The influence of shear span ratio on load capacity of fibre reinforced concrete elements with various steel fibre volumes.
Salna, Remigijus ; Marciukaitis, Gediminas
Abstract. This paper analyses the influence of steel fibre volume
and shear span ratio on the strength of fibre Reinforced concrete elements in various states of stress. 36 beams with three different
shear spans (a/h = 1, 1,5, and 2%) and three different fibre volumes (1,
1,5, and 2%) were tested to examine how these factors influence the
behaviour of such elements. Test results suggest that steel fibre volume
and shear span can increase load capacity, plasticity and cracking.
Experimental research showed that steel fibre volume has different
influence at different shear span ratios. Regression analysis of
experimental data was carried out and empirical approach showing
different effect of these factors was proposed. Furthermore, test
results were compared with different theoretical and empirical
approaches of other authors.
JEGOS PETIES IR AUKSCIO SANTYKIO ITAKA BETONINIU ELEMENTU
LAIKOMAJAI GALIAI, ESANT IVAIRIEMS DISPERSINIO ARMAVIMO KIEKIAMS
Santrauka
Straipsnyje analizuojama plieniniu fibru kiekio itaka dispersiskai
armuotam betonui, esant ivairiems itempimu buviams. 36 sijos su trimis
skirtingomis lenkimo momento ir skersines jegos santykio reiksmemis
(arba a/h = 1, 1,5, 2 santykiais) bei su trimis plieniniu fibru armavimo
procentais (1%, 1,5%, 2%) buvo isbandytos, siekiant nustatyti, kaip sie
veiksniai daro itaka dispersiskai armuoto betono elgsenai.
Eksperimentiniai tyrimai parode, kad sie veiksniai turi didele itaka
dispersiskai armuotu betoniniu bandiniu ilinkiams, pleisetumui,
plastiskumui bei laikomajai galiai, be to, plieniniu fibru kiekis esant
skirtingoms jegos peties ir aukscio santykio reiksmems, turi skirtinga
itaka. Atlikus eksperimentiniu tyrimu regresine analize, straipsnyje
pateikta israiska, parodanti skirtinga siu veiksniu itaka. Gauti
eksperimentiniai rezultatai taip pat palyginti su ivairiu autoriu
teoriniais skaiciavimo metodais.
Reiksminiai zodziai: dispersiskai armuotas betonas, laikomoji
galia, plastiskumas, pleisetumas.
Keywords: steel fibre reinforced concrete, load capacity,
plasticity.
1. Introduction
Different building structures, such as beamless reinforced concrete slabs, footings of foundation, shear in beams, have a brittle failure
mode and versatile complex stress behaviour [1-3]. This failure occurs
when tensile strength exceeds limit values. This failure is usually very
sudden due to brittle behaviour of plain concrete in tension. Steel
fibre reinforced concrete (SFRC) is well-known as a plastic composite
material with significantly higher tensile strength, resistance to crack
formation and propagation, which can replace brittle failure mode to
plastic in punching shear [4-6], or shear in beams [7-12].
The research of stress-strain state shows that failure is
influenced by bending moment and shear force ratio (shear span and depth
ratio) [13, 14], because shear stresses have significant effect on
principal stresses. Design methods of tensile strength of SFRC and its
behaviour in various states of stress are differently estimated by some
authors [4, 7, 15, 16]. It shows that stress and strain state of fibre
reinforced concrete at different bending moment and shear span ratios is
not fully analysed. That's why it is reasonable to analyse SFRC as
a composite material in versatile complex stress behaviour.
This paper presents results of the test in flexural steel fibre
reinforced concrete beams under different bending moment and shear force
(shear span and depth) ratios.
Regression analysis of experimental data was carried out, and
empirical approach showing different effect of these factors was
proposed. Furthermore, test results were compared with different
theoretical and an empirical approaches of other authors [4, 7, 15, 16].
