Low charge transport refrigerator (I). Refrigerant charge and strategies of charge reduction/Mazos dozes transportinis saldytuvas (I). Saldymo agento doze ir dozes sumazinimo strategijos.
Vaitkus, L.
1. Introduction
For a long time, subjects dealing with the refrigerant charge in
equipment were not a priority. For practical purposes a common
estimation was to assess that 50% of the evaporator's volume is
filled with liquid. Things started to change after the Montreal's
protocol (1987) highlighted the destructive influence of some
refrigerants on the ozone's layer, and the Kyoto's protocol
(1997) underlined that most of refrigerants considerably contribute to
the greenhouse effect. Refrigeration units cannot avoid refrigerant
leaks, and can thus have a harmful impact on the environment. Therefore
recently studies on refrigerant charge reduction have become more
numerous.
The charge reduction is a major design objective for refrigerating
equipment using hydrocarbons because of their flammability. However,
when trying to reduce the atmospheric emissions, the restriction in
charge should be also adopted in systems operating with halogenated
refrigerants since lower charge per system leads to lower annual
emissions. With the low charge systems the double positive effect is
gained. Not only annual emissions from systems during their use are
reduced, but also greenhouse gas (GHG) stock build up is prevented,
which will reduce 'End of Life' emission in the future.
Therefore, considering the environmental challenges the refrigerant
charge minimization is one of the most important targets for
refrigeration and air conditioning (RAC) applications.
However, any measure reducing refrigerant emissions that also
decreases system energy efficiency must be cautiously estimated taking
into account GHG emissions related to energy use. If energy usage of
refrigerating or air conditioning system is included in a comparison,
the balance of such a measure can be negative. Therefore, according to
Harmelink et al, [1] any system adaptation should only be carried out if
it results in lower Total Equivalent Warming Impact (TEWI).
The object of this study is refrigerating systems, used in
refrigerated bodies for delivery vans to be used for the distribution of
refrigerated goods (vegetables, meat, ice cream etc.) to the end
customers. Such refrigerated bodies are usually built with an integrated
refrigerating plant with eutectic system. The information and
recommendations available from the previous studies are analyzed
primarily considering their applicability in such system.
The term 'Eutectic System' refers to a refrigeration
system that uses the phase change of a liquid medium to absorb and
dissipate large amounts of thermal energy while remaining at a constant
pre-arranged temperature. Phase change occurs when we freeze a solution
solid by removing its heat or as it thaws into a liquid again while it
absorbs heat. The eutectic solution is stored in the steel or aluminium
tank (eutectic plate) and acts like a renewable ice block, freezing
solid during the refrigeration run cycle and thawing during off periods.
Such a system has some advantages. They operate with big
'hold-over' OFF periods due to the thermal mass of the stored
eutectic solution and because of the eutectic's phase change. The
cold storage is used for the maintenance of a sufficient low temperature
during distribution, where no access to electric supply is available,
and the refrigerating plant is not working. Also these plants can
generate cold during the night, with the vehicle in garage, by
connecting to the electrical supply net. Operation during the cooler
periods (the night) ensures lower condensing temperature, which
increases system efficiency.
The storage temperature in the goods must not exceed -18[degrees]C
and the crystallization temperature of the eutectic mixture is usually
-33[degrees]C. These levels of temperature mean that the refrigerating
compressor is working under very high compression ratio and utilization
of energy is relatively poor. Condensing temperature is usually about
30[degrees]C; evaporation temperature during the crystallization of
eutectic mixture is in the range of -43 - -15[degrees]C, but at the end
of pull down cycle it goes below -50[degrees]C and may even reach
-57[degrees]C. For R507A refrigerant this will give the compression
ratio above 24. The stationary refrigerator for such temperatures would
use two-stage refrigerating system with intercooler. However in
transport refrigerating systems the space and weight are limiting
factors and onestage systems are used instead.
Further a review of studies considering refrigerant charge and
charge reduction is presented.
2. Sensitivity of refrigerating system performance to charge levels
and optimal charge
One of important aspects is sensitivity of refrigerating system
performance to charge levels. Grace et al. [2] investigated the effect
of refrigerant charge on steady-state system performance and identified
parameters sensitive to charge level for leak detection in vapour
compression refrigeration systems. The investigations were performed on
a small 4 kW nominal cooling capacity vapour compression water-to-water
chiller equipped with plate type heat exchangers. Refrigerant R404A was
used as a working fluid. The system was equipped with thermostatic
expansion valve (TXV). The liquid receiver was not used. The results
indicate that the chiller could operate over a wide range of charge
levels, 25% below to 25% above the design value without significant
impact on its performance. Outside this range, the performance was found
to be strongly dependent upon the charge level--at charge levels below
25% undercharge the cooling capacity falls very rapidly and at 50%
undercharge it drops down to 50% of its maximum value. At overcharge
levels greater than 25% the cooling capacity also begins to fall slowly,
dropping by 7% from its maximum value at 40% overcharge conditions. The
impact of charge level was much more pronounced on the condensing
temperature and pressure than on the evaporating temperature and
pressure. At charge levels below 25% of design value the system operated
with incomplete condensation. Moving from 25% undercharge to 25%
overcharge provided only a small change in the cycle on the P-h diagram.
