Experimental investigation of heat transfer coefficient of a refrigerant mixture in a fin-and-tube evaporator.
Raj, M. Herbert ; Lal, D. Mohan
Introduction
HCFC has been effectively used in many refrigeration and
airconditioning applications due to its better thermodynamic and
material compatibility. The fully halogenated chlorofluorocarbons are
responsible for destroying the stratospheric ozone layer. The
hydrochlorofluorocarbon (HCFC) refrigerants are being replaced by
hydrofluorocarbon (HFC) and HFC mixtures due to environmental concerns.
R407C is recommended as an alternative to replace R22 in a window
airconditioner but its oil miscibility nature is the main problem.
Previous research [1, 2] reported that addition of HC blend (54.8% R600a
and 45.2% R290a) to R407C will over come the oil miscibility issue with
mineral oil and it was proved that the M20 refrigerant mixture (80%
R407C and 20% HC blend by wt) could be viable drop-in substitute without
changing the mineral oil.
The fin-and-tube evaporators are widely used in airconditioning and
processing applications. The knowledge of overall heat transfer
coefficients is of prime importance to optimize the design of heat
exchangers for refrigeration and airconditioning applications since;
most of the designs are based on overall heat transfer coefficients.
Evaporation of pure and mixed refrigerant has been studied inside the
horizontal and vertical tubes by large number of researchers, both the
experimentally and analytically. A large number of correlations have
been proposed based on experimental results to predict the heat transfer
coefficient in forced convective boiling in horizontal and vertical
smooth tube for pure refrigerant and mixture [3-8]. During the past few
decades, many research works have been carried out on air-side
performance of fin-and-tube evaporator and the heat transfer and
friction characteristics of fin-and-tube evaporator with different fin
configurations were measured [9-11]. Based on the experimental database
heat transfer and friction correlations were predicted for air-side of
fin-and-tube heat exchangers.
Horuz [12] investigated theoretically and experimentally the
parameters affecting the cooling capacity and overall heat transfer
coefficient of fin-and-tube heat exchanger. The air velocity, fin
spacing, tube diameter, evaporator temperature, refrigerant type and
frost height were varied during experimentation. The overall heat
transfer coefficient of R717, R22, R502, R134a and R12 were calculated
and compared with theoretical results. Somchai et al [13] studied the
two-phase heat transfer coefficient characteristics of R134a,
evaporating inside a plate fin- and-tube evaporator with plain fin
geometry. The experiments were conducted at the different average
saturated refrigerant temperatures. During experimentation the
volumetric flow rate of air passing through the evaporator were varied
between 0.25 [m.sup.3]/s and 0.5 [m.sup.3]/s and between 0.7 [m.sup.3]/s
and 1.25 [m.sup.3]/s for the condenser.
Vapor and liquid compositions are different for a multi-component
mixture, and will continuously change throughout the heat transfer
process, which influences the properties of the two phases. A change in
the saturation temperature during the evaporation and condensation
processes at a constant pressure is known to have important effects on
the heat exchanger design. To the best of the author's knowledge,
there are no heat transfer study report currently available on the tube
side evaporative heat transfer characteristics of M20 refrigerant
mixture flowing through the fin-and-tube heat exchanger. In the present
study, evaporative heat transfer characteristic of M20 refrigerant
mixture in a fin-and-tube evaporator has been analyzed experimentally in
a vapor compression system. The indoor and outdoor temperatures were
varied in accordance with BIS [14] standards.
Experimentation
The experimental facility mainly consists of the psychrometric test
room and the unit under test suitably instrumented to conduct the heat
transfer study.
Psychrometric test room
An experimental setup was constructed as shown in fig.1 that would
facilitate performance assessment of a window air-conditioner on various
indoor and outdoor conditions in accordance with different standards
(BIS and ASHRAE). The psychrometric room consists of two adjacent
chambers to maintain indoor and outdoor conditions respectively. Both
the rooms have separate AHUs with a cooling coil (Dehumidifier), air
heater and steam injection facility (Humidifier) which are controlled /
modulated by suitable feed back control system to maintain the required
indoor and outdoor test conditions indicated in fig.1. The facility has
been designed to maintain individual temperature readings within the
tolerance prescribed in BIS- -1391-1992 and ASHRAE-116 -1995 standards
([+ or -] 0.5[degrees]C for dry bulb temperatures and [+ or -]
0.3[degrees]C for wet bulb temperatures). Six temperature sensors were
strategically located in each room to confirm the uniformity in room
temperature within [+ or -] 0.5[degrees]C.
