Reduced voltage stresses across power transformer winding sections provided with metal oxide surge absorbers.
Ansari, Mohd. Zahed Ahmed ; Gurumurthy, G.R. ; Amarnath, J. 等
Introduction
Power transformers in service experience different types of
transient overvoltages. One of them is effects of lightning. Lightning
overvoltages are characterized by very steep initial rate of rise of
voltage and relatively slower rate of fall of voltage with respect to
time. Surge voltages with steep front time are most important type of
transient overvoltages which can cause damage to insulation of
transformer windings. The practice of design and construction of HV
transformer windings to withstand effects of surge voltages with steep
fronts appearing at its line terminal has been to provide a surge
voltage distribution controlling ring at line end which is also called
as static end ring. Other method of improving the steep front surge
voltage withstand performance of power transformer HV windings is to
increase the series capacitance between turns of sections or discs of
winding known as interleaving [1-3].
MOA blocks have been known to be able to provide very good surge
protection to equipments used in electrical power stations and
substations for more than a decade. Their technology has advanced to
highly satisfactory levels as to be able to provide surge absorbers
having required type of characteristics to suit different applications
[4, 6, 7]. The voltage V relating to current I through a surge absorber
block is given by the equation V = K[I.sup.[beta]] (K and [beta] are
constants for the MOA blocks).
Computer simulations carried out on HV windings of power
transformers provided without and with suitable MOA blocks to
investigate behavior of these windings due to appearance of very fast
rise time transient voltage at its line terminal are reported in this
paper. The values of [alpha] considered for study are 6, 12 and 18.
Extensive investigations have shown that it is essential to provide MOA
blocks of appropriate characteristics (i.e., [beta] and K values) across
all sections of winding referring to entire HV winding length if it is
desired to reduce the voltage stresses enormously. However, it may be
noted here that by providing suitable MOA blocks across 50% of winding
length only, voltage stresses across sections can be reduced to some
extent. All the simulation investigations reported in this paper have
been carried out using PSpice software version 10.
Simulation
Model winding and analysis
The HV winding has been represented by a single layer coil wound on
an insulating former of mean diameter 20.1cms and coil consisting of 8
sections, each coil section constituted 60 turns. Thus, the HV winding
equivalent circuit consists of sections incorporating series inductance
L, series capacitance Cs and ground capacitance Cg, which represent
inductance due to turns of coil sections, capacitance between terminals
of coil sections and capacitance of coil sections to ground. In the
present investigations mutual inductance between coil sections
[M.sub.12], [M.sub.21].... [M.sub.18], [M.sub.81].... etc have also been
considered in the simulations.
Initial Voltage distribution without surge absorber block
HV windings of power transformer can be represented by equivalent
circuit network for analysis of surge behavior as shown in Fig. 1 [1-3].
Although close coupling of all turns do exist in power transformer
windings, for investigation of behavior of windings for fast front surge
voltages (near step voltages) appearing at line terminal, effect of
inductance can be ignored for analysis of initial voltage distribution
[1-3]. Therefore, the equivalent network for study of behavior for
initial voltage distribution is as shown in Fig. 2.
[FIGURE 1 OMITTED]
The initial voltage distribution for a equal to 6, 12 and 18 for
step voltage input at line terminal with neutral end of winding grounded
is obtained using the equation [1]:
[[epsilon].sub.x] = E Sinh ([alpha]x) / Sinh [alpha](1)
[alpha] = (n)[square root of [C.sub.g] / [C.sub.s]] (2)
[FIGURE 2 OMITTED]
E = Magnitude of input step voltage
n = number of sections in transformer winding equivalent network
x = fraction of winding length from neutral end (in present study
referring to node position)
[e.sub.x] = voltage at fraction of winding length with respect to
neutral
Initial voltage distribution with surge absorber blocks
Equivalent circuit representation of transformer HV winding for
analysis of surge behavior with surge absorber block provided across 25%
of winding portion is shown in Fig. 3.