2. Analysis of SFRC tensile strength estimation methods
The main factors influencing SFRC tensile strength are these:
volume and distribution of steel fibres in principal section, anchorage
of fibre in concrete matrix, yield strength of fibre and strength of
concrete [17, 18]. Distribution of steel fibres in principal section and
anchorage of fibre in concrete matrix is viewed differently by various
authors [4, 7, 15, 16]. For example, method [15], based on modelling
SFRC structure, estimates these factors by separate coefficients,
replacing dispersed reinforcement by equivalent reinforcement. Whereas
in method [16], the distribution of steel fibres in principal section is
based on stochastic theory. In this method, failure occurs when concrete
exceeds shear strength between fibres. In methods [4, 7], all these
factors are estimated by empirical coefficients.
According to method [15], SFRC tensile strength before cracking is
shown in Eq (1):
[f.sub.SFRC,t] = [f.sub.ct] (1-[V.sub.f]) +
[[sigma].sub.f][V.sub.f][[lambda].sub.p][[lambda].sub.or] [greater than
or equal to] [f.sub.y][V.sub.f][[lambda].sub.red]. (1)
Eq (2) represents tensile strength of SFRC cracked element:
[f.sub.SFRC,t] = [[lambda].sub.red] [f.sub.y][V.sub.f] = 0,41 (1-
[beta][f.sub.y][D.sub.f]/4[f.sub.c][L.sub.f]) [f.sub.y][V.sub.f]. (2)
SFRC compression strength is expressed in Eq (3):
[f.sub.SFRC,c] = [f.sub.c] + [[lambda].sub.red][V.sub.f][f.sub.y],
(3)
where [f.sub.ct] is tensile strength of concrete, [V.sub.f]--volume
fraction of steel fibres, [[sigma].sub.f]--stresses in fibres,
[f.sub.y]--yield strength of fibres, [D.sub.f]--fibre diameter,
[L.sub.f]--fibre length, [beta] =
[f'.sub.sub.c]/[[tau].sub.u]--coefficient, [f'.sub.c] =
0,7[f.sub.c,cube]--compression characteristic strength of concrete,
[[tau].sub.u]--fibre anchorage stresses in concrete matrix, obtained
from test results, [[lambda].sub.red]--coefficient replacing chaotic
reinforcement by equivalent reinforcement. It is calculated in Eq (4):
[[lambda].sub.red] = [[lambda].sub.p] [[lambda].sub.or]
[[lambda].sub.an], (4)
where [[lambda].sub.p] is coefficient, evaluating the distribution
of fibres in normal section, [[lambda].sub.or]--fibre orientation
coefficient, [[lambda].sub.an]--fibre anchorage coefficient.
Eq (5) represents SFRC tensile strength according to method [16]:
[f.sub.SFRC,t] = 0,375 [f.sub.ct] [L.sub.f]/[D.sub.f] [square root
of ([V.sub.f][K.sub.o])], (5)
where [K.sub.o]--fibre orientation coefficient, calculated in Eq
(6, 7):
if t[greater than or equal to][L.sub.f], [K.sub.o] = 0,5 + 0,097
[L.sub.f]/t (6)
if t > [L.sub.f], [K.sub.o] = 0,637 + 0,296 [L.sub.f]/t (7)
where t--width of cross-section.
In method [4], SFRC tensile strength is expressed by Eq (8):
[f.sub.SFRC,t] = (0,54 + 0,09[V.sub.f])[square root of
(0,8[f.sub.c])], (8)
where [f.sub.c]--concrete cylinder compressive strength.
Eq (9) presents SFRC tensile strength according to method [7]:
[f.sub.SFRC,t] = [f.sub.cif]/20 - [square root of (F)] + 0,7 +
[square root of (F)] (9)
where [f.sub.cuf]--cube strength of SFRC concrete (MPa), and
F--fibre factor, calculated in Eq (10):
F = [L.sub.f]/[D.sub.f] [V.sub.f] [d.sub.f] (10)
where [d.sub.f]--bond factor: 0,5 for round fibres, 0,75 for
crimped fibres, and 1,00 for indented ones.