To measure the supply air flow rate from the unit under test a code
tester is available in the indoor room. This code tester design is based
on ASHRAE standard 41.2--1987 [15]. This consists of a set of nozzles
that can be suitably selected to allow the air to flow through the
selected nozzle. The pressure drop across the nozzle is measured using a
differential pressure transducer. There is an auxiliary blower driven
with a VFD to maintain zero gauge pressure at the receiving chamber.
This is done so that the UUT does not experience any resistance to throw
the supply air due to upstream surging effect of the flow through
nozzle. The code tester was connected with a suitable leak proof duct to
the supply grill of the UUT. The air flow rate was varied using a
selector switch generally available in window airconditioner appliance.
[FIGURE 1 OMITTED]
Unit Under Test
The unit under test was suitably modified to connect temperature
sensors (RTDs PT100-class A [+ or -] 0.15[degrees]C accuracy) and
pressure sensors ([+ or -] 0.1% accuracy) across each component. The
mass flow rate of refrigerant was measured by a Coriolis type mass flow
meter ([+ or -] 0.1% accuracy) connected in the liquid line. The entire
flow lines along with components were properly insulated to avoid heat
infiltration. The power consumed by the compressor was measured by a
separate power meter ([+ or -] 0.25% accuracy). Same diameter and
different length of capillaries were used for R22 and M20. Suitable hand
shutoff valves were used to select the required capillary to be included
in the circuit. One sight glass was provided in the liquid line to check
the condition of the condensed refrigerant in the circuit. The supply
and return air temperatures (DBT and WBT) were measured by suitable RTDs
(class--A) fixed at appropriate locations. The evaporator with plain fin
geometry are made from aluminum plate finned, copper tube. The external
dimension of the fin-and-tube evaporator is 410 x 365 x 90mm (Height x
width x Depth). The outer diameter of the copper tube is 9.52 mm.
Data Logging
All measured data are logged into a PC through a suitable data
logging system. Once steady state condition is achieved all the data
will be automatically logged in to the system. The steady state
condition is manually confirmed by checking the uniformity in
temperature indicated by all the room temperature sensors in accordance
with the test conditions. After stabilization of indoor and outdoor air
temperature, refrigerant temperatures and pressures across the each
component, flow rates of refrigerant and air were scanned and recorded
in the computer through a data acquisition system.
Experimental Procedure
The performance of the system was determined in accordance with the
BIS--1391- 1992 test conditions (given in fig. 1) for residential sized
air conditioner. In air enthalpy test method, refrigerating capacity is
determined from the difference in enthalpies obtained against DBT and
WBT of air entering and leaving the unit under test (UUT) and the
associated air flow rate under specified test conditions. The mass of
air was calculated using the measured pressure drop across the nozzle
and DBT and WBT of sample air in the code tester based on ASHRAE
standard 41.2-1987 [18]. Refrigerant side measurements were also made to
ensure that the maximum difference between the air side and refrigerant
side capacity was less than 6% as prescribed in the standards.
Properties of refrigerant were extracted from REFPROP [17].
To have a realistic comparison of the performance of the M20
refrigerant mixtures with conventional refrigerant the experiment was
carried out initially with the conventional refrigerant R22. At steady
state refrigerant mass flow rate, pressure and temperature across the
evaporator and condenser, DBT / WBT of return as well as supply air and
mass flow rate of air were measured for the various indoor and outdoor
room conditions as given in fig. 1.