[FIGURE 3 OMITTED]
[Z.sub.B]: Metal oxide surge absorber block
[V.sub.A]: Voltage across [Z.sub.B] when passing surge current
[I.sub.A]
[C.sub.eq]: Equivalent capacitance across terminal 'p'
and ground due to chain of [C.sub.g] and [C.sub.s]
Referring to Fig.3, the voltage appearing across the capacitive
network of transformer winding portion after the surge absorber block
can be written as:
[V.sub.p] = E - [V.sub.A] (3)
[V.sub.p] = Voltage across equivalent capacitance [C.sub.eq]
(across point p and ground as shown in Fig.3)
Relation between voltage and current for MOA block [4, 5] is:
[I.sub.A] = [KV.sub.[beta]] (4)
K and [beta] are constants. Value of [beta] is in range of 25 to 30
Referring to Fig.3, [I.sub.A] is also the current entering to the
capacitance network at point p with equivalent capacitance [C.sub.eq].
Therefore, for extremely short time duration after appearance of step
voltage E at line terminal, we can write
d[V.sub.p] / dt = [I.sub.A] / [C.sub.eq](5)
From (2) and (3) we can write after integration:
[V.sub.p] = [I.sub.A] / [C.sub.eq] t + D (6)
D = constant of integration.
We have the initial conditions that IA = 0 at t = 0. Therefore
value of constant D = 0 in (4)
Thus, during the initial time period after appearance of step
voltage, we have
[V.sub.p] = [I.sub.A] / [C.sub.eq] t (7)
The MOA block has a highly non linear voltage current relationship
and for surge current magnitudes [I.sub.A] in the range of few hundred
amperes to few thousand amperes, the voltage across it does not change
appreciably. Also, the resistance offered by metal oxide surge absorber
block is a low value for flow of large surge currents through it and the
equivalent capacitance [C.sub.eq] (capacitance between points p and
ground in Fig. 3 gets charged up to the maximum value in very quick time
(in the order of small fraction of microsecond). This situation can be
considered as though a step voltage of magnitude (E-VA) appears across
[C.sub.eq], which is the capacitance equivalent network representing the
portion of the HV transformer winding connected to the end of the metal
oxide surge absorber block. Thus, the initial voltage distribution
referring to remaining transformer winding portion is calculated
considering as though a step voltage of magnitude (E-[V.sub.A]) appears
at point p and ground in Fig. 3 applying same method as detailed in
previous section.
Discussions and comparison
The initial voltage distributions along winding length for values
of [alpha] equal to 6, 12 and 18 are shown in Fig. 4 considering
magnitude of input step voltage E as 1.0 pu.
The voltage stress across the winding insulation near the line end
can be observed to be very much higher as compared to uniform stress
distribution. Also, voltage stress at line end portion of winding can be
observed to increase considerably with increase in [alpha] value from 6
to 18.
[FIGURE 4 OMITTED]
When a MOA block is provided across 25% of winding length at line
terminal which develops a constant voltage of 0.25 pu (approx.) during
flow of surge currents through it, the altered surge voltage initial
distributions are as shown in Fig. 5. The input surge voltage magnitude
considered in this case also is same as 1.0 pu step voltage at line
terminal. The values of maximum voltage stresses developed in the
transformer HV winding due to presence of metal oxide surge absorbers
are reduced considerably. Calculations of these values have shown that
for HV winding with [alpha] = 6, the maximum stress is reduced by 22.7%.
The reduction in stress for winding with [alpha] = 18 is 20.3%.
The non-uniform initial voltage distribution is due to effect of
capacitive network which is made up of [C.sub.s] and [C.sub.g]. The
initial voltage distribution arising due to capacitive network does not
exist for longer duration of time. Subsequent to charging of capacitive
network in the initial short duration of time, currents start flowing
through the inductive network and finally after sufficient duration of
time uniform voltage distribution due to inductive effects of network
will be reached. The transition from non-uniform initial voltage
distribution to final uniform distribution takes place through a series
of damped oscillations between capacitive and inductive networks. The
initial voltage distribution represents envelope of maximum possible
transient voltage zero current phase. With the introduction of MOA
blocks, analysis in earlier sections has shown that maximum voltage
stresses across coils of HV transformer windings due to initial voltage
distribution are considerably reduced. From these considerations, the
maximum voltages that can be developed in the windings during transition
from initial voltage distribution due to appearance of a series of
damped oscillations will also be reduced appreciably when MOA blocks are
provided across the portion of windings at line end (in this case across
25% of winding length).
