首页    期刊浏览 2025年02月28日 星期五
登录注册

文章基本信息

  • 标题:Research of low energy house design and construction opportunities in Lithuania/Mazai energijos naudojancio namo projektavimo ir statybos Lietuvoje galimybiu tyrimas.
  • 作者:Venckus, Nerijus ; Bliudzius, Raimondas ; Endriukaityte, Audrone
  • 期刊名称:Technological and Economic Development of Economy
  • 印刷版ISSN:1392-8619
  • 出版年度:2010
  • 期号:September
  • 语种:English
  • 出版社:Vilnius Gediminas Technical University
  • 摘要:Considering the tendencies of energy production and price, it is becoming urgent to reduce energy consumption in buildings. The European Parliament's Industry Committee (ITRE) on 31 March 2009 stated that, starting from 2019, all newly constructed buildings must produce the same amount of energy they consume. The committee's recommendation adopted by the European Parliament on 23 April 2009 (European Parliament 2009) oblige the Member States to provide intermediate national targets to reduce energy consumption in buildings, i.e. determine the minimum number of buildings with zero energy consumption in 2015 and 2020.
  • 关键词:Architectural design;Architecture and energy conservation;Energy efficient buildings;House construction;Residential construction

Research of low energy house design and construction opportunities in Lithuania/Mazai energijos naudojancio namo projektavimo ir statybos Lietuvoje galimybiu tyrimas.


Venckus, Nerijus ; Bliudzius, Raimondas ; Endriukaityte, Audrone 等


1. Introduction

Considering the tendencies of energy production and price, it is becoming urgent to reduce energy consumption in buildings. The European Parliament's Industry Committee (ITRE) on 31 March 2009 stated that, starting from 2019, all newly constructed buildings must produce the same amount of energy they consume. The committee's recommendation adopted by the European Parliament on 23 April 2009 (European Parliament 2009) oblige the Member States to provide intermediate national targets to reduce energy consumption in buildings, i.e. determine the minimum number of buildings with zero energy consumption in 2015 and 2020.

To implement these intermediate objectives in European Union, a concept of the low energy building was formed. The main idea is that the low energy buildings should consume less energy to compare to buildings built in accordance to the local countries requirements (Jovanovic et al. 2009; Madlener and Alcott 2009). EU member states are developing definitions of low energy buildings, but only in 7 of them these definitions are officially published. Several countries are planning to publish them in the coming year (The European Alliance of Companies for Energy Efficiency in Buildings 2008). In most EU countries, a ratio between the energy consumption is determined, comparing low energy buildings and buildings built according to the normative requirements. In other countries, the specific energy consumption values are defined. They must be fulfilled to include energy-efficient buildings in the low energy buildings group. The most comprehensive and widely used concept of a low energy in Europe is offered by the German scientist W. Feist (Passive House Institute 2009a), also called the passive house concept, where the maximum permissible energy consumption for the heating of the building are presented, and at the same time, the total primary energy consumption is limited. The requirements for building elements thermal properties and the air tightness of the building are also presented in this concept.

Lithuania is also foreseeing the design and construction of low energy buildings. So it becomes necessary to explore the possibilities to use one of these existing design and construction concepts or develop own approaches by using the experience of other countries and adaptation to local Lithuanian climate conditions. The first step to achieve this was completed--the first dwelling house corresponding to the passive house approach was designed and built in Lithuania. The issues that arose during the process and their solutions are presented in this article.

2. Substantial attitudes of the passive house concept

The essence of the passive building's concept is that the building must be properly oriented, sealed and insulated (Passive House Institute 2008) (Stecher and Klingenberg 2008) in a way that a conventional heating system would not be required and the building could be heated by air supplied into the building, the amount of which must conform to the minimal hygiene requirements. In this heating system supplied air is heated by air extracted from the heated space; additional heat source, if needed, and type of energy depend on the situation. As the temperature of air, supplied to the indoor area cannot be greater than 50 [degrees]C, the building heat loss through thermal envelopes must not exceed 10 W/[m.sup.2] (Passive House Institute 2009b) (Bertrand and Rybka 2008). This is achieved by using a thicker insulating layer (Ginevicius et al. 2008) (Zavadskas et al. 2008), choosing windows with low heat transfer characteristics and designing the structural assemblies so that the heat transfer coefficients of thermal bridges do not exceed 0.01 W/[m.sup.2]K. In order to select an energy-efficient heating system, the heat produced by appliances and humans inside the building as well as heat gained through the windows in the form of sun rays must be evaluated (Dombayci 2010). The amount of the solar heat gains depends on the area of translucent envelopes in the building and their cardinal orientation. The best results are achieved when the building is designed so that the rooms which require more light are aimed at the southern part and the corridors, bathrooms, storage or similar areas are aimed at the northern half of the building. The shape of the building must be as close to a cube as possible, in which case it gives the smallest envelope to floor area ratio. The building must be equipped with extra heating device, in order to ensure required temperatures in the rooms during periods of very low external air temperatures or in cases if the ventilation--heating system fails.