Before starting the experiment with mixture, the mixture was
prepared separately in a cylinder. For the mixture, the equivalent
charge quantity for the considered mass of R22 was obtained, along with
the mass of R407C and the HC blend, making use of the specific volume
ratios at suction condition. Each mixture component was weighed
individually in an electronic balance with an accuracy of [+ or -] 0.1 g
and filled in the cylinder with the help of a suitable charging
manifold. After completing all the performance tests with R22, the
refrigerant was recovered and equivalent quantity of M20 mixture was
charged. The same tests for performance, pull down and per day energy
consumption were repeated for M20.
Test condition
In general mass flux, heat flux, inlet quality and saturation
temperature and pressure are the major factors which affect evaporative
heat transfer in all heat exchanger. But in practical cases, the heat
transfer coefficient is mainly affected by evaporator inlet air
temperature and condenser inlet air temperature in air cooled heat
exchangers. In this study, the evaporator air inlet and condenser air
inlet temperatures are varied in accordance with BIS [14] standards.
Data reduction
The inside area, outside surface area and air side area are
calculated using equations from Kuppan [16] based on the measured
diameter of tube, thickness of the tube, number of fins, fin thickness.
The enthalpy of supply and return air are calculated using the measured
DBT and WBT of the supply and return air. Refrigerant side enthalpies
are calculated based on measured inlet and outlet temperatures and
pressures. The refrigerant and refrigerant mixture properties were
calculated from REFPROP version 7.1 [17].
The overall heat transfer coefficient, U can be calculated using
eqn. 1
[U.sub.o] = [Q.sub.ave]/F[A.sub.o][DELTA][T.sub.lm] ... (1)
Where,
[Q.sub.ave] = ([Q.sub.a] + [Q.sub.r])/2 ... (2)
[Q.sub.a] = [??]([DELTA][h.sub.a]) ... (3)
[Q.sub.r] = [??]([DELTA][h.sub.r]) ... (4)
Where, [DELTA][T.sub.lm]) is the logarithmic mean temperature
difference, [A.sub.o] is the outside surface area and F is the
correction factor which is equal to 1 [13] for this kind of fin-and-tube
evaporator.
The temperature difference, LMTD was determined from the inlet and
exit temperatures (DBT) of the air flowing through the evaporator and
from the inlet and outlet saturation temperature of refrigerant flowing
in the test section. The refrigerant temperature at the inlet of the
test section was calculated by considering isenthalpic process in
expansion device. The inlet two-phase temperatures were calculated based
on the calculated inlet quality and measured saturation pressure. The
outlet temperature of refrigerant mixture was calculated based on the
dew point temperature at the corresponding measured pressure and wall
temperature.
Result and discussion
Experiments were performed for R22 and M20 refrigerant mixture at
the test conditions as given in fig.1. Based on measured parameters the
evaporator pressure, heat flux, overall heat transfer coefficient, LMTD
and mass flow rate for M20 refrigerant mixture were discussed with the
baseline results of R22 at two different air velocity.
Figure 2 shows the variation of refrigerant pressure with velocity
of air passing over the evaporator with different test conditions for
R22 and M20. It was observed that as the air velocity increases the
refrigerant pressure decreases for all test conditions. The maximum
pressure reached in ETA_M compared to other test conditions due to
higher operating conditions. However at higher velocity for all test
condition the evaporator inlet pressure was lower for all test
conditions. But all test conditions the refrigerant pressure of M20 was
higher than that of R22. It was measured that the evaporator inlet
pressure of M20 refrigerant was higher in the range 0.5% to 3.66% than
R22 at all operating conditions.
[FIGURE 2 OMITTED]
Figure 3 shows the variation of mass flow rate for R22 and M20 at
two different velocities with various test conditions. As the velocity
increases the mass flow rate decreases for all test conditions. However
at higher velocity the mass flow rate was lower for all test conditions.
It was found that the mass flow rate of M20 refrigerant mixture was
lower than that of R22 for a same test condition due to lower liquid
density than R22 as evidence from REFPROP [17]. The mass flow rate of
M20 refrigerant mixture was lower in the range 8.58% to 13.1% than R22
at all studied operating conditions.