[FIGURE 5 OMITTED]
The general construction practices over past few decades for
transformer HV windings to withstand effects of surge voltage initial
distribution have been to provide static end ring at line terminal
[1-3], providing increased insulation size for conductors near line
terminal and adopt interleaved type of construction for coils. By
providing metal oxide surge absorber blocks as detailed above, it is
possible to overcome these special constructional requirements for
making HV winding of transformer withstand effects of steep front surge
voltages. It may be noted here that providing metal oxide surge absorber
as described above reduces the energy in the incoming surge voltage wave
to the extent of energy dissipation in the surge absorber block. Thus,
the surge voltage energy which can cause damage to transformer HV
winding can also be reduced considerably.
Voltage distributions with MOA blocks across 50% of winding from
line end
The equivalent circuit for analysis of surge behavior of HV
windings of power transformer MOA blocks across 50% of winding from line
end is shown in Fig. 6 [1-3].
[FIGURE 6 OMITTED]
Fig. 7 and 8 show simulated voltages to ground at different points
of HV winding when the first 50% of HV winding are provided with MOA
blocks [Z.sub.B] (Fig. 6) for values of [alpha] equal to 6 and 18
respectively (neutral grounded). We observe from these figures that
maximum voltage is appearing across last section of the winding although
the surge voltage magnitude across 50% of the winding which are provided
with MOA blocks are considerably reduced. Further we observe that the
time instance of appearance of maximum surge voltage across last section
of winding is increasing with increasing [alpha] value of windings.
Further we observe that the time instance of appearance of maximum
surge voltage across last section of winding is increasing with
increasing [alpha] value of windings. For comparison, surge responses of
HV winding without presence of MOA blocks at different nodes are shown
in Fig. 9.
[FIGURE 7 OMITTED]
[FIGURE 8 OMITTED]
[FIGURE 9 OMITTED]
This figure shows that there are possibilities of occurrence of
very large voltages across sections of winding due to voltage
oscillations caused by appearance of unit step voltage at line terminal.
These voltage oscillations are due to natural frequencies of winding
which consists of capacitances and inductances. Such enormous voltage
oscillations with respect to the time are considerably reduced (see Fig.
7 and 8) even when MOA blocks are provided across 50% of winding only
from the line end. This suggests that enormous magnitude high voltages
appearing across sections of HV winding can be reduced to certain extent
by providing suitable MOA blocks across first few sections of the HV
winding. However the maximum value of surge voltage can be between 35%
to 45% of the surge magnitude that appears at line terminal. Other
important aspect we can observe from this investigation is the
appearance of negative voltages with respect to ground. The magnitudes
of negative voltages to ground for case in which MOA blocks are provided
across 50% of winding are very much smaller as compared to the values
that can be present in the winding without the MOA blocks. It may also
be noted from these figures that for the case of windings with MOA
blocks across 50% of winding, the magnitude of positive node voltages
does not exceed the input surge voltage magnitude which is 1.0 pu. Also,
we observe that the positive node voltage magnitude for case without MOA
blocks can be higher than input surge magnitude by approximately 25% due
to voltage oscillations.
Voltage distributions with MOA blocks across all sections of HV
winding
Fig. 10 and 11 show voltage distribution across sections of winding
when 100% of winding are provided with suitable MOA blocks. We observe
from these figures that there are no oscillations on waveform of voltage
to ground at different node positions of the winding. Also, these
figures indicate that the maximum surge voltage to ground does not
exceed the magnitude of the input step voltage. Further there are no
voltage reversals at any node position on the winding. The maximum value
of surge voltage across any section of the winding in this case is
approximately 23.5% for all the three [alpha] values. The behavior of HV
winding when all sections of the winding are provided with suitably
designed MOA blocks can be explained as follows:
When a steep front HV surge appears at terminal of winding, till
sufficient magnitude current flows through the nonlinear blocks, the
voltage distribution is governed mainly by the effect of series
capacitance across sections and shunt capacitances to ground (in less
than small fraction of micro second time). Once sufficient current
(approximately few milliamperes) is established through highly non
linear resistance path of MOA blocks, the voltage distribution across
winding sections is completely decided by the V-I characteristics of the
MOA blocks. The MOA blocks not only serve to reduce surge voltage across
winding sections but also dissipate surge energy and thus prevent
possibility of winding failures.
