Lightning protection of structures and electronic equipment: a case study.
Okyere, P.Y. ; Eduful, George
Abstract
Lightning-related damages to structures and electronic equipment
can be mitigated by following lightning protection techniques
recommended in recognized national and international standards. However,
field engineers in many parts of the world doubts the effectiveness of
these design practices and are reluctant to use them. The paper uses a
case study to demonstrate the effectiveness of some standard methods for
lightning protection system for structure and equipment. The case study
was undertaken at the premises of a gold mining company located in an
area of high lightning activity. Frequent damages to the company's
electronic and telecommunication equipment and structures became a major
concern. The paper presents and discusses the techniques applied to
mitigate the problem and reports the results achieved which demonstrate
the effectiveness of the techniques.
Keywords: Lightning Protection System, Grounding System, Rolling
Sphere Method, Critical Resistance of Electrode.
Introduction
Lightning is a phenomenon that has often caused severe damage to
life and property. Direct lightning strike on structure results in an
impulse current ranging from around 3kA to 200kA. Long duration impulse
current can cause fire whereas short duration high current peak tend to
tear or bend metal parts [1]. The best protection against direct strike
is still the conventional lightning protection system which serves to
provide lightning attachment points and paths for the lightning current
to be safely dissipated into the ground. The system basically consists
of air terminals deployed at appropriate points on the structure to
intercept the lightning current, ground or earth electrodes to dissipate the lightning current into the earth and down conductors to carry the
lightning current from the air terminals to the ground electrodes. The
design and positioning of the air terminals are achieved using the
Rolling Sphere Method (RSM). This method is widely recognized in
national and international standards and its effectiveness has been
verified [2, 3].
Damages to electronic equipment can also result from indirect
lightning strike. The indirect strike induces transient over voltages
and currents which reach the electronic systems via power supply, data,
communication and signal lines. The lightning-induced over voltages can
arise from direct lightning strike on overhead lines, rise in ground
potential due to discharge of lightning current into the ground or
intense electromagnetic fields radiated by lightning flashes. Most of
the electronic equipment damage is caused by ground potential rise.
Electrical damage from ground potential rise (GPR) has an estimated cost
in the millions of dollars a year, but few field engineers or service
managers in the industry are even aware of the phenomenon [4]. The GPR
may not destroy equipment immediately but may weaken individual
components that fail later.
A series of field-proven national standards provides methods for
protecting structures and equipment from direct lightning and GPR
effects. These documents have existed for years, but most field
engineers and technicians doubt their effectiveness and are reluctant to
use them. For example, many national standards and research articles
recommend the interconnection of all earthing systems such as lightning
protection, power and communication, of a given installation to have a
single earth. In other part of the world, it effectiveness is being
doubted [5].
In the case study, certain number of the above lightning techniques
has been employed to check physical damage to structures and failure of
electronic systems at the premises of a mining company located in a
lightning prone area having isokeraunic level of 160 [6]. The paper
presents the techniques as applied and the results achieved.
Application of The Rolling Sphere Method
The RSM concept is based on electrogeometric model EGM. This model
is based on striking distance concept. From the physics of lightning
strike, a streamer emitted by an earth-based object cannot propagate to
a descending leader until the electric fields between the object and the
streamer are sufficiently high [2, 7]. The fields are proportional to
the amount of charge. Also, the peak current of a lightning strike is
proportional to the leader charge [7]. Thus, the striking distance is
related to the lightning current. The striking distance is greater for
larger current discharges [2, 7]. Use of the EGM and the
empirically-derived striking distance provides a method for calculating
the placement of air terminals to collect lightning current above a
desired threshold, the RSM being a simple method for applying the EGM.
The use of RSM for the design and position of air terminals involves
rolling an imaginary sphere of a radius equal to an assumed striking
distance over the air termination network. The sphere rolls up and over
air terminals and other grounded metal objects intended for direct
lightning protection. A piece of equipment is protected from a direct
stroke if it remains below a curved surface of the sphere by virtue of
the sphere's being elevated by the air terminals. Equipment that
touches the sphere or penetrates its surface is not protected. The RSM
generally assumes the striking distance to be the same for all
land-based objects irrespective of their geometry and for the earth
itself [2].