[FIGURE 3 OMITTED]
Figure 4 shows the variation of heat flux for R22 and M20
refrigerant mixture at two different velocity of air with different test
conditions. It was observed that as the velocity increases heat flux
increases for all test conditions. The test ETA has higher heat flux
than the other test conditions. The heat flux of R22 was varied from
7.716 to 9.428 kW/[m.sup.2] and M20 was varied from 7.450 to 8.585
kW/[m.sup.2] at all tested conditions. It was observed that the heat
flux of M20 refrigerant mixture was lower in the range 1.8% to 9.82%
than R22 at the studied operating conditions.
[FIGURE 4 OMITTED]
Figure 5 the variation of logarithmic mean temperature difference
with velocity of air passing through the evaporator with different test
conditions for R22 and M20 refrigerant mixture. Due to lower refrigerant
outlet condition, the LMTD decreases as the velocity increases for all
considered operating conditions. The test ETB has high LMTD than the
other test conditions due to higher operating condition for R22 and M20
refrigerant mixture. However at higher velocity LMTD is lower for all
test conditions. It was observed that the M20 refrigerant mixture LMTD
was higher in the range 1.15% to 8.67% than R22. This was attributed due
to higher air outlet temperatures and higher inlet and outlet
temperatures of M20 refrigerant mixture.
Figure 6 shows the variation of overall heat transfer coefficient
for R22and M20 refrigerant mixture at different velocity of air passing
through the evaporator with different test conditions. However at
highest air velocity for all test condition the overall heat transfer
coefficient is lower for both the refrigerant. The test ETA has higher
overall heat transfer coefficient than other test conditions due to
lower LMTD. The overall heat transfer coefficient was varied for R22 in
the range 143.73 to 193.81 W/[m.sup.2]K and for M20 refrigerant mixture
131.56 to 174.45 W/[m.sup.2]K. The overall heat transfer coefficient of
M20 was lower than R22 for all test conditions due higher LMTD and lower
heat transfer rate for the same geometric conditions. The overall heat
transfer coefficient of M20 was lower in the range 6.72% to 20.76% than
R22 at all studied operating conditions.
[FIGURE 5 OMITTED]
[FIGURE 6 OMITTED]
Uncertainty Analysis
Experimentation using R22 and M20 refrigerant mixture included the
measurement of air temperatures (DBT and WBT), pressure difference
across the nozzles, refrigerant temperature and pressures at various
locations of the systems and refrigerant mass flow rate. Air-side heat
transfer rate, refrigerant-side heat transfer rate, overall heat
transfer coefficient were calculated based on the measured parameters.
The uncertainties in air-side heat transfer rate, refrigerant-side heat
transfer rate and overall heat transfer coefficient were in the range
2.6% to 3.5%, 1.2% to 2.0% and 3.2% to 4.7% respectively. The
uncertainties for the R22 and M20 refrigerant mixture were calculated
from the equations listed below,
[U.sub.o] = [Q.sub.ave]/[DELTA][T.sub.lm] ... (1)
[Q.sub.ave] = [Q.sub.r,ac] + [Q.sub.a,ac] ... (2)
[Q.sub.r,ac] = [[??].sub.r] ([DELTA][h.sub.r]) ... (3)
[Q.sub.a,ac] = [[??].sub.a] ([DELTA][h.sub.a]) (4)
[DELTA][h.sub.a] = f([DELTA][P.sub.nozzle], [T.sub.WBT],
[T.sub.DBT]) ... (5)
[DELTA][h.sub.r] = f([T.sub.e,in], [T.sub.e,out], [P.sub.e,in],
[P.sub.e,out], [T.sub.WBT], [T.sub.DBT]) ... (6)
[DELTA][T.sub.lm] = f([T.sub.e,in], [T.sub.e,out],