Usually low energy building is associated with the passive house concept which was developed in Germany and has the following requirements:

--Extremely good thermal insulation of external building envelope. The heat transfer coefficients of walls, roofs and floors should not exceed 0.15 W/[m.sup.2]K; heat transfer coefficients of windows should not exceed 0.8 W/[m.sup.2]K and the heat transfer coefficients of thermal bridges should not exceed 0.01 W/[m.sup.2]K, whereas the total annual energy requirement to heat the building must be not larger than 15 kWh/[m.sup.2].

--The external envelope of a building should be airtight. Measured air exchange ratio in the building, where the external and internal air pressure is 50 Pa must be no greater than 0.6 times per hour. The natural air change in passive house should not exceed 0.04 times per hour.

3. Planning and envelope structural solutions

Building site and positioning of the rooms:

Passive house was designed and built in the township of Gulbinai in Vilnius city near the lake Gulbinas. The technical characteristics of the building are: heated area (according to the PHPP methodology of calculation)--194.4 [m.sup.2], house height--7.14 m, number of storey's--2. The building was designed in a newly built area so there was a possibility to orient it according to cardinal points (Fig. 1).

The windows of the open area kitchen and living room on the first floor (Fig. 2) and the windows of bedrooms on the second floor are directed to the south - southwest. Staircases, lavatories and a workroom are designed on the first floor. The window area of the southern facade takes up 47.8% of the southern wall, the window area of the northern wall area--5.2%. Calculated annual heat losses through the windows of the building are 22.2 kWh/[m.sup.2] and annual solar heat gains--26.3 kWh/[m.sup.2]. If this building would be designed with the same total amount of windows, but half of them would be oriented to the south and half to the north, the annual heat loss through the windows would remain the same but the annual solar heat gains would drop to 19.4 kWh/[m.sup.2], i.e. by 26.2%.

Windows:

The windows with the heat transfer coefficient from 0.73 to 0.84 W/[m.sup.2]K (depending on the size of the windows) are installed in order to fulfil the passive house concept recommendations. In comparison, if windows conforming to the national regulations STR 2.01.05:2005 were installed, the heat transfer coefficient would be 1.6 W/[m.sup.2]K and annual heat loss through the windows would increase by 100.5% from 22.2 to 44.5 kWh/[m.sup.2]. The design value of windows solar heat gain coefficient g is 0.57 and the annual solar heat gains through the transparent glazing areas reach 26.3 kWh/[m.sup.2]. Protection from the overheating in the summer time is provided by mobile shutters and a curtain on the southern side of the building.

[FIGURE 1 OMITTED]

[FIGURE 2 OMITTED]

Roof construction:

The passive house roof was designed with a one slope (Fig. 3). The roof structure consists of the wooden I-beams and mineral wool insulation. The roof slope oriented to the north, inclination 5%. Between the I-beams 40 cm mineral wool layer is installed. The heat transfer coefficient of this roof is 0.08 W/[m.sup.2]K (regular value--0.16 W/[m.sup.2]K). The designed annual heat loss through the roof is 4.85 kWh/[m.sup.2] and equal to 52.2% of heat loss through a similar roof conforming to the national regulations.

Walls:

Load-bearing walls are made of clay bricks. Mineral wool insulation is used to insulate the walls. Wooden logs or thin-layer plaster are used as external finish, depending on the type of the wall. Two types of external walls constructions are designed: ventilated wall (Fig. 4) and rendered facade (Fig. 5). The thickness of the mineral wool layer is 35 cm. The heat transfer coefficient of walls varies from 0.10 to 0.11 W/[m.sup.2]K (regular value--0.20 W/[m.sup.2]K). The design value of annual heat loss through the walls is 18.33 kWh/[m.sup.2]. It is 54.5% of the heat loss of through similar walls conforming to national standards.

