Automated reserve arming control system for power supply.
Badea, Milian ; Moraru, Sorin-Aurel ; Grigorescu, Costin-Marius 等
Abstract: This paper presents an application that can be used to
maintain the power supply for industrial consumers. The power supply is
maintained by monitoring the presence or absence of voltage on power
lines and selecting the corresponding one to provide electrical energy
for the system's consumers. The monitoring and control system is
composed of a Siemens 315 PLC, a Siemens MP 277 touch screen operating
panel and a series of Sentron PAC3200 power monitoring devices that
communicate with each other using Profibus, MPI and Modbus networks and
communication protocols.
Key words: monitoring device, energy, power, modbus, profibus
1. INTRODUCTION
The high reliability of electrical energy supply of industrial
processes is a very important issue because it can prevent the losses
and damages that can be produced by intermittent electrical energy
supply. In order to achieve this, the supply with electrical energy of
the industrial consumers can be made using different ways and different
equipment.
The application presented in this paper makes the Automated Reserve
Arming (ARA) in the electrical energy supply system of a commercial
unit. This supply system consists of two separate supply lines and two
energy generators. Switching between the supply lines and the energy
generators is made in automatic manner in order to provide almost
continuous electrical energy supply (Margineanu, 2005, Vladareanu,
2005).
2. SYSTEM STRUCTURE
The Automated Reserve Arming project is made with the help of the
following hardware equipment:
* A Siemens CPU 315-2-DP PLC.
* A Siemens MP 277 Operating Panel.
* A series of Sentron PAC3200 power monitoring devices.
The structure of the entire system is presented in Fig. 1 and the
roles of the equipment are presented in the following paragraphs.
The Siemens MP 277 Operating Panel is used to display the
parameters of the electrical energy supply network and communicates with
the PLC unit through a MPI network.
The Siemens Sentron PAC3200 power monitoring devices communicate
with the PLC unit through a Profibus network. These devices monitor a
number of network parameters and send them to the PLC unit (Margineanu,
2005, Popescu, D., 2005). These measurements are very useful for the
human operator because they show exactly all the system state changes
that appear while the system is in operation.
The information from the power generators is received through a
RS485 network using the Modbus communication protocol (Popescu, S.,
2005).
The supply with electrical energy is made through two separate
transformers, one being primary and the other the reserve. The system
also uses two generators that can provide the needed electrical energy
in the case of voltage lask on both transformer lines. Switching between
the reserve and the generators is made using automated arming switches.
[FIGURE 1 OMITTED]
The state of these switches is read using the PLC's digital
inputs and the command to open or close one is made using the PLC's
digital outputs. The protection against simultaneous closing of both
line switches is implemented at both hardware and software levels.
Switching between the supply lines is made based on the presence or
absence of voltage on them. To verify the presence or absence of the
three voltage phases on the supply lines the following methods are
implemented:
* Using relays that detect the presence or absence of voltage.
Checking the values provided by the three Siemens Sentron PAC3200
power monitoring devices.
3. APPLICATION PRESENTATION
Three operating modes were implemented for the application. These
modes are:
* Manual.
* Semi automatic.
* Full automatic.
The manual operating mode allows the human operator to close or
open any switch. The hardware level protection is still present.
The semi automatic operating mode consists of making a complete
switching operation from one power source to another one. The start of
the sequence is made using a button from the system's operating
panel.
The sequence consists of the following steps:
* Opening the already closed switch.
* Making a temporization to wait for the electric arc to disappear.
* Closing the switch for the desired power source.
The full automatic operating mode represents the normal operating
mode of the system. The network is monitored by the Sentron devices and
the voltage detection relays.
The transformer that powers the consumers when the system goes into
this operating mode is considered to be the main one. It will power the
consumers as long as the relays detect the presence of voltage on its
lines.
If, for any reason, the voltage is not detected then the system
will wait for 2 seconds to avoid switching in the case of very short
power failures and after that time it will make the switch to the second
transformer which is stored as the reserve one.
If the voltage is absent also on the lines of the second
transformer, then the backup generators will be powered on. When the
voltage is present again, the power source is chosen using the following
criteria:
* If the voltage is present on the lines of both transformers, then
the system will select the main transformer.