The analysis of these methods clearly illustrates that the
distribution of steel fibres in principal section, and the anchorage of
fibre in concrete matrix are estimated differently. Also, different
concrete strength characteristics in the discussed methods were used.
Furthermore, nearly all methods analysed [4, 7, 16] are based on
empirical findings of the authors. Eq (1), provided by method [15], is
more accurate, as it is based on modelling SFRC structure.
3. Methodology of experimental research
Three series of tests with three different shear spans (a/h = 1,
1,5, and 2, Fig 1) and three different fibre volumes (1, 1,5, and 2%)
were carried out in this experimental program. The research is aimed to
imitate various stress strain states with different fibre volumes
ranging from simple bending elements [19, 20] to deep beams [14].
Therefore, such different shear span values were chosen. 36 specimens,
including plain concrete, were tested. The cross-section of specimens b
x h=100 x 200 mm, and length l = 500; 750;1000 mm. Fig 2 shows test
setup. Water cement ratio w/c for all beams was 0,51.
[FIGURE 1 OMITTED]
In the tests reported, fibre type MPZ50/1, Art. No 1010
(Metalproducts Ltd) was applied, where fibre length was 50 mm and its
diameter 1 mm. These dimensions correspond to the aspect ratio of l/d=50
/1=50. Nominal yield strength of steel fibres was [f.sub.yk] = 1100 MPa.
Specimens were reinforced with three volume fractions: 1, 1,5 and 2%
(78,5 kg/[m.sup.3], 117,8 kg/[m.sup.3], and 157 kg/[m.sup.3],
respectively).
During the test, midspan deflections, tensile and compression
strain, as well as strain in the tension zone near the crack of the
beams, were measured. The load was applied to the beams through a
100x100x10 mm steel plate. Fig 1 shows a loading configuration and
layout of different gauges.
[FIGURE 2 OMITTED]
Average load capacities of tested beams are presented in Table 1,
and their graphical expression in Fig 3. Typical failure of specimens is
demonstrated in Fig 4.
[FIGURE 3 OMITTED]
[FIGURE 4 OMITTED]
As the curves on Fig 3 show, the greatest influence on load
capacity is observed at shear span ratio a/h= 1. This case reminds of
the case of deep beam in the way that principal stresses are strongly
influenced by shear stresses. After increasing fibre volume from 1 to
2%, when a/h= 1, load capacity grows from 1,62 to 1,89 times. At higher
values of shear span ratio, the increase of load capacity is not so
significant. For example, when a/h= 1,5 and a/h= 2, the increase from
1,26 to 1,56 and 1,14 to 1,54 times, respectively, is observed.
[FIGURE 5 OMITTED]
Fibre volume [V.sub.f] and shear span ratio a/h have significant
influence on deflection, plasticity and cracking of the element.
Besides, this influence is different, depending on these factors. As the
curves presented on Fig 5 show, with different [V.sub.f] and a/h, three
different groups of elements can be defined in respect of load capacity
as well as deflections. At high values of ratio a/h, deflections
significantly grow with a small rise in load capacity, whereas at low
values of ratio a/h, the growth of both deflections and load capacity is
observed. It is clearly seen that load capacity, in variation of
[V.sub.f] at different a/h, is influenced by [V.sub.f].
[FIGURE 6 OMITTED]
These factors also influence the cracking of elements (Fig 6). When
a/h = 1, 1,5 and 2, cracks appear at failure loads (0,6 ... 0,7), (0,7
... 0,8) and (0,8 ... 0,85) [F.sub.u], respectively.
The analysis of tension and compression strains showed (Fig 7) that
with increasing a/h, plastic strains can be observed at higher load
capacity values: when a/h = 1, 1,5 and 2, ductile strain appears at
failure loads (0,4 ... 0,55), (0,55 ... 0,65) and (0,65 ... 0,78)
[F.sub.u], respectively.
