Possibilities of replacement of absorption cooling unit by system of Peltier modules in process optimization of trigeneration system control.
Suriansky, Jozef ; Kocur, Vladimir
Abstract: Article describes the analysis and experimental
measurings of cooling system equivalent to absorption cooling unit,
which could be used as cooling system of trigeneration unit. Replacement
of this system is created by laboratory model of Peltier module working
in ratio 1:130. Peltier module is not replacement of real system, which
would ensure production of cold usable in practice. However it is
suitable means for application of simulation and experiments control of
trigeneration unit.
Key words: trigeneration, Peltier module, measuring of cooling
system, control of system
1. INTRODUCTION
Thermal system of trigeneration unit is system, which has thermal
energy as input and cold as output. This system is economically
challenging for purpose of research of control. There was an effort to
find such system, which would replace it and be sufficient as laboratory
model for creation of trigeneration control algorithms. Peltier module
was selected for this purpose. It works on a different principle and its
input is not thermal energy but electricity. However similarity between
absorption cooling unit and Peltier module was confirmed in (Kocur &
Suriansky, 2010). On the bases of this knowledge measurements of cooling
system were performed, which are described in article in more detail.
Article aims to show the possibility of Peltier module as appropriate
regulation element.
2. EXPERIMENTAL MEASUREMENTS
2.1 Laboratory model of cooling system
[FIGURE 1 OMITTED]
Model is created by Peltier modules P1 /[I.sub.max] = 8.5A,
[U.sub.max] = 15.4V and [Q.sub.max] = 71W/ (HB Corporation-a) and
P2/[I.sub.max] = 30.5A, [U.sub.max] = 15.6V and [Q.sub.max] = 257W/(HB
Corporation -b). Modul P2 is used in cooling mode and P1 in thermal load
mode. Modul P2 needs to ensure dissipation of heat from its hot side for
right operation. Although cooling mode on one side is increasing by
enlarging of modul input power but it causes proportional increasing of
heating on the other side. Heatsink with fan is used for this purpose.
Cold side of module P2 is connected to Cu plate, which represents
measuring environment. On the Cu plate is placed digital temperature
sensor (T1) ADT7301 which works with accuracy of 13-bits and with
temperature resolution of 0,03125 [degrees]C (Analog Device, 2004).
Plate with sensor is fully isolated from surrounding environment with
isolated material. For simulation of cooling load Peltier module P1 is
used, which heats environment by costant heat. Communication between
sensors is performed through SPI bus and operation is controlled by
processor ATMEGA32. Next sensor is installed on the heatsink (T2). This
serves to measure thermal side temperature of module P2. Third
temperature sensor (T3) measures ambient temperature.
2.2 Characteristics of thermal load
Function of heating is ensured by module P1. In this case
temperature of hot side was measured. As pattern, temperature
characteristic for heating to temperature 30[degrees]C is shown on the
Fig.2. Measured characteristics, which are necessary for measuring of
system coolling are more specified in Tab.2. For indication in table
applies: [I.sub.1], [U.sub.1] and [P.sub.1] [??] supply current, voltage
and input power of module P1, t [??] temperature stabilization time of
Cu plate heated by module P1, [T.sub.h] [??] temperature of Cu plate
after stabilization time, which is heated by module P1.
[FIGURE 2 OMITTED]
2.3 Cooling system with load
System represented by module P2, which cools Cu plate was loaded
through heating of Cu plate by module P1 in different time intervals by
different thermal powers, which corresponds to temperatures in following
order: 40, 30, 35 and 27[degrees]C. Modul itself was connected just at
the time 100 seconds, until that time ambient temperature was measured,
which had 24,5[degrees]C. The first load for cooling system was actually
ambient temperature. Change of load was performed always after
stabilization of previous state. On the Fig.3 courses of measured
temperature of researched Cu plate are shown. For better clarity of
individual time intervals of graph these intervals are separated by
white and grey color. Results of measurement are summarized in Tab.3,
wherein: [t.sub.0-4] [??] time of made change of cooling system,
[T.sub.cu], [??] temperature of Cu plate after stabilization of state.
[FIGURE 3 OMITTED]
Next measurement (Fig.4) was also performed for cooling with load
but with difference, that load was constant during the whole measurement
(corresponding to temperature of heating to 30[degrees]C) and cooling
power was changed.
[FIGURE 4 OMITTED]
Results of measurement are in Tab.4, where [I.sub.2] [??] supply
current of module P2.