[FIGURE 10 OMITTED]
[FIGURE 11 OMITTED]
The explanation for surge voltage response curves for the situation
where MOA blocks are provided across 50% of winding sections is that the
other 50% of winding without MOA blocks can give rise to the initial
node voltage variations in time range 0 to 10 microseconds as may be
observed from Fig. 7 and 8. In view of the fact that there are no
enormous node voltage oscillations that is present only in case where no
MOA blocks are used across sections of winding, for cases where 50% of
winding or 100% of winding sections are provided with MOA blocks, the
simulation results indicate (Fig. 7 and 8 & 10 and 11) that graded
insulation type construction can be effectively used for HV winding.
Conclusion
Computer simulation investigations of HV windings of HV power
transformers for its behavior with [alpha] values 6, 12 and 18 to
appearance of very fast rise voltage surges at line terminal have
indicated that:
1. The response of windings without MOA blocks consists of enormous
magnitudes of voltage oscillations and magnitudes of node voltage
distribution in this case can be higher than the magnitude of input
surge at few nodes. Also, at few other nodes the surge magnitude can
reach negative values to considerable voltage levels.
2. By providing suitable MOA blocks across sections of winding up
to 50% of length of winding, the surge voltage magnitudes can be reduced
to some considerable extent. In this case the surge voltage magnitude at
any of the nodes is not higher than the magnitude of the input surge.
3. When all sections of entire winding are provided with suitable
MOA blocks, the surge voltage distributions have no oscillations. The
magnitude of surge voltage at any of nodes is less than the input surge
voltage magnitude and the magnitudes of surge voltages appearing across
sections of winding are reduced to larger extents.
4. For cases where 50% of winding or entire winding sections are
provided with suitable MOA blocks, graded insulation type construction
can be effectively used for HV winding of power transformers.
Acknowledgements
The authors would like to thank the authorities of Ghousia College
of Engineering, Ramanagaram, BNM Institute of Technology, Bangalore and
JNTU, Hyderabad for cooperation, encouragement and for providing
facilities to publish this work.
References
[1] L. F Blume et al, Transformer engineering (John Wiley and Sons,
1952).
[2] S. B Vasutinsky, Principles, operation and design of power
transformer (PSG College of Technology, Coimbatore (Book), Tamilnadu,
India, 1962).
[3] B. Heller and A. Veverka, Surge phenomena in electrical
machines (London, Iliffe Books Ltd., 1968).
[4] E. Kuffel, W. S. Zaengl and J. Kuffel, High voltage
engineering: fundamentals (Newnes, Elsevier, 2000).
[5] Yuanfang Wen and Chengke Zhou, A novel method for predicting
the life time of MOV, IEEE Trans. on Power Delivery, 19(4), 2004,
1689-1691.
[6] Yuanfang Wen and Chengke Zhou, Experimental studies on the use
of MOV in transformer windings, IEEE Trans. on Power Delivery, 20(2),
2005, 1441-1446.
Mohd. Zahed Ahmed Ansari (1), G. R. Gurumurthy (2) and J. Amarnath
(3)
(1) Department of Electrical & Electronics Engineering, Ghousia
College of Engineering, Ramanagaram--571511, Karnataka, India Phone:
+919900650035, Email: zahedansari@gmail.com (2) Department of Electrical
& Electronics Engineering, BNM Institute of Technology,
Banashankari, Bangalore--560070, Karnataka, India Phone: +919845038229,
Email: grgurumurthy@yahoo.com (3) Department of Electrical &
Electronics Engg., JNTU, Hyderabad--500085, Andhra Pradesh, India Phone:
+919347277771, Email: amarnathjinka@yahoo.com