[FIGURE 3 OMITTED]

[FIGURE 4 OMITTED]

[FIGURE 5 OMITTED]

Floor:

Floor on the ground is insulated with a 33 cm extruded polystyrene foam layer. The heat transfer coefficient of the floor is 0.12 W/[m.sup.2]K (normative value--0.25 W/[m.sup.2]K). A design annual heat loss through the floor is 4.1 kWh/[m.sup.2] and it comes to 48.7% of the heat loss of the same structure conforming to national standards.

Thermal bridges:

Building elements and their connections should be built in a way that the values of the heat transfer coefficients of the linear thermal bridges do not exceed the guidelines by PHPP--0.01 W/[m.sup.2]K .

Building air tightness:

An air-tight inner layer of the wall must be assembled and appropriate combination of insulation and wind protective layers must to be installed to ensure the air tightness of the building. The inner surface of the load-bearing walls, made of clay bricks was plastered to ensure air tightness. Ventilated facade of the building (Fig. 4) is constructed from mineral wool insulation wind protection slabs on top of low density insulation layer in order to decrease the air permeability. The building was inspected for air leakages before installation of internal finishes. Identified leak sites have been sealed. Therefore the final result of the measurement was better than the minimum requirements.

The measured building air changes at 50 Pa difference of external and internal air pressure was 0.4 times per hour (PHPP recommendations [less than or equal to] 0.6 times per hour). In real operating conditions, the air exchange does not exceed 0.1 times per hour. If the air tightness of the building meets the requirements of STR 2.05.01:2005 (1.5 times per hour at 50 Pa pressure difference) the annual building heat losses due to infiltration can reach 40 kWh/[m.sup.2].

Ventilation:

In order to reduce the consumption of energy required for the heating--ventilation system, a heat recovery device with a heat recovery efficiency of 82 % was selected. Air heating--ventilation system takes outside air and supplies it through the garage to the heat exchanger device. This device heats incoming external air by using the heat extracted from outgoing inside air. Air of the required temperature is supplied to the rooms, and removed from the kitchen and the bathrooms.

Reserve heating source:

The designed heating system provides the required indoor temperature only when the outside air temperature is not below 12[degrees]C--15[degrees]C (Pupeikis et al. 2010). At low external air temperatures, it is necessary to increase the temperature of supplied air over the 50 [degrees]C limit or the air flow rate. The first case disagrees with the hygienic requirements, in the second case the required ventilation air quantity is exceeded, and the velocity of air movement in the rooms is increased. Therefore, the required thermal energy at the coldest period will be supplied by additional floor heating, with the power of 8.9 W/[m.sup.2], which consists of one pipe installed in the floor plate in the perimeter.

Building energy performance:

Energy demand and building energy consumption were calculated by passive house planning package (PHPP) and according to national regulations. The result is presented in Table 1.

4. Passive house benefits

The annual heat consumption of the building decreases from 72 kWh/[m.sup.2] to 15 kWh/[m.sup.2]. The inner surface temperature of non-transparent envelopes during the coldest five day period does not fall more than 2 [degrees]C below the internal air temperature, therefore comfort conditions are always ensured (Jurelionis and Isevicius 2008). Temperature difference of the glass inner surface and internal air temperature during the coldest day is 4.1 [degrees]C, when the windows with a heat transfer coefficient of 0.8 W/[m.sup.2]K are installed.

Proper air tightness of the building ensures that the ventilation heat loss decreases from 46 kWh/[m.sup.2] per year (STR 2.05.01:2005, for a building that complies with the requirements of national standards) to 7.6 kWh/[m.sup.2] per year (Fig. 6). In addition, up to 80% of the required heat is recovered in the heating--ventilation system using the recuperative device. In an air tight building, air is supplied to the rooms through filters; therefore it is clear of dust.

[FIGURE 6 OMITTED]

According to the national regulations, a heating season of 6 months is required for a new house in Lithuania. The duration of the heating season of the passive house is reduced to five months (Fig. 7). In October and April, the heat losses are covered by the internal heat gains and solar gains through the windows.

The air tightness of the building and a thick layer of thermal insulation in the envelopes, triple glazing in the windows provide protection from external noise.