[FIGURE 7 OMITTED]
Fibre volume has a significant influence on plasticity and
compression zone of the element. With small [V.sub.f], normal crack
destroys compression zone in nearly the same manner as in the concrete
element. With the increase of [V.sub.f], compression zone plastic hinge is formed like one in simple bending beam. Besides, fibre volume has
significant influence on the height of compression zone. Experiments
show that the average height of compression zone at 0,5 [F.sub.u], was
equal to 64-65 mm in conventional concrete element. In SFRC beams it was
noticeably greater: the average height of compression zone, at fibre
volume [V.sub.f] =1, 1,5 and 2%, was equal to 68-72, 72-75 and 76-78 mm,
respectively.
In conclusion, the influence of shear stresses on principal
stresses and fibre volume effect on the height of compression zone are
the main factors determining load capacity.
4. Comparison and analysis of theoretical and experimental results
The comparison of theoretical and experimental results, with the
variation of [V.sub.f], at different a/h, is presented in Figs 8, 9.
[FIGURE 8 OMITTED]
Comparing theoretical methods, all authors estimate fibre volume as
a linear function. The character of curves is similar in empirical
methods [4, 7] (curves are parallel). The character of curves in methods
[15, 16], compared with methods [4, 7], is not similar (they are not
parallel), because fibre volume was evaluated using SFRC structure
modelling and not empirical coefficients. However, though having
different characters, the curves in methods [15, 16] better correspond
to test results.
[FIGURE 9 OMITTED]
Comparing theoretical and test results, method [15] most closely
corresponds to test results. However, the influence of [V.sub.f] is
overestimated in some cases and even exceeds test results. Methods [4,
7, 16] are more conservative.
Table 2 presents how differently authors estimate the influence of
fibre volume on load capacity. The table also shows empirical
expressions provided by regression analysis of test results. The ratio
of SFRC and concrete specimens load capacities is expressed by
equations. can be expressed by linear function (reliability is high and
variation factor is low). Linear function is applied in methods [4, 7,
16], but it could not be applied to method [15] (Eqs 1, 2), because such
values can exist, at which [f.sub.SFRC,t] < [f.sub.c,t]. Empirical
expressions, provided by regression analysis, clearly show different
influence of [V.sub.f] on load capacity at different a/h.
This effect can be explained by decreasing ratio a/h, in deep beams
influenced not only by bending, but bending with shear. Besides,
compared with plain concrete, SFRC behaves differently in shear,
therefore such great difference occurs. This influence, the so-called
"arch action", is expressed through empirical coefficients by
many authors [8, 9, 13], analysing reinforced concrete behaviour in
shear. However, this effect for SFRC is estimated by the same equations.
The difference between plain concrete and SFRC is clearly illustrated in
Fig 3.
[V.sub.f], and a/h can be expressed as one function (Fig 10). This
function cannot be expressed as a linear one, because reliability is
only 0,83 and variation factor exceeds 0,14. After regression analyses
of 36 beams, the influence of these factors can be demonstrated by the
following polynomial function:
[MATHEMATICAL EXPRESSION NOT REPRODUCIBLE IN ASCII], (11)
where a' = 3,403, b = -5, 218, c = 1,937, d'=3,634, e =
0, 498, f = -2,331, g = -0,816, h = -0, 248, i = 0,195, and j = 0,560.
Reliability of polynomial function is 0,966, and variation factor
is 0,067.
[FIGURE 10 OMITTED]
However, quite good results can be achieved with a more simple
function. The increase of load capacity within the range of a/h = 1....2
and [V.sub.f] = 1...2%, can also be expressed in the following way:
[beta] = [f.sub.u,SFRC/[F.sub.u,Concrete] = [(1,158 -
0,249/[(a/h).sup.2] - 0,312[V.sup.0,5.sub.f]).sup.-1] (12)
In this equation, the influence of shear span ratio and fibre
volume on load capacity can be estimated with reliability of the
function equal to 0,92 and variation factor equal to 0,097.
5. Conclusions
1. Test results show that plasticity, cracks propagations and load
capacity of elements are greatly influenced by steel fibre volume and
shear span.