Tassou and Grace [3] focused their article on fault diagnosis and
refrigerant leak detection in vapour compression refrigeration system.
The test facility used for development and validation of the fault
diagnosis system was identical to analyzed in [2]. It was found that the
coefficient of performance (COP) of this system was relatively constant
at its maximum across a broad range of charge levels and that
discrimination is required at charge levels differing by more than 33%
from the nominal. The sensitivity to refrigerant charge levels is a
function of the system considered and liquid-to-liquid systems are less
sensitive to refrigerant charge than air-to-air systems. The developed
fault diagnosis and leak detection system shows an undercharge fault
when the system charge falls below 33% of nominal charge and an
overcharge fault when the charge level is above 33% of nominal charge.
Superheat out of evaporator was used to diagnose undercharge and
subcooling out of condenser was used to diagnose overcharge.
Choi and Kim [4, 5] investigated the influence of refrigerant
charge on the performance of heat pumps with electronic expansion valves
(EEV) and capillary tube. Water-to-water heat pumps without liquid
receiver were analyzed. The results indicate that the variation of the
capacity for the EEV system with respect to refrigerant charge was less
pronounced than that for the capillary tube system. With the EEV system,
the variations of the capacity were almost negligible as refrigerant
charge was altered from--10% to +20% of full charge. With the rise of
the condensing temperature, the optimum charge amount of the EEV system
needs to be increased. For such system the COP was relatively
insensitive to refrigerant charge--for R407C system maximum reduction of
COP at charge conditions from -20% to +20% of full charge was 3.6%.
The effect of refrigerant charge level on airconditioning systems
was also examined by Goswami et al. [6]. The authors concluded that
charge level has a significant effect on the performance of
air-conditioning systems at levels below 80% of normal. For a charge
level of 90% of normal, the effect on COP and cooling capacity was found
to be negligible.
Farzad [7] also studied the effect of improper charging on air
conditioner performance for a short tube orifice, a TXV and a capillary
tube. He found that the units using TXV were less sensitive to charge
amounts. In the -15% to +10% charge range the capacity and efficiency of
TXV unit was relatively constant (max. capacity and efficiency
degradation was within 3%).
Corberan et al. [8] presented charge optimization study of a
reversible water-to-water propane heat pump. The system was equipped
with scroll compressor, brazed plate condenser and evaporator and TXV.
The liquid receiver was not used. It was found that the COP has a clear
maximum with approximately the same value of charge for both cooling and
heating conditions, the maximum being more pronounced under cooling
conditions. Thus a reversible unit charge optimised at one operating
condition will be also at optimum under the reverse condition.
Bjork and Palm [9] investigated performance of a domestic
refrigerator under influence of varied refrigerant charge, expansion
device capacity (EDC) and ambient temperature. Household refrigerator
with SLHX and low pressure liquid accumulator (integrated in evaporator)
was analyzed. EEV with stepper motor + capillary tube combo was used as
expansion device in order to have variable expansion device capacity. It
was found, that the energy consumption had a flat and wide minimum for
certain combination of EDC and charges. Low sensitivity to charges (flat
minimum) was explained by evaporator accumulator, which acts as a buffer
that protects the system from either superheat or a cold suction line.
It was also suggested that SLHX should insignificantly increase the
charge due to lowered evaporator inlet quality and the dryout point
moving closer to the evaporator outlet.
Cho et al. [10] investigated effects of refrigerant charge amount
on the performance of a typical transcritical CO2 heat pump in cooling
mode operation. The test system consisted of a variable speed scroll
compressor (heating capacity 4.5 kW), finned-tube gascooler and
evaporator, and an expansion device (EEV driven by a stepping motor).
The system characteristics of the C[O.sub.2] system were compared with
those for the R22, R407C and R410A systems. Fig. 1 represents the COP
ratios of the compared systems with deviation from optimal charge. At
undercharged conditions the C[O.sub.2] system showed the largest
reduction in the COP. The cooling COP of the R410A system showed the
largest drop at +5% of optimal charge. For the C[O.sub.2] system, the
reduction of COP was more significant at undercharged conditions than at
overcharged conditions. For -20% of optimal charge, the COPs for the
R22, R407C and C[O.sub.2] systems decreased by 4, 8 and 25%,
respectively, and for -10% of optimal charge, those reduced by 2, 5.5
and 10%, respectively. However, for +5% of optimal charge, the R22,
R410A, R407C and C[O.sub.2] systems showed reductions of the COP by 2,
5.5, 3, and 2%, respectively. The C[O.sub.2] system showed higher
performance sensitivity to refrigerant charge than that other compared
systems.
[FIGURE 1 OMITTED]
Rozhentsev [11] investigated a low-temperature Joule-Thomson
refrigerating machine, using a nonazeotropic mixture of refrigerants.
The machine was equipped with a single-stage hermetic compressor,
operated at the temperature level of -75[degrees]C and was charged with
the working non-azeotropic mixture which comprised of two components
with considerably different thermodynamic properties. The behaviour of
such refrigerating machine is found to be essentially different from the
behaviour of refrigerating machines working by use of pure refrigerants
or azeotropic mixtures. The amount of the minimum acceptable mixed
refrigerant mass charge for the machine has been found. Under the mass
charges below the minimum one, the temperature and power performance of
the mixed refrigerant refrigerating machine are considerably higher than
the designed ones and those operating modes are taken as inadmissible.