[FIGURE 7 OMITTED]

5. Differences between the passive house concept and the requirements of Lithuanian building standards

Passive house design program PHPP (Passive House Planning Package) was used for energy consumption calculations for the passive house in Lithuania, whereas design values and normative recommendations adapted for this program.

The main differences were observed while calculating between the PHPP methodology and methodology used in Lithuania, and the differences between the thermal and technical parameters used for calculation in these phases:

--different external climate data is used in calculations;

--different evaluation of internal heat gains during the exploitation period;

--the method of determining the demand of necessary air supply to ensure the internal microclimate parameters varies;

--different performance evaluation of the ventilation equipment.

For the building heat losses calculations, the average external air temperature during the heating season in Lithuania is used. The PHPP program uses average monthly temperatures to evaluate exact heat demand. For the building heating load calculations according to STR 2.09.04:2008, outdoor air temperature is selected from the national building regulations (RSN 156-94 "Climatology of Buildings") depending on the thermal inertia of the building envelope. Potential temperatures for the heating load calculation are: the average of the coldest day, the average of the coldest day and the coldest five days, the temperature of the coldest five days. The temperatures used in the PHPP program for the heating load calculation are: the temperature of the coldest days on a sunny day, the average temperature of a cloudy day of average cold. In the PHPP program, solar radiation data in Lithuania's climate zone from the 1981-2000 period is used, while solar radiation statistics according to Lithuanian climatology RSN 156-94 were prepared using data from the 1955-1980, 1955 to 1991 periods.

The design values of internal heat gains have a significant impact on the calculation of the balance of passive house heat losses and internal gains. In the case of design model, and without knowing the appliances used, the total number of inhabitants and other specific exploitation conditions, PHPP recommends using an internal heat gain that is not greater than 2.1 W/[m.sup.2], with regards to the influence of inhabitants and household appliances. According to STR 2.09.04:2008, the heat release of inhabitants in residential apartments of one or two flats is 1.2 W/[m.sup.2], and the heat release of electrical lighting and appliances is--1.6 W/[m.sup.2]. Due to such differences, a difference up to 2.5 kWh/[m.sup.2] of energy consumption for heating per year is achieved.

When calculating the heat losses due to ventilation, it was determined, that the difference between the amount of air extracted (Table 2) from the rooms according to STR 2.09.02:2005 (Annex 1) and PHPP varies from 17 to 63%.

For the evaluation of the efficiency of the ventilation heat recovery unit using the PHPP program, a further evaluation of the energy consumption for the heat recovery process is needed. This reduces the manufacturer declared efficiency up to 12% (Fahlen et al. 2006).

6. Passive House concept integration to Lithuanian climatic conditions

After the passive house was designed, using Lithuanian climatic data (Vilnius city), an evaluation of the building's heat demand was made, using the climate data of various European cities. The calculation results (Table 3) indicate that same house, built in Austria, would use two times less energy for heating than it does in Lithuania, built in Helsinki -60% more. The heat transfer coefficients of the walls, roof and floor of the Lithuanian passive house are (0.10 to 0.12 W/[m.sup.2]K) 30%-50% lower than ones presented in the passive house concept. According to PHPP, in a German house it is enough to achieve a threshold value of (0.15 W/[m.sup.2]K). Such improvement of the thermal properties of envelopes in Lithuania is related to the technical capabilities of their installation and their cost.

While designing and building the passive house in Lithuania, all solutions to achieve required insulation level were developed and implemented. Building air tightness level even exceeds recommended value, what means high quality designers and builders attitude. The cost of the passive house price increased by 11% to compare to a same building built on a normative level. At this moment, energy consumption monitoring of the passive house is carried out, the purpose of which is to check the building's energy performance and compare it to calculations.

Analysis of the results have also shown that in colder climate countries such as Finland, Sweden and Norway, it would be difficult to achieve the requirements provided in the passive house concept, or it would require specific solutions, which would significantly increase the cost of the building. Therefore, in these countries, the design and construction of passive houses generally comply with the passive house concept, but the requirements for energy consumptions are adjusted according to the climate conditions. Such provisions would also be appropriate in Lithuania.

7. Conclusions and recommendations

1. Technical analysis of the design and construction of the building's envelopes shows that it is possible to reduce heat losses through the envelopes by about 30% compared to a building designed according to national standards.