[T.sub.DBT,supply], [T.sub.DBT,return]) ... (7)
[delta][Q.sub.a,ac] = [[([delta][[??].sub.a]/[[??].sub.a]).sup.2] +
[([delta][DELTA][h.sub.a]/[DELTA][h.sub.a]).sup.2].sup.1/2] ... (8)
[delta][[??].sub.a] =
[[([delta][DELTA][P.sub.nozzle]/[DELTA][P.sub.nozzle]).sup.2] +
[([delta][T.sub.WBT]/[T.sub.WBT]).sup.2] +
[([delta][T.sub.DBT]/[T.sub.DBT]).sup.2].sup.1/2] ... (9)
[delta][DELTA][h.sub.a] =
[[([delta][h.sub.a,supply]/[h.sub.a,supply]).sup.2] +
[([delta][h.sub.a,return]/[h.sub.a,return]).sup.2].sup.1/2] ... (10)
[delta][h.sub.a,supply] = [[([delta][T.sub.WBT]/[T.sub.WBT]).sup.2]
+ [([delta][T.sub.DBT]/[T.sub.DBT]).sup.2].sup.1/2] ... (11)
[MATHEMATICAL EXPRESSION NOT REPRODUCIBLE IN ASCII] ... (12)
[delta][DELTA][T.sub.lm] =
[[([delta][T.sub.e,in]/[T.sub.e,in]).sup.2] +
[([delta][T.sub.e,out]/[T.sub.e,out]).sup.2] +
[([delta][T.sub.DBT,supply]/[T.sub.DBT,supply]).sup.2] +
[([delta][T.sub.DBT,return]/[T.sub.DBT,return]).sup.2].sup.1/2] ... (13)
Conclusions
The heat-transfer characteristics of M20 refrigerant mixture and
R22 were experimentally investigated in a fin-and-tube evaporator as a
function of evaporator air inlet temperature, condenser air inlet
temperature and air velocity. A study was carried out in a 9.525mm
smooth tube fin-and-tube evaporator with optimum charge quantity of R22
and M20 refrigerant mixture. Based on the measurement the following
conclusions were drawn,
(1) The inlet pressure of M20 was higher in the range 0.5% to
3.66%.
(2) Mass flow rate of M20 was 8.58% to 13.1% lower than R22
(3) Heat flux of M20 was lower in the range 1.8% to 9.82%.
(4) LMTD of M20 was higher in the range 1.4% to 8.67%.
(5) Overall heat transfer coefficient of M20 was lower in the range
6.28% to 20.76%.
The fact that POE oil can be dispensed with by using R407C/HC blend
refrigerant mixture in the place of R407C is a significant finding in
this work. This mixture would be the better choice to retrofit the
existing window air-conditioners while R22 has to be phased out. When
R22 is to be phased out, there may be millions of airconditioners
operating with R22 in both developed and developing countries.
Retrofitting with M20 is an option to extend the life of such units
without changing the mineral oil in the compressor, although the
performance is slightly poorer.
Nomenclature
A Surface area ([m.sub.2])
AHU Air handling unit
ASHRAE American society of Heating Refrigerating
Air-Conditioning Engineers
BIS Bureau of Indian Standards
DBT Dry bulb Temperature ([degrees]C)
h Heat transfer coefficient (W/[m.sup.2]/K)
HC Hydrocarbon
HFC Hydroflurocarbon
k Thermal conductivity (W/m/K)
L Length of the tube (m)
LMTD Logarithmic mean Temperature difference (K)
m mass flow rate
[m.sub.a] mass the air (kg of dry air/hr)
MFM Mass Flow Meter
NF Normal fan speed
Q Heat transfer rate (W)
RTD Resistance temperature detector
SG Sight Glass
SQ Super Quiet fan speed
T Temperature
U Overall heat transfer coefficient (W/[m.sup.2]/K)
UUT Unit under test
WBT Wet bulb Temperature ([degrees]C)
Subscripts
a Air
ave Average
f Fin
I Refrigerant side
lm LMTD
in Inlet
m mean
o Outer
out Outlet
r Refrigerant
s Saturation
w wall
Greek Symbol
[delta] Thickness of wall
[[eta].sub.o] Effectiveness
[eta] Surface efficiency
References
[1] Jabaraj, D.B., Avinash, P., Mohanlal, D., and Renganarayanan,
S., 2006 "Experimental investigation of HFC407C/HC290/HC600a
mixture in a window air conditioner", Energy Conversion and
Management, 47, pp 2578-2590.