Dmitriyev and Pisarenko [12] suggested a simple correlation to
calculate the optimum charge in a domestic refrigerator in which the
evaporator and condenser internal volumes are the only parameters:
[G.sub.r] = 0.41[V.sub.e] + 0.62[V.sub.c]-38
where [G.sub.r] is the refrigerator charge in grams, [V.sub.e] the
evaporator internal volume in ml and [V.sub.c] the condenser internal
volume in ml. They found that the COP was more sensitive to over than
undercharging. They also found that the optimum charge was independent
on the ambient temperature. The correlation was designed for refrigerant
R12. However, Bjork and Palm [9] tested the correlation for Isobutane
household refrigerator multiplying the result with the density ratio of
Isobutane to R12 (0.41 liquid/liquid). They have found that suggested
optimum charge was an overcharge of only 15% to the nominal charge.
Therefore the correlation may be used as a first estimation of optimum
charge for household refrigerator.
Vjacheslav et al. [13] proposed rationally based algorithm to
evaluate optimal mass charge into refrigerating machines. The model was
created for refrigerating system without liquid receiver with capillary
tube expansion device. It takes into account the major components of the
refrigerating system (condenser, evaporator, expansion device and
compressor). The calculated results give an identical trend to those of
experimental data for the systems with capillary tube expansion device.
Ratts and Brown [14] presented an experimental analysis of the
effect of refrigerant charge level on a cycling-clutch, orifice-tube
(CCOT) automotive refrigeration system. The system was equipped with
liquid separator--accumulator after the evaporator. Thermodynamic losses
were quantified as a function of the refrigerant charge level. The
experimental results show that the system is more efficient as the
refrigerant charge level decreases. This is accomplished at the expense
of increased refrigeration temperature and decreased refrigeration
capacity.
3. The charge distribution and refrigerant mass measurement
Another important aspect is refrigerant mass measurement and charge
distribution. Most of the refrigerant charge is in the form of liquid
inside the unit, and depends on the geometry of the evaporator and
condenser, on the volume of the liquid line, on the evaporation and
condensation temperatures, on the subcooling, and on the amount of oil
in the compressor.
Ding et al. [15] presented quasi on-line measurement method (QOMM)
for measuring refrigerant mass distribution inside a refrigeration
system. The method is combination of liquid nitrogen method (LNM) and
on-line measurement method (OMM). Compared with LNM, QOMM can accelerate
the measurement process. The results showed that the maximal prediction
deviation of the refrigerant charge in the whole refrigeration system is
1.7%. The article also gives case study using the new measurement
method. An R410A inverter air conditioning system was analyzed under
steady state conditions. The cooling capacity of the system was 7.1 kW,
power consumption of the compressor was 1.7 kW, and the refrigerant
charge was 2 kg. The refrigerant in the condenser, the evaporator and
the compressor were 50.0 [+ or -] 3.4%, 16.0 [+ or -] 1.3% and 14.0 [+
or -] 2.3% of the whole charge, respectively (the inner volume of the
analyzed condenser was 2.4 times larger than that of the evaporator).
Bjork [16] presented refrigerant mass measurement technique based
on the quick closing valves technique and the equations of state. The
system was computer automated and can operate autonomously. The
refrigerating system is subdivided into various control volumes by
quick-closing valves, in order to trap the refrigerant. Each control
volume is then expanded into a tank large enough to achieve a
superheated state. When thermodynamic equilibrium is reached, the
temperature and pressure in the tank are measured and the charge is
calculated. This method is adapted to measure low quantities of
refrigerant, but is not so practical for larger quantities.
Bjork and Palm [17, 18] used this technique for the investigation
of refrigerant mass charge distribution in a domestic refrigerator.
These works provide experimental data of the charge distribution in a
capillary tube throttled cooling system under varied load conditions. It
was found that the condenser and compressor mass charges increased
whereas the evaporator charge decreased upon increased thermal load.
These trends confirm the simulations from Kuijpers et al. [19]. The
largest charge variation is found in the evaporator--from the lowest to
the highest thermal load the charge in this component decreases more
than 30%. The charge increase in the condenser and in the compressor was
explained by the increasing system pressure. The charge decrease in the
evaporator cannot solely be explained by an increased inlet quality and
increased mass flow and was partially caused by a decreased charge in
the accumulator. The results highlight one important feature of the
accumulator: it acts as a charge buffer from which refrigerant is
displaced to other parts of the system at increased thermal load without
starving the evaporator.
Charge distribution in a 5 kW heat pump using propane as a working
fluid was presented by Primal et al. [20] (Fig. 2). The experimental
system had no liquid receiver, used plate heat exchangers and EEV as
expansion device. Optimal charge for the system was 300 g.