2.4 Evaluation and results of experiments
Results of measurements shown in graphs on the Fig.3 and Fig.4 and
summarized in tables show onto conduct of Peltier module in load mode.
It is necessary to note, that achieved results are valid only for the
given cooling system using this concrete used system of heat
dissipation. With other system results will be different in various
ways. By connection of module P 1 working in heating mode to module P2
working in cooling mode, it is possible to observe conduct of cooling in
individual phases of system load. From these graphs can be clearly seen,
that given system is possible to regulate with no problems by means of
regulator. From Tab.4 is clear, that the most effective cooling (on
bases of stabilization speed and cooling ability) by module P2 on such
conditions will be achieved by supply current 10A. Therefore, for
Peltier module P2 working in described conditions and supplied by
current 10A parameters of system were calculated, which can be used by
design of system regulation. Transient characteristic (Nascak &
Suriansky, 2004) of this system after calculation has form:
S(s) = 0,2208/1 + 146 x s (1)
[FIGURE 6 OMITTED]
3. CONCLUSION
From graphs can be clearly seen, that given system is possible to
be regulated with no problems by means of regulator. Desribed
experimental measurements of system are key step to creating of control
algorithms of trigeneration unit with using of described laboratory
equivalent model of cooling system. Created algorithms can be applied
for needs of simulations and experiments of trigeneration control, based
on which it is possible to know better conduct of this system and so
optimize operation of control. In the next time of research will be
designed regulatory circuit and then created simulation model of
trigeration system with using equivalent cooling unit based on Peltier
module.
4. REFERENCES
Analog Device (2004). ADT7301, Preliminary Technical Data,
Available from: http://pdfl.alldatasheet.com/datasheet-pdf/
view/85924/AD/ADT7301.html Accessed: 2011-03-31
HB Corporation-a. Thermoelectric Cooler TEC1-12708, Available from:
http://pdfl.alldatasheet.com/datasheet-pdf/view
/227421/ETC2/TEC1-12708.html Accessed: 2011-03-31
HB Corporation-b. Thermoelectric Cooler TEC1-12730, Available from:
http://pdfl.alldatasheet.com/datasheet-pdf/view
/164396/ETC/TEC1-12730.html Accessed: 2011-03-31
Kocur, V. & Suriansky, J. (2010). Similarity of simulation
models of absorption cooling unit and Peltier module, In: Acta
Facultatis Technicae, Vol. XV., No. 1 /2010, pg. 95-105, Technical
University in Zvolen, Slovakia, ISSN 1336-4472
Nascak, L. & Suriansky, J. (2004). Basics of automation and
process control, Technical University in Zvolen, Slovakia, ISBN 80-228-1430-X, Zvolen
Tab. 2. Table of measured values by Peltier module P 1
[T.sub.h] [I.sub.1] [U.sub.1] [P.sub.1] t[s]
[[degrees]C] [A] [V] [W]
27 1,65 4,05 6,68 669
30 2,33 5,7 13,28 690
35 3,22 8 25,76 1014
40 3,7 9,5 35,15 1588
Tab. 3. Table of measured values of cooling system with
change of load by module P1 (*state corresponding to load of
ambient temperature)
state [t.sub.0-4] [T.sub.h] [T.sub.eu] note
[s] [[degrees] [[degrees]
C] C]
[t.sub.0] 100 24,5 8,2 connection
of module P2 *
[t.sub.1] 1120 40 21,2 connection
of load P1
[t.sub.2] 2740 30 13,4 1. change
of load P1
[t.sub.3] 4580 35 18 2. change
of load P1
[t.sub.4] 6580 27 11 3. change
of load P1
Tab. 4. Table of measured values of cooling system with
constant load and with change of cooling power.
state [t.sub.0-4] [T.sub.h] [T.sub.cu] note
[s] [[degrees] [[degrees]
C] C]
[t.sub.0] 0 -- 30 connection of load P1
(30 [degrees]C]
[t.sub.1] 1410 10 12,9 connection of module P2
[t.sub.2] 3000 15 18,3 1. change of P2 cooling
power
[t.sub.3] 4900 5 16,0 2. change of P2 cooling
power
[t.sub.4] 6400 8 13,8 3. change of P2 cooling
power
[t.sub.5] 7900 20 30,8 4. change of P2 cooling
power
[t.sub.6] 9900 20 26,0 disconnection of load
P1
[t.sub.7] 11890 5 9,6 1. change of P2 cooling
power
[t.sub.8] 14200 10 7,9 2. change of P2 cooling
power