2. Load capacity of tested beams, in variation of volume fraction
at different a/h, is different. When a/h= 1, load capacity grows from
1,62 to 1,89 times. At higher values of shear span ratio, the increase
of load capacity is not so significant. For example, when a/h= 1,5 and a
/ h = 2, the increase from 1,26 to 1,56 and 1,14 to 1,54 times,
respectively, is observed.
3. The analysis of theoretical methods demonstrates that fibre
volume, distribution of steel fibres in principal section, anchorage of
fibres in concrete matrix and concrete strength characteristics are
estimated differently. These factors determine the difference between
theoretical results.
4. Experimental researches show that fibre volume and shear span
ratio is very important. This expression [beta] and those two mentioned
above parameters can be expressed as a surface function. Based on
regression analysis of experimental data, empirical equation, evaluating
these factors, was proposed.
Received 23 June 2006; accepted 16 March 2007
References
[1.] VAINIUNAS, P.; POPOVAS, V.; JARMOLAJEV, A. Punching Shear
Behaviour Analysis of RC Flat Floor Slab to Column Connection. Journal
of Civil Engineering and Management, 2002, 8(2), p. 77-82.
[2.] SALNA, R.; MARCIUKAITIS, G.; VAINIUNAS, P. Estimation of
Factors Influencing Punching Shear Strength of RC Floor Slabs. Journal
of Civil Engineering and Management, 2004, 10(2), p. 137-142.
[3.] SALNA, R.; MARCIUKAITIS, G.; VAINIUNAS, P. Analysis of
Resistance to Punching Shear of Beamless Reinforced Concrete Floor
Slabs. In Proc of the 8th International Conference "Modern Building
Materials, Structures and Technique", Vilnius, 19-22 May 2004.
Selected papers, ed E. K. Zavadskas, P. Vainiunas and F. M. Mazzolani,
Vilnius: Technika, 2004, p. 615-619.
[4.] HARAJLI, M. H.; MAALOUF, D.; KHATIB, H. Effect of Fibres on
the Punching Shear Strength of Slab Column Connections. Cement and
Concrete Composites, 1995, 17(2), p. 161-170.
[5.] KUTZING, L.; KONING, G. Punching Behaviour of High Performance
Concrete Columns with Fiber Cocktails. Lacer 5, University of Leipzig,
2000, p. 253-260.
[6.] CHEN, S. Strength of Steel Fiber Reinforced Concrete Ground
Slabs. Structures and Buildings, 2004, 157(2), p 157-163.
[7.] NARAYANAN, R.; DARWISH, I. Y. S. Use of Steel Fibres as Shear
Reinforcement. ACI Structural Journal, 1987, 84(3), p. 216-227.
[8.] ASHOUR, S. A.; HASSANAIN, G. S.; WAFA, F. F. Shear Behaviour
of High-Strength Fiber Reinforced Concrete beams. ACI Structural
Journal, 1992, 89(2), p. 176-184.
[9.] SHARMA, A. K. Shear Strength of Steel Fibers Reinforced Beams.
ACI Journal, 1986, 84(4), p. 624-628.
[10.] LI, V. C.; WARD, R.; HAMZA, A. M. Steel and Synthetic Fibres
as Shear Reinforcement. ACI Material Journal, 1992, 89(5), p. 499-508.
[11.] LI, V. C. On the Shear Behaviour of Engineered Cementitious Composites. Advanced Cement Based Materials, 1993, 1(3), p. 142-149.
[12.] KWAK, Y. K.; KIM, W. S.; KIM, J. Shear Strength of Steel
Fibers--Reinforced Concrete Beams without Stirrups. ACI Structural
Journal, 2002, 99(4), p. 530-538.
[13.] ZSUTTY, T. Shear Strength Prediction of Separate Categories
of Simple Beams Test. ACI Journal, 1971, 68(2), p. 138-143.
[14.] CHO, S. H. Shear Strength Prediction by Modified Plasticity
Theory for Short Beams. ACI Structural Journal, 2003, 100(1), p.
105-112.
[15.] RABINOVICH, F. N. Composite Material Based on the Fibre
Reinforced Concrete. The Questions of Theory, Design, Technology,
Structures: monograph. Moscow: Publishing Office ASV, 2004. 506 p. (in
Russian).