Primal et al. [21] also investigated propane heat pump designed for
low refrigerant charge. The experimental system was equipped with
mini-channel aluminium evaporator and condenser. The total internal
volumes of the aluminium heat exchangers were less than 50% of those of
the plate heat exchangers in [20]. It was found that the amount of
refrigerant charge in the heat pump with the mini channel heat
exchangers was about 200 g, comparing to 300 g for system with plate
type heat exchangers. The heat pump was tested with different heat
source temperatures and with a constant heat sink temperature. The
refrigerant quantity in the system was varied for each heat source and
heat sink temperature combination and the COP of the system was
determined. The superheat was independent of the refrigerant charge and
was kept between 4 and 6.5 K. The sub-cooling at the condenser outlet
was allowed to increase for higher charges and therefore was strongly
coupled to the system charge. Optimum charges for each heat source
temperature correspond to a subcooling of 4-5 K.
[FIGURE 2 OMITTED]
It was found that the COP was more or less constant when the charge
was above a certain minimum level. Below this level, the COP dropped
significantly. As for the COP the capacity is more or less constant as
long as the charge is above the optimum charge. The capacity and COP
reduction for lower refrigerant charges is caused by the decrease of the
evaporation temperature. The reason for this decrease is the
'starvation' of the evaporator.
Charge distribution tests showed that the amount of refrigerant in
the evaporator (volume 376 [cm.sup.3]) was almost same for all four
tests (23--26 g), even though the evaporation temperature varied from
-16.5 to +4.5[degrees]C. Also, the amount of refrigerant in the liquid
line was the same in all four experiments (23--24 g). The amount of
refrigerant in the condenser (volume 437 [cm.sup.3]) varied from 69 to
93 g, showing an increase of 24 g in spite of the fact that the
condensing temperature was almost constant. It was concluded that use of
mini channel heat exchangers reduces considerably refrigerant charge in
heat pumps and refrigerating systems.
Similar results were obtained by Corberan et al. [8] who used
IMST-ART software in order to examine the distribution of the charge
inside the refrigerating system. It was found that most of the charge of
the unit (about 50%) is in the condenser and mainly at its final part
and outlet port. The evaporator contains another significant part of the
charge (about 14%). Nearly 30% of the total charge is found dissolved in
the lubricant oil in the compressor. The amount of refrigerant in the
oil is for the most part dependent on the evaporation pressure and on
the oil temperature. Therefore, the amount of charge in the compressor
is, a function of the evaporation temperature. The authors suggest that
since most refrigerant inventory corresponds to liquid refrigerant and
that its density is fairly constant, the total mass in all components of
the system, with the exception of the condenser, is non-dependent on the
variation of the charge. The condenser stores the extra charges in the
system varying the subcooling. With the increase of charge in the system
the amount of charge in the evaporator also slightly increases, since
the increase in subcooling is leading to a decrease in the vapour
quality at the inlet of the evaporator.
Since most of the charge of the unit is in the condenser, some
charge reduction studies are focused on different low charge heat
exchanger designs. Cavalini et al. [22] investigated performance of
large capacity propane heat pump with low charge heat exchangers.
Shell-and-tube heat exchangers using minichannels were tested along with
conventional brazed plate heat exchangers. It is shown that a 100 kW
heat pump without a liquid receiver can be run with around 3 kg of
propane using a plate condenser and a plate evaporator. Using the
minichannel condenser, around 0.8 kg (25% of the total mass) reduction
can be obtained with a negligible performance loss.
Hrnjak and Litch [23] presented experimental results from a low
charge and compact ammonia chiller. It was equipped with an air-cooled
condenser with microchannel aluminium tubes and a plate evaporator.
Charge, heat transfer, and pressure drop measurements were taken for a
serpentine flat macro tube and parallel flow microchannel tube
condensers. Condenser performance was quantified in terms of heat
capacity, refrigerant and air side pressure drops, heat transfer
coefficient values, and refrigerant inventory. Comparisons show the
superiority of the microchannel design. Microchannel (Dh = 0.7 mm)
charge is an average of 53% less than for the serpentine (Dh = 4.06 mm).
The "microchannel" condenser charge per capacity ratio is
around 76% less than for the "macrochannel" serpentine
condenser.
Another important observation which can be found in [23] considers
connection between subcooling and charge. According to the article, the
liquid subcooling is a large contributor to total charge. The relative
predicted charge contributions from the refrigerant phase zones for the
data point with the highest liquid subcooling tested are 0.5% from
superheated vapour, 29.2% from the two-phase region, and 70.3% from
liquid subcooling. From the data point with the lowest liquid
subcooling, the contributions are 0.5% from superheated vapour, 60.1%
from the two-phase region, and 39.4% from liquid subcooling. Even though
the subcooling region is only a small portion of the total tube length,
it holds most of the total inventory. Thus it is advantageous to reduce
subcooling not only for increased heat transfer, but to reduce
refrigerant charge.
4. Calculation of the refrigerant charge
The calculation of refrigerant charge in a single phase pipe
(liquid or vapour), is easy. The charge in a receiver depends on the
shape and the filling ratio. The major difficulty is evaluation of the
two-phase components (heat exchangers). There are a lot of works,
analyzing various aspects of two-phase flow. For example [24] provides
an analysis of the heat transfer for condensation process and [25]
analyzes pressure changes of condensing annular flow and [27-29]
analyzes charge distribution.