2. Adopted air heating system with efficient heat exchange device reduces the heating demand of the building for ventilation by six times. To achieve this value, a high level of air tightness is required.

3. With the correct combination of insulation of the building's envelope and heating ventilation system, the energy consumption for heating is reduced approximately four times compared to a building conforming to the national requirements. Therefore such a building can be assigned to the category of very low energy houses.

4. In order to accelerate the construction of low energy houses, it is necessary to improve the technical Lithuanian construction regulations, to introduce more accurate calculation methods for heat losses through envelopes, methods of evaluation of solar heat gains and influence of heat release inside the buildings.

5. The definitions of low energy buildings and very low energy buildings should be established in Lithuania, as well as limits of energy consumption for heating of such buildings. Air tightness tests and recommended values of primary energy consumption must be established.

6. The practice of low energy building design and construction would enable a smooth transition to construction of net zero-energy buildings in Lithuania

doi: 10.3846/tede.2010.33

Received 30 October 2009; accepted 5 August 2010

References

Dombayci, A. O. 2010. The prediction of heating energy consumption in a model House by using artificial neural networks in Denizli-Turkey, Advances in Engineering Software 41: 141-147. doi:10.1016/j.advengsoft.2009.09.012

Bertrand, O.; Rybka, A. 2008. Design of a passive hotel in Rzeszow, Poland, in Low Carbon Urban Built Environments Conference, Munchen, Germany, September 2008.

European parliament [online] 2009/04/24 [cited 4 April 2010]. Available from Internet: <http://www.europarl.europa.eu>.

Fahlen, P.; Voll, H.; Naumow, J. 2006. Efficiency of pump operation in hydronic heating and cooling system, Journal of Civil Engineering and Management 12(1): 57-62.

Ginevicius, R.; Podvezko, V.; Raslanas, S. 2008. Evaluating the alternative solutions of wall insulation by multicriteria methods, Journal of Civil Engineering and Management 14(4): 217-226. doi:10.3846/1392 3730.2008.14.20

Jovanovic, M.; Afgan, N.; Radovanovic, P.; Stevanovic, V. 2009. Sustainable development of the Belgrade energy system, Energy 34: 532-539. doi:10.1016/j.energy.2008.01.013

Jurelionis, A.; Isevicius, E. 2008. CFD predictions of indoor air movement induced by cold window surfaces, Journal of Civil Engineering and Management 14(1): 29-38. doi:10.3846/1392-3730.2008.14.29-38

Madlener, R.; Alcott, B. 2009. Energy rebound and economic growth: A review of the main issues and research needs, Energy 34: 370-376. doi:10.1016/j.energy.2008.10.011

Pupeikis, D.; Burlingis, A.; Stankevicius, V. 2010. Required additional heating power of building during intermitted heating, Journal of Civil Engineering and Management 16(1): 141-148. doi:10.3846/ jcem.2010.13

Passive House Institue [online]. Passive House: learn the basic knowledge [cited 20 December 2008]. Available from Internet: <http://www.passiv.de/07_eng/index_e.html>.

Passive House Institue [online]. What Can be a Passive House in Your Region with Your Climate? [cited 20 November 2009a]. Available from Internet: <http://www.passiv.de/07_eng/index_e.html>.

Passive House Institute [online]. Passive House: Comfort through Efficiency [cited 25 December 2009b]. Available from Internet: <http://www.passivhaustagung.de/Passive_House_E /passivehouse.html>.

RSN 156-94. 1995. Statybine klimatologija [Climatology of buildings]. Vilnius.

Stecher, D.; Klingenberg, K. 2008. Design and Performance of the Smith House, A Passive House, ASHRAE Transactions, 209-217.

STR 2.05.01:2005. Pastatu atitvaru silumine technika [Thermal technology of building elements]. Vilnius: Ministry of Environment of the Republic of Lithuania.

STR 2.09.04:2008. Pastato sildymo sistemos galia. Silumos poreikis sildymui [Power of the building heating system. Energy consumption for the heating]. Vilnius: Ministry of Environment of the Republic of Lithuania.

STR 2.09.02:2005. Sildymas, v?dinimas ir oro kondicionavimas (1 priedas) [Heating, ventilation and air conditioning]. Vilnius: Ministry of Environment of the Republic of Lithuania.