[2] Jabaraj, D.B., Narendran, A., Mohanlal, D., and Renganarayanan,
S., 2007, "Evolving an optimal composition of HFC407C/HC290/HC600a
mixture as an alternative to HCFC22 in window air conditioners",
International Journal of Thermal Sciences, 46, pp 276-283.
[3] Boissieux, X., Heikal, M.R., and Johns, R.A., 2000,
"Two-phase heat transfer coefficients of three HFC refrigerants
inside a horizontal smooth tube, part I: evaporation",
International Journal of Refrigeration, 23, pp. 269-283.
[4] Choi, T.Y., Kim, Y.J., Kim, M.S., and Ro, S.T., 2000,
"Evaporation heat transfer of R32, R134a, R32/134a, and
R32/125/134a inside a horizontal smooth tube", International
Journal of Heat and Mass Transfer, 43, pp. 3651- 3660.
[5] Gungor, K.E., and Winterton, R.H.S., 1987, "Simplified
General Correlation for Saturated flow Boiling and Comparisons of
Correlations with Data", Chemical Engineering Research and Design,
65, pp. 148-156.
[6] Kattan, N., Thome, J.R., and Favrat, D., 1998, "Flow
boiling in horizontal tubes: part 3-development of a new heat transfer
model based on flow pattern", Journal of Heat Transfer,
Transactions of ASME, 120, pp. 156-165.
[7] Jung, D.S., McLinden, M., Radermacher, R., and Didion, D.,
1989, "Horizontal flow boiling heat transfer experiments with a
mixture of R22/R114", International Journal Heal Mass Transfer, 32,
pp. 131-145.
[8] Wang, C.C., Kuo, C.S., Chang, Y.J., and Lu, D.C., 1996,
"Two-phase flow heat transfer and friction characteristics of R22
and R407C", ASHRAE Transactions: Symposia, 102, pp. 830-838.
[9] Yan, Sheen., 2000, "A heat transfer and friction
correlation of fin-and-tube heat exchangers", International Journal
of Heat and Mass Transfer, 43, pp. 1651-1659.
[10] Wang, C.C., and Chi, K.Y., 2000, "Heat transfer and
friction characteristics of plain fin-and-tube heat exchangers, Part I:
new experimental data", International Journal of Heat and Mass
Transfer, 43, pp. 2681-2691.
[11] Webb, R.L., 1990, "Air-side heat transfer correlations
for flat and wavy plate fin-and-tube geometrics", ASHRAE
Transactions, 96, pp. 445-449.
[12] Horuz, I., Kurem, E., and Yamankaradeniz, R., 1998,
"Experimental and theoretical performance analysis of air cooled
plate finned tube evaporators", International Communication in Heat
and Mass Transfer, 25, pp. 787-798.
[13] Wongwises, S., Disawas, S., Kaewon, J., and Onurai, C., 2000,
Two-phase evaporative heat transfer co-efficient of refrigerant HFC-134a
under forced flow condition in a small horizontal tube, International
Communication in Heat Mass Transfer, 27, pp. 35-48.
[14] Indian Standard 1391, (1992) Part-I "Specification of
Unitary Air Conditioners".
[15] ANSI/ASHRAE 41.2-1987, "Standard methods for laboratory
air flow measurement".
[16] Kuppan, T., Heat Exchanger Design Hand book, pp 159-228,
Marcel Dekker Publications, 2000.
[17] National Institute of Standards and Technology, NIST
Thermodynamic properties of refrigerants and their mixtures, data base
23, (REFPROP V 7.1).
[18] ASHRAE standards. Methods for Testing for Rating Seasonal
Efficiency of Unitary Air Conditioners and Heat Pumps. ANSI/ASHRAE
116-1995, Atlanta.
M. Herbert Raj * and D. Mohan Lal
Refrigeration and Air Conditioning Division, Department of
Mechanical Engineering, Anna University, Sardar Patel road, Chennai,
India.
* Corresponding author E-mail address: herbertraj09@gmail.com