The two-phase flow can adopt various flow patterns. To determine
the fluid charge, it is necessary to know the proportion of vapour and
liquid at any location. This proportion differs from the volume
fraction, mass flow rates and densities. In order to evaluate the
refrigerant charge, one must know the void fraction or the averaged
volumetric fraction of gas in two-phase flow. At the i-th position the
void fraction can be defined as
[[epsilon].sub.vi] = [dV.sub.v.i]/[dV.sub.i] =
[A.sub.v,i]/[A.sub.i] (1)
where [dV.sub.i] is an elementary volume, [dV.sub.v,i] is volume of
gas in elementary volume, [A.sub.i] is cross-section, [A.sub.v,i] is the
fraction of the cross section occupied by gas.
The mass contained in the entire volume V (the total charge) is
[MATHEMATICAL EXPRESSION NOT REPRODUCIBLE IN ASCII.]
where [[rho].sub.vi], [[rho].sub.ii] are vapour and liquid density
(kg/[m.sup.3]).
To calculate the refrigerant charge it is necessary to know the
void fraction. It is usually linked to vapour quality x ([kg.sub.v]/kg),
which is the fraction of total mass flow which is in the gas form.
The average vapour and liquid velocities [u.sub.vi] and [u.sub.li]
are given by
[u.sub.vi] = [G.sub.vi]/[[rho].sub.vi] [[epsilon].sub.vi] (2)
[u.sub.li] = [G.sub.li]/[[rho].sub.li](1-[[epsilon].sub.vi] (3)
where [G.sub.vi], and [G.sub.li] are vapour and liquid mass fluxes
(kg/([m.sup.2]s)) at a given position i.
The slip ratio is
[S.sub.i] = [u.sub.vi]/[u.sub.li] (4)
Using these equations the void fraction is connected to the quality
[MATHEMATICAL EXPRESSION NOT REPRODUCIBLE IN ASCII.] (6)
The thermodynamic terms can be found when temperature and pressure
are known. The slip ratio is determined using correlations. The simplest
approach is to consider the gas-liquid mixture as a homogeneous flow,
where the average liquid velocity is equal to the average gas velocity
([S.sub.i] = 1). Then a void fraction is equal:
[MATHEMATICAL EXPRESSION NOT REPRODUCIBLE IN ASCII.] (7)
This relation serves as a reference for other existing
correlations.
Premoli et al. [26] assumed an annular flow in tubes and developed
the correlation for the slip ratio:
[MATHEMATICAL EXPRESSION NOT REPRODUCIBLE IN ASCII.]
with
[MATHEMATICAL EXPRESSION NOT REPRODUCIBLE IN ASCII.]
where [MATHEMATICAL EXPRESSION NOT REPRODUCIBLE IN ASCII.] is Weber
number; [Re.sub.l] = [GD.sub.h] (1-x)/[[mu].sub.l], Reynolds number for
liquid; [Re.sub.lo] = [GD.sub.h]/[[mu].sub.l], is Reynolds number for
liquid only; [D.sub.h] is hydraulic diameter, m; [sigma] is surface
tension, N/m; G is mass flux, kg/([m.sup.2] s); [[mu].sub.i] is liquid
dynamic viscosity, Pa s.
According to Rice [27], Premoli correlation is one of the most
effective for refrigerating systems. According to Kuijpers et al. [28],
only the Premoli correlation gives satisfactory results for the charge
calculation in a condenser, while homogeneous model underestimates the
charge in a condenser. For Farzad and O'Neal [29], models depending
on the mass flux, such as Premoli correlation, predict a refrigerant
charge that is more significant and is more effective.
5. Superheat in evaporator and subcooling in condenser
Superheat in evaporator for TXV and EEV controlled systems does not
depend on refrigerant charge, except of the cases of significant
undercharge (below 25% of optimal charge [2, 3]). At 50% undercharge [2]
the superheat rises to approximately 10 K. The high superheat at low
charge levels is a result of insufficient refrigerant in the evaporator
which leaded to larger evaporator area devoted to superheating. Zero
superheat would be optimal, but TXV and EEV are not able to work at such
settings.
Considering the influence of refrigerant subcooling in condenser,
different sources give contradictory information. In the literature it
is generally taken for granted that for optimal operation there should
be no subcooling. According to Stoecker [30], subcooling is not normally
desired, since it indicates that some heat transfer surface that should
be used for condensation is used for subcooling. This reduces the
cooling, and condensing pressure increases. Vjacheslav et al. [13] in
their algorithm for optimal mass charge evaluation also assumed that
optimal conditions corresponds to the state where the refrigerant is
fully condensed, or minimal subcooling just enough to ensure stable
operation.
However, in the works [3-5], [8], [10] and [21] we have different
results. In [3] it was found that subcooling at optimal charge was more
than 5 K. At -33% undercharge the subcooling was still above 2 K. Choi
and Kim [4] also found significant subcooling of 4-5 K at optimal charge
for EEV controlled heat pump with R22 refrigerant (Fig. 3). The
subcooling for similar system with R407C [5] was a bit smaller, but
still significant 2-3.5 K. Comparing [4] and [5] we can see that for
different refrigerants subcooling at optimal charge is different--for
R22 the subcooling is almost two times bigger, than for R407C. Primal et
al. [21] also found that optimum charges for each heat source
temperature correspond to a sub-cooling of 4-5 K. From the Fig. 3 we can
also see, that even at -20% undercharge we still have full condensation
and 1 K subcooling.