The European Alliance of Companies for Energy Efficiency in Buildings. 11 December, 2008 [cited 2 April 2010]. Available from Internet: <http://euroace.org/verylowenergybuildings/index.htm>.

Zavadskas, E. K.; Kaklauskas, A.; Turskis, Z.; Tamosaitien?, J. 2008. Selection of the effective dwelling house walls by applying attributes values determined at intervals, Journal of Civil Engineering and Management 14(2): 85-93. doi:10.3846/1392-3730.2008.14.3

Nerijus Venckus (1), Raimondas Bliudzius (2), Audrone Endriukaityte (3), Josifas Parasonis (4)

(1) Department of Civil Engineering and Architecture, Kaunas University of Technology, Student? g. 48, LT-51367Kaunas, Lithuania, e-mail: venckus.nerijus@gmail.com

(2) Institute of Architecture and Construction, Kaunas University of Technology, Laboratory of Thermal Building Physics, Tunelio g. 60, LT-44405 Kaunas, Lithuania, e-mail: silfiz@asi.lt

(3) Department of Architectural Engineering, Vilnius Gediminas Technical University, Sauletekio al. 11, LT-10223 Vilnius, Lithuania, e-mail: audrone.endriukaityte@paroc.com

(4) Department of Architectural Engineering, Vilnius Gediminas Technical University, Sauletekio al. 11, LT-10223 Vilnius, Lithuania, e-mail: josifas.parasonis@vgtu.lt

Nerijus VENCKUS. PhD student of Civil Engineering, Researcher at the Laboratory of Thermal Building Physics of the Institute of Architecture and Construction, KTU. Research interests: unsteady heat transfer, thermal energy balance of buildings.

Raimondas BLIUDZIUS. Doctor, Head of the Laboratory of Thermal Building Physics at the Institute of Architecture and Construction, KTU. Research interests: thermal processes in building, thermal and hydro properties of building materials and elements.

Audrone ENDRIUKAITYTE. Doctor, UAB "Paroc" marketing director, Senior Lecturer at the Department of Architectural Engineering, Vilnius Gediminas Technical University (VGTU). Research interests: building structures and thermal processes in buildings.

Josifas PARASONIS. Professor, Doctor Habil. Vilnius Gediminas Technical University (VGTU), Sauletekio al. 11, Vilnius, Lithuania. PhD, Vilnius Civil Engineering Institute (VISI, now VGTU, 1973). Doctor Habil. (technical sciences, NIIZB, Moscow, 1992). Professor, VGTU (1994). Head of Dept of Architectural Engineering. Author of over 170 publications (research results and study guides). Research interests: reliability of structures and buildings; energy efficient and resource saving buildings.
Table 1. Technical and economical characteristics of the building

                                                         According to
                                             Passive       national
Characteristic                                house       regulations

U-value (heat transfer coefficients):
  External walls                            0.10-0.11        0.20
  Roof                                        0.08           0.16
  Floor                                       0.12           0.25
  Windows                                      0.8            1.6
Transmition heat losses, kWh/[m.sup.2]        41.9           62.5
  per year
Ventilation heat losses, kWh/[m.sup.2]         7.6           46.0
  per year
Annual heat demand kWh/[m.sup.2] per           15             72
  year
Primary energy demand, kWh/[m.sup.2]           107            166
  per year
Heatin load during coldest period,             16             57
  W/[m.sup.2]

Table 2. Required extracted air flow ratio from the rooms

Name of the room     Air flow ratio      Air flow ratio
                      according to      according to PHPP
                        national
                      regulations

     Kitchen         72 [m.sup.3]/h      60 [m.sup.3]/h
    Bathroom         54 [m.sup.3]/h      40 [m.sup.3]/h
     Shower          54 [m.sup.3]/h      20 [m.sup.3]/h
       WC            36 [m.sup.3]/h      20 [m.sup.3]/h

Table 3. Heating energy consumption depending on climate

    State             City           Energy consumption for heating
                                         per year, kWh/[m.sup.2]

   Germany           Hanover                      11.2
   Austria          Salzburg                       7.4
 Switzerland    Bern (Liebefeld)                   8.4
   Denmark         Copenhagen                     10.4
   Ireland           Dublin                        3.9
   Poland            Warsaw                       14.5
   Finland          Helsinki                      24.3
联系我们|关于我们|网站声明
国家哲学社会科学文献中心版权所有