* If the voltage is present on the lines of the reserve
transformer, then this one will be selected. In both cases, the backup
generators will be powered off.
The human operator can view the real time value of the main system
perameters on the operating panel. From the defined screens, the most
important one is represented by the single line diagram screen presented
in Fig. 2 (Simatic HMI MP 277 Operating Instructions, 2009).
This screen presents the status of the switches, the presence or
absence of voltage on different sections of the power lines and the
values of the power network parameters received from the Sentron PAC3200
power monitoring devices. These values are received through the Profibus
network.
The elements that are presented with the red color on this screen
are currently powered on and those presented with black are currently
powered off.
The variations and events are treated separately. They are stored
in a history location that can keep up to 200.000 records. If this value
is exceded, then the oldest records are erased to allow the new ones to
be stored. The events are stored in order to he able to replay some
sequences of the ARA system (Springer, 2006).
The alarms are represented by actions that can endanger the
system's operation and need to be treated urgently. They block the
ARA system in its current state and don't allow for any switching
operation until the human operator acknowledges them by pressing a Reset
button.
The alarms are signaled both visual and acoustic.
[FIGURE 2 OMITTED]
4. MODBUS COMMUNICATION
The communication with the generators is made using the Modbus
protocol. The CP341 communication processor of the Siemens PLC
implements only the ASCII version of the Modbus protocol (CP341:
Point-to-Point Communication, Installation and Parameter Assignment,
2000). In order to be able to use the RTU version of the same protocol,
the users must purchase some hardware and software items from the
PLC's manufacturer (Loadable Driver for Point-to-Point CPs, Modbus
Protocol, RTU Format, 2003).
In order to be able to communicate with Modbus RTU slave units
using the ASCII version, the following steps needed to be made:
* A CRC16 calculation method was implemented.
* When sending an ASCII message, the two CRC16 checksum bytes were
added at the end of it.
* When receiving an ASCII message, the two CRC16 checksum bytes are
extracted and for the remaining message the CRC16 checksum is
calculated.
* The calculated CRC16 checksum and the received one are compared.
If the number of bytes received is equal with the one requested and
if the two checksums are equal, then the communication has ended without
any errors and a new reading can be initiated.
5. CONCLUSION
An Automated Reserve Arming control system used for providing
continuous electrical energy supply for industrial consumers is very
useful because industrial processes depend on reliable electrical energy
supply.
This system can also be used to monitor the quality of the power
supply by using the measured parameters provided by the Sentron PAC3200
power monitoring devices. These devices have the following main
features: direct voltage measurement on the system or using voltage
transformers; monitors more than 50 parameters; offers 10 energy
counters to capture active energy, reactive energy, apparent energy for
off--peak and on --peak, etc.
6. ACKNOWLEDGEMENTS
This paper is supported by the Sectoral Operational Programme Human
Resources Development, financed from the European Social Fund and by the
Romanian Government under the project number POSDRU/107/1.5/S/76945.
7. REFERENCES
Margineanu, I. (2005). Automate programabile, Ed. Albastra, ISBN
973-650-156-6
Popescu, D. (2005). Automate programabile. Constructie,
functionare, programare si aplicatii, Ed. Matrix Rom Bucuresti, ISBN
973-685-942-8
Popescu, S. (2005). Tehnici avansate de comunicatie, Ed. Albastra,
ISBN 973-650-127-2
Springer, B. (2006). A Monitoring System for PLC Controlled
Manufacturing System Based on Fieldbus, Knowledge Enterprise:
Intelligent Strategies in Product Design, Manufacturing and Management
207
Vladareanu, L. (2005), Controlul in timp real cu automate
programabile in mecanica solidului. Studii si cercetari aplicative, Ed.
Bren, ISBN 973-648-432-7
*** (2000) CP341: Point-to-Point Communication, Installation and
Parameter Assignment, Siemens
*** (2003) Loadable Driver for Point-to-Point CPs, Modbus Protocol,
RTU Format, Siemens
*** (1996) Modbus Protocol Reference Guide, Modicon
*** (2009) Simatic HM7 MP 277 Operating Instructions, Siemens