[FIGURE 3 OMITTED]
Jensen and Skogestad [31] also investigated optimality of
subcooling. For analyzed ammonia refrigerating system contrary to
popular belief they found that subcooling by 4.66 K reduces the
compression work by 1.74% comparing to the case with saturation out of
the condenser. The condensing pressure increases, but it is compensated
by reduction in flowrate. According to their estimation the improvement
of 2% would be larger if the pressure drop in the piping and equipment
was accounted for in the model.
The connection between charge, subcooling and performance for the
unit without liquid receiver is analyzed in deep by Corberan et al. [8].
According to their analysis the influence of the charge in such system
is attributable to the fact that extra refrigerant must find space
inside the refrigerant circuit. The only way for the refrigerant cycle
to react when the charge is increased is by increasing the fraction of
the condenser which is full of liquid and therefore increasing the
subcooling. To increase the subcooling, an increase in the heat
transferred from the condenser to the secondary fluid must occur; hence,
the condensing temperature and pressure must increase. The increase in
subcooling at the highest charges is due to increase of the saturation
temperature at higher condensation pressures and not to a decrease in
the outlet refrigerant temperature. The increase in the subcooling
always has a positive effect on the COP. On the other hand, the
necessary increase in condensation pressure to produce the higher
subcooling produces a decrease in the COP. Therefore, one effect is
positive while the other is negative; this leads to the observed maximum
in COP. The rapid decrease of performance, both capacity and COP at low
charges, when the charge is further reduced is due to the appearance of
bubbles at the inlet of the expansion valve.
The subcooling increases while the charge is increased from the
minimum charge (which corresponds to saturation outlet). Low subcooling
is obtained with an almost undetectable increase in condensation
pressure, this leading to an effective increase in COP. However, when
small temperature approach is attained, the increase in subcooling
requires a proportional increase in the condensation temperature,
quickly degrading the COP. As a result the optimum subcooling is mostly
imposed by the temperature approach at the outlet of the condenser for 0
K subcooling. The optimum subcooling of a refrigeration unit will depend
mainly on the condenser performance. Higher number of transfer units
(NTU) will lead to a lower value of the optimum subcooling since the
condensation temperature will become closer to the water temperature.
This conclusion is in line with [31] according to which the optimal
degree of sub-cooling becomes smaller as the heat transfer (UA-value) is
increased. With an infinite heat transfer area the subcooling is not
optimal.
6. Strategies of charge reduction
Palm [32] investigated refrigerating system with minimum charge of
refrigerant. In addition to mini-channel heat exchangers, his
suggestions for charge reduction are (i) use of indirect system, (ii)
use of low-pressure receiver in the suction line rather than the common
high pressure receiver in the liquid line, (iii) capillary tube used as
expansion device, (iv) use compressor with small internal volume and
small oil charge, (v) use non-miscible oils. When using secondary
refrigeration, the power consumption increase (indirect TEWI) is
compensated by the charge reduction (direct TEWI).
The influence of evaporator's supplying mode was investigated
by Vrinat et al. [33]. They have found that the liquid filling rate of
flooded evaporators would be a little higher than that of direct
expansion fed evaporators with a respectively, 25% and a 10% volume
filling. A strict concern of charge reduction will result in preferring
the evaporator's direct expansion supplying.
Poggi et al. [34] presented a review of the refrigerant charge
studies in a refrigerating plant and evaluation of the influence of the
refrigerant charge on COP and on the cooling capacity.
7. Conclusions
Because of the influence of HCFC and HFC refrigerants to the direct
greenhouse effect, it is important to reduce their atmospheric emission.
Therefore a reduction of the charge in the system is significant goal to
achieve.
Summarizing the available works considering refrigerant charge we
can see that the refrigerant mass charge in the system is linked to the
system performance. Independently on the system, too little charge will
cause draining of the condenser into the evaporator, two-phase feeding
of expansion valve (incomplete condensation) and inadequate filling of
evaporator.
As long as the charge is sufficient to ensure the complete
condensation, the effect of further charge increase depends on
refrigerating system used. Most of the discussed works investigated the
systems without a receiver. Bjork and Palm [17, 18] and Ratts and Brown
[14] investigated refrigerating systems with a low side receiver, but
because of different control systems application of their results to
transport refrigerating unit with eutectic plates is limited.
If the system allow liquid subcooling in condenser (no high
pressure liquid receiver present in the system), the unit performance
depends on the charge. For such system it is possible to determine
refrigerant charge, which maximizes refrigerating system COP. Such
charge is called "optimal charge". Some COP increase over the
case of complete condensation (saturated outlet) is achieved through
liquid subcooling in condenser. The expected increase is about 2% plus
some positive effect from lower pressure drop in the piping and
equipment. The positive effect depends on refrigerant used, type of
condenser (air cooled or water cooled), UA-value of condenser, hydraulic
losses in evaporator etc.