[16.] STEPANOVA, G. G. Researches of Steel Fibre Reinforced
Concrete in Gradient of Stress State. Summary of Doctoral Thesis.
St.-Petersburg Institute of Civil Engineering, St.-Petersburg, 1975. 28
p. (in Russian).
[17.] MARCIUKAITIS, G. The Principles of Creation and Prognoses of
Structures Composites. Vilnius, Technika, 1998. 134 p. (in Lithuanian).
[18.] SWAMY, R. N.; MAGNAT, P. S.; RAO, C. V. S. K. The Mechanics
of Fiber Reinforcement of Cement Matrices. In Fibre reinforced concrete,
Special Publication No 44, American Concrete Institute, Farmington
Hills, Michigan, 1974, p. 1-28.
[19.] MAALEJ, M.; LI, V. C. Flexural Strength of Fiber Cementitious
Composites. ASCE Journal of Materials in Civil Engineering, 1994, 6(3),
p. 390-406.
[20.] MAALEJ, M.; LI, V. C. Flexural/Tensile Strength Ratio in
Engineering Cementitious Composites. ASCE Journal of Materials in Civil
Engineering, 1994, 6(4), p. 513-527.
Remigijus Salna, Gediminas Marciukaitis
Dept of Reinforced Concrete and Masonry Structures, Vilnius
Gediminas Technical University, Sauletekio al. 11, LT-10223 Vilnius,
Lithuania. E-mail: gelz@st.vtu.lt
Remigijus SALNA. PhD student, Dept of Reinforced Concrete and
Masonry Structures. Vilnius Gediminas Technical University (VGTU), BSc
(2000) and MSc (2002) in Civil Engineering at Vilnius Gediminas
Technical University. Author of 5 scientific articles. Research
interests: punching shear of plain and fibre reinforced conctete.
Gediminas MARCIUKAITIS. Professor, Doctor Habil, Dept of Reinforced
Concrete and Masonry Structures. Vilnius Gediminas Technical University
(VGTU). PhD (Kaunas Politechnical Institute, 1963). Research visit to
the University of Illinois (1969). Doctor Habil (1980) at Moscow Civil
Engineering University, Professor (1982). Author and co-author of 5
monographs, 6 text-books and more than 300 scientific articles. Research
interests: mechanics of reinforced concrete, masonry and layered
structures, new composite materials, investigation and renovation of
buildings.
Table 1. Summary of test programme
Average load capacities of beams
[f.sub.
c,cube], [F.sub.u], kN ([beta] =
[V.sub.f],% MPa [F.sub.u.SFRC],/[F.sub.u,Concrete])
a / h = 1 a / h = 1,5 a / h = 2
0% 46,30 41,50(1,00) 26,4(1,00) 19,13(1,00)
1% 45,29 67,14(1,62) 33,30(1,26) 21,9(1,14)
1,5% 45,20 74,23(1,79) 39,40(1,49) 27,90(1,46)
2% 42,95 77,10(1,86) 41,20(1,56) 29,46(1,54)
Table 2. The ratio of SFRC and concrete specimens load
capacities in variation of [V.sub.f]
Reliability of
y = [F.sub.u,SFRC]/ function (variation
Method [F.sub.u,Concrete] factor)
[15] y = 0,913 + 0,202[V.sub.f] 0,613 (0,168)
(y = 0,913 + 0,06[V.sub.3.sup.3) 0,953 (0,058)
[16] y = 0,972 + 0,505[V.sub.f] 0,991 (0,049)
[4] y = 1,000 + 0,165[V.sub.f] 0,999 (0,001)
[7] y = 1,021 + 0,167[V.sub.f] 0,953 (0,039)
Regression
analysis
a/h=1 y = 1,021 + 0,585[V.sub.f] 0,955 (0,098)
a/h=1,5 y = 0,993 + 0,302[V.sub.f] 0,928 (0,067)
a/h=2 y = 0,996 + 0,292[V.sub.f] 0,906 (0,075)