolonu atsparumui kaitrai, isvesti.
Reiksminiai zodziai: eksperimentinis tyrimas, asine apkrova,
betonserdes plienines vamzdines kolonos, laikomoji galia, atsparumas
ugniai.
Zygimantas Blazevicius (1), Audronis Kazimieras Kvedaras (2)
Dept of Steel and Timber Structures, Vilnius Gediminas Technical
University, Sauletekio al. 11, LT-10223 Vilnius, Lithuania E-mail: (1)
zygiui@centras.lt, (2) akve@st.vtu.lt
Zygimantas BLAZEVICIUS. MSc (CE), PhD student from 2002 at the Dept
of Steel and Timber Structures of Vilnius Gediminas Thechnical
University. Field of research: composite steel-concrete structures,
their fire resistance.
Audronis Kazimieras KVEDARAS. Professor, Doctor Habil, Head of Dept
of Steel and Timber Structures and Director of the Innovatory Scientific
Institute of Special Structures ,Kompozitas" of Vilnius Gediminas
Technical University. Field of research: steel structures and composite
steel-concrete and timber-concrete structures. Member of IABSE and
ASCCS, invited NATO expert (1996, 2000).
Table 1. Geometrical parameters of HC-FST and HC specimens
No Type of the Code of the h [mm]
cross-section specimen
1 HC-FST 1I1 2004
2 HC-FST 3I2 2000
3 HC-FST 5I1 1999
4 HC-FST 2I2 1992
5 HC-FST 1T1 300
6 HC-FST 2T2 298,5
7 HC-FST 2T1 298
8 HC-FST 3T1 298
9 HC-FST 3T2 298
10 HC-FST 4T1 298
11 HC-FST 5T1 296
12 HC-FST 0T1 295
13 HC 0TB2 296,5
14 HC 1TB2 296
15 HC 4TB2 300
16 HC 5TB2 300
17 HC-FST 0I1 1999
18 HC-FST 0I2 2000,5
19 HC-FST 2I1 2003
20 HC-FST 4I2 2000
Type of the [t.sub.a] [t.sub.c, Type of
cross-section [mm] mean] [mm] the test
HC-FST 1,65 20,1 I
HC-FST 1,6 31,9 I
HC-FST 1,63 24,875 I
HC-FST 1,6 28,9 I
HC-FST 1,65 23,6 I
HC-FST 1,6 25,5 I
HC-FST 1,6 15,9 I
HC-FST 1,6 16,15 I
HC-FST 1,6 16,55 I
HC-FST 1,63 19,025 I
HC-FST 1,63 24,375 I
HC-FST 1,6 15,65 I
HC 1,6 21,9 I
HC 1,65 21,6 I
HC 1,63 20,875 I
HC 1,63 20,375 I
HC-FST 1,6 27,15 II.1
HC-FST 1,6 20,65 II.2
HC-FST 1,6 20,9 II.1
HC-FST 1,63 33,725 II.1
NOTES
1. The cross-sections of all the HC-FST and HC specimens are hollow
and round-shaped. The outer diameter of the HC-FST specimens: 219 mm.
The outer diameter of the HC specimens: 215,8 mm.
2. The meanings of the markings in the Table columns: h--element
length; [t.sub.a]--steel shell thickness; [t.sub.c,mean]--mean
thickness of the concrete ring of the element.
3. Test type marking and test type description:
* "I"--determination of the compressive strength whether the HC-FST
or HC specimens are under axial loading and normal ambient conditions;
* "II.1"--fire resistance determination of the HC-FST specimens
under 25-ton axial load and ISO 834 fire conditions;
* "II.2"--fire resistance determination of the HC-FST specimens under
18-ton axial load and ISO 834 fire conditions.
Table 2. Main parameters of the test
No Type of the Code of the Type of
cross-section specimen the tests
1 HC-FST 1I1 I
2 HC-FST 22I I
3 HC-FST 32I I
4 HC-FST 5I1 I
5 HC-FST 0T1 I
6 HC-FST 1T1 I
7 HC-FST 2T1 I
8 HC-FST 2T2 I
9 HC-FST 3T1 I
10 HC-FST 3TI2 I
11 HC-FST 4T1 I
12 HC-FST 5T1 I
13 HC 0TB2 I
14 HC 1TB2 I
15 HC 4TB2 I
16 HC 5TB2 I
17 HC-FST 0I1 II.1
18 HC-FST 02I II.2
19 HC-FST 2I1 II.1
20 HC-FST 42I II.1
No [N.sub.utr] [t.sub.max] T
[kN] [[degrees]C] [min]
1 62,5 - -
2 69,0 0 0,0
3 74,5 - -
4 72,5 - -
5 60,5 - -
6 98,0 - -
7 86,0 - -
8 94,0 - -
9 75,5 - -
10 55,0 - -
11 86,0 - -
12 81,0 - -
13 63,5 - -
14 37,0 - -
15 30,0 - -
16 54,2 - -
17 25,0 1020 59,4
18 18,0 920 29,8
19 25,0 1190 37,0
20 25,0 1244 51,0
The meanings of the markings of the table columns: [N.sub.utr]--the
trial load-bearing capacity for axially loaded specimen,
[t.sub.max]--the maximum temperature of the furnace reached during
the fire resistance test, T--the duration of heating during
the fire resistance test.