However, this COP increase is not free. The liquid subcooling is a
large contributor to total charge since the subcooling region holds
significant fraction of the total charge inventory. Experimental proof
for this statement may be found in various sources, for example in
[2-7]. In these works different systems were analyzed but similar
conclusions were obtained. Significant performance degradation is
observed when the charge reduction exceeds 25% from the optimal charge.
However, charge reduction up to 20% is possible without significant
deterioration of performance, and at 10-15% of charge reduction the
effect on performance is negligible for systems with TXV or EEV. It is
safe to suggest, that incomplete condensation occurs only when charge
reduction is 20--25% from optimal and all (rather insignificant)
efficiency increase is the effect of liquid subcooling in condenser.
Thus if the low charge system is on target, it is advantageous to
reduce subcooling. Actually, when selecting a charge for low charge
system one should not try to optimize the charge considering maximum
COP, but rather just ensure complete condensation. This will cause some
performance degradation, but this may be compensated by other means with
lower influence to charge. Such system could be the system with high
pressure liquid receiver, in which liquid subcooling is not allowed by
design. If liquid level in the receiver is high enough to avoid the
appearance of bubbles at the inlet of the expansion valve, the variation
of charge should only affects the level of liquid refrigerant in the
receiver and, therefore, the unit performance becomes non-dependent on
the charge.
The big attention should be paid to condenser, where the biggest
part of the charge is located. The microchannel condenser is a good
choice for low charge system.
Considering vapour superheat in evaporator, the relationship to
refrigerant charge is weak. In the most of discussed systems the
superheat was determined by the control system rather than by the
charge. The exception is the case of significant undercharge when the
inadequate feeding of evaporator causes the increase of superheat. With
the increase of superheat, the charge in evaporator decreases, but this
can not be considered a charge reduction strategy since the negative
effect on performance is more pronounced. Actually it would be
preferable to have a system with no superheat. Potentially this could be
ensured by the low-charge system with low pressure receiver, recommended
by Palm [30].
Considering the expansion device, both the systems with TXV and EEV
are considered less sensitive to refrigerant charge, when compared to
system with capillary tube. At the given conditions there are no
significant differences in the charges of TXV and EEV controlled
systems. The one should also have in mind that all here discussed EEV or
TXV systems were analyzed at static conditions (constant condensing and
evaporation temperature). The dynamic mode of operation may introduce
additional factors influencing refrigerant charge.
Also, most of the discussed systems were not equipped with SLHX.
While the SLHX will cause some charge increase in evaporator due to
lower vapour quality after expansion, it also has some positive effects.
First of all, the SLHX may increase the system efficiency (COP). It also
helps ensuring proper liquid subcooling before the expansion device.
This allows decreasing the diameter of liquid lines, which leads to
lower charge. Therefore the SLHX should be carefully estimated when
developing the low charge system.
Acknowledgements
Lithuanian State Studies Foundation and JSC Carlsen Baltic provided
support for this work.
Received February 02, 2011
Accepted November 10, 2011
References
[1.] Harmelink, M.; De Jager, D.; Kerssemeeckers, M.; Hendriks, C.;
Van Brummelen, M. 2002. TEWI: Total equivalent warming impact: A
practical approach. Non-C[O.sub.2] greenhouse gases. Millpress,
Rotterdam pp. 627-632.
[2.] Grace, I.N.; Datta, D.; Tassou S.A. 2005. Sensitivity of
refrigeration system performance to charge levels and parameters for
on-line leak detection, Applied Thermal Engineering 25: 557-566.
[3.] Tassou S.A.; Grace, I.N. 2005. Fault diagnosis and refrigerant
leak detection in vapour compression refrigeration system, International
Journal of Refrigeration 28: 680-688.
[4.] Choi, J.; Kim, Y. 2002. The effects of improper refrigerant
charge on the performance of a heat pump with an electronic expansion
valve and capillary tube, Energy 27: 391-404.
[5.] Choi, J.; Kim, Y. 2004. Influence of the expansion device on
the performance of a heat pump using R407C under a range of charging
conditions, International Journal of Refrigeration 27: 378-384.
[6.] Goswami, D.Y.; Ek, G.; Leung, M.; Jotshi, C.K.; Sherif, S.A.
1997. Effect of refrigerant charge on the performance of air
conditioning systems, Proceedings of the Intersociety Energy Conversion
Engineering Conference 3 (Pt. 4): 1635-1640.
[7.] Farzad, M. 1990. Modelling the effects of refrigerant charging
on air conditioner performance characteristics for three expansion
devices. Dissertation Information Service, Texas A&M University,
UMI, Ann Arbor, MI. 263p.
[8.] Corberan, J.M.; Martinez, I.O.; Gonzalvez, J. 2008. Charge
optimisation study of a reversible water-to-water propane heat pump,
International Journal of Refrigeration 31: 716-726.
[9.] Bjork, E.; Palm, B. 2006. Performance of a domestic
refrigerator under influence of varied expansion device capacity,
refrigerant charge and ambient temperature, International Journal of
Refrigeration 29: 789-798.
[10.] Cho, H.; Ryu, Ch.; Kim, Y.; Kim, H.Y. 2005. Effects of
refrigerant charge amount on the performance of a transcritical
C[O.sub.2] heat pump, International Journal of Refrigeration 28:
1266-1273.
[11.] Rozhentsev, A. 2008. Refrigerating machine operating
characteristics under various mixed refrigerant mass charges,
International Journal of Refrigeration 31: 1145-1155.
[12.] Dmitriyev, V.I.; Pisarenko, V.E. 1984. Determination of
optimum refrigerant charge for domestic refrigerator units,
International Journal of Refrigeration 7: 178-180.
[13.] Vjacheslav, N.; Rozhentsev, A.; Wang, C. 2001. Rationally
based model for evaluating the optimal refrigerant mass charge in
refrigerating machines, Energy Conversion and Management 42: 2083-2095.
[14.] Ratts, E.B.; Brown, J.S. 2000. An experimental analysis of
the effect of refrigerant charge level on an automotive refrigeration
system, International Journal of Thermal Science 39: 592-604.
[15.] Ding, G.; Ma, X.; Zhang, P.; Han, W.; Kasahara, S.;
Yamaguchi, T. 2009. Practical methods for measuring refrigerant mass
distribution inside refrigeration system, International Journal of
Refrigeration 32: 327-334.
[16.] Bjork, E. 2005. A simple technique for refrigerant mass
measurement, Applied Thermal Engineering 25: 1115-1125.
[17.] Bjork, E.; Palm, B. 2006. Refrigerant mass charge
distribution in a domestic refrigerator. Part I: Transient conditions,
Applied Thermal Engineering 26: 829-837.
[18.] Bjork, E.; Palm, B. 2006. Refrigerant mass charge
distribution in a domestic refrigerator. Part II: Steady state
conditions, Applied Thermal Engineering 26: 866871.
[19.] Kuijpers, L.J.M.; Janssen, M.J.P.; Verboven, P.J.M. 1988. The
influence of the refrigerant charge on the functioning of small
refrigerating appliances, ASHRAE Transactions 94: 813-828.
[20.] Primal, F.; Samoteeva, O.; Palm, B.; Lundqvist, P. 2001.
Charge distribution in a 5 kW heat pump using propane as working fluid.
16 Nordiske Kelemede 099, Nordiske Varmepumpedage 29-31, Kebenhvn,
p.299.
[21.] Primal, F.; Palm, B.; Lundqvist, P.; Granryd, E. 2004.
Propane heat pump with low refrigerant charge: design and laboratory
tests, International Journal of Refrigeration 27: 761-773.
[22.] Cavallini, A.; Da Riva, E.; Del Col, D. 2010. Performance of
a large capacity propane heat pump with low charge heat exchangers,
International Journal of Refrigeration 33: 242-250.
[23.] Hrnjak, P.; Litch, A.D. 2008. Microchannel heat exchangers
for charge minimization in air-cooled ammonia condensers and chillers,
International Journal of Refrigeration 31: 658-668.
[24.] Sinkunas, S.; Kiela, A. 2011. Heat transfer for film
condensation of vapour, Mechanika 17(2): 144-148.
[25.] Saffari, H.; Dlir, N. 2011. Effect of friction stress of
droplets with film on prediction of pressure changes in condensing
tubes, Mechanika 17(1): 50-56.
[26.] Premoli, A.; Di Francesco, D.; Prina, A. 1970. Una
correlazione adimensionale per la determinazione delle densita di micele
bifasiche. In: XXV Congresso Nazionale ATI, Triete, Italie, septembre.
1970.
[27.] Rice, C.K. 1987. The effect of the void fraction correlation
and heat flux assumption on refrigerant charge inventory predictions,
In: American Society of Refrigerating and Air Conditioning Engineers
Meeting, New York. 341-357.
[28.] Kuijpers, L.; Janssen, M.; De Wit, J. 1987. Experimental
verification of liquid hold-up predictions in small refrigeration heat
exchanger, In: XVII International Congress of Refrigeration, Wien,
Austria. 307315.
[29.] Farzad, M.; O'Neal, D. 1994. The effect of void fraction
model on estimation of air conditioner system performance variables
under a range of refrigerant charging conditions, Revue Internationale
du Froid 17(2): 85-93.
[30.] Stoecker, W.F. 2004. Industrial Refrigeration Handbook.
McGraw-Hill. 688p.
[31.] Jensen, J.B.; Skogestad, S. 2007. Optimal operation of simple
refrigeration cycles Part I: Degrees of freedom and optimality of
sub-cooling, Computers and Chemical Engineering 31: 712-721.
[32.] Palm, B. 2007. Refrigeration systems with minimum charge of
refrigerant, Applied Thermal Engineering 27: 1693-1701.
[33.] Vrinat, G.; Macchi, H.; Leducq, D. 2000. Estimation de la
charge en frigorige'ne dans les boucles frigorifiques basse
pression (2e'me partie), Revue Ge'ne'rale du Froid. 4p.
[34.] Poggi, F.; Macchi-Tejeda, H.; Leducq, D.; Bontemps, A. 2008.
Refrigerant charge in refrigerating systems and strategies of charge
reduction, International Journal of Refrigeration 31: 353-370.
L. Vaitkus
Kaunas University of Technology, K. Donelaicio g. 20, 44239 Kaunas,
Lithuania, E-mail: liutauras.vaitkus@ktu.lt