Application of the RSM to air terminal in the form of Franklin rods
could be simplified by deriving an analytical formula for the zone of
protection for a single mast defined by the RSM. Referring to Fig. 1,
the distance R known as lateral distance or attractive radius for the
mast can be obtained from the equation
[d.sub.s.sup.2] = [R.sup.2] + [([d.sub.s] - H).sup.2] (1a)
where [d.sub.s] is the striking distance and H is the height of the
mast as
[R.sup.2] = 2[d.sub.s] H - [H.sup.2] (lb)
or
R = [square root of H(2[d.sub.s] - H) (1c)
Also for a distance r away from the mast, the height h of an object
that touches the curve surface of the rolling sphere can be obtained
from
[d.sub.s.sup.2] = [(R - r).sup.2] + [([d.sub.s] - h).sup.2] (2a)
as
[(R - r).sup.2] = [2d.sub.s] h - [h.sup.2] (2b)
[FIGURE 1 OMITTED]
The radius r is termed the radius of protection for an object of
height h. Dividing Eq. (1b) by Eq. (2b) and simplifying gives Eq. (3)
which can be used to calculate the radius of protection for an object of
a given height h under a lightning rod or mast of height H.
r = R[[1 - [square root of 2[d.sub.s] h - [h.sup.2]/2[d.sub.s]H -
[H.sup.2]] (3)
For example, if a lightning rod is set at 12 metres above local
earth, then for a striking distance [d.sub.s] of 33m, the attractive
radius R = 25m(from Eq. (1c)) and for an object of h = 1.5 m, its radius
of protection r = 15.3 m (from Eq. (3)).
Fig. 3.3 shows a graphical representation of Eq. (3) for two cases:
H = 30 with a striking distance of 33 and H = 12 with a striking
distance of 60.
[FIGURE 2 OMITTED]
For a design of lightning protection system, International
Electrotechnical Commission (IEC 61024-1) presents four protection
levels for the protection of structures (see Table 1). The level of
protection chosen gives the minimum peak current expected to be
intercepted by the lightning protection system and this is turn used to
derive the rolling sphere radius.
Electronic Equipment Protection
Surge protective devices [SPDs] properly applied to electric
circuit can protect electronics from most of the secondary effects of
lightning. More than 90% of SPDs are based on Metal Oxide Varister MOV component connected across the terminals to be protected [8]. The MOV is
non linear device which allows large amounts of surge current to flow
through it whilst maintaining a relatively small voltage across it. SPDs
work by detecting over voltages, and shorting them out. Properly chosen
and installed MOV demonstrates an excellent ability to clamp over
voltages to a safe level absorbing excess of the transient energy
associated with lightning. However, no surge protective device ever made
will protect electronic equipment from a ground potential rise [4, 9].
During a ground potential rise, the surge protective devices, merely
offer an additional current path off the affected site to remote ground.
They actually provide a path for current to flow in the reverse
direction [4]. GPR effects can be mitigated by diligent application of
the following techniques:
Divide and Control
The control of dissipating lightning-strike energy requires
division [9]. This is an absolute must for success because of the
magnitude of the current and the resulting surge impedance of any single
dissipation path. Electrode system should be well spread in order to
have fast and less concentrated dispersion of charge brought by the
lightning current, into the mass of earth. According to Gomez [5],
crowded configuration of earth electrodes or a single earth electrode
may not facilitate such charge dispersion. A radial electrodes connected
to a ground ring bonded together is one sure way of dividing the
lightning current [9]. For example, ten radial electrode bonded to a
ground ring will divide lightning current up into 10 smaller segments.
This will help ensure that the lightning will more likely follow the
designated paths for dissipation into the earth, and lower the resulting
GPR. According to More et al [10], the optimum length of such radials is
approximately 8 metres, with interconnecting 1.4m ground rods [11].
Longer-length radials will offer little dissipation improvement because
the lightning-strike energy will not remain on the radials for much over
24 m [12]. The ground potential rise and a potential profile over soil
during striking event are much more reduced for this configuration in
comparison with others [13].
Reducing Ground Resistance Value
GPR is directly proportional to earth electrode resistance and the
current flowing through it [14]. Hence, any attempt to reduce the earth
electrode resistance is likely to lower the GPR value and consequently
reduce its effects. There are a number of methods which can be used to
reduce earth resistance of earth electrodes on sites where soil
resistivity is high, replacement of the soil within its effective
resistance area with more conductive soil being one of them. Replacing
the soil in the entire effective resistance area is in general not
practical. The effectiveness of replacing soil in the critical
resistance area only is one technique that can be applied [11].
Bonding
Lightning potential equalization is considered indispensable in
electronic equipment protection. This is believed to be of greater
importance than the ground resistance of earthing system [15]. Single
point grounding is an absolute must to prevent GPR and from damaging
equipment [9]. This is achieved by establishing what is called a common
reference bar. Every earth conductor that enters or leaves a
'service entrance point' is bonded to the reference bar. This
means earth of power, phone, coaxial and control cabling are all bonded
together at the reference bar. The reference bar is then grounded
through a lowest inductance connection. Current cannot flow between two
points of equal potential, even if the equipment rises to several
thousand of volts during strike, no voltage differentials will exist
that can drive damaging currents through them.
Case Study
Introduction
The case study was undertaken at the administration area of the
Bibiani Mines, a mining company located in the western region of Ghana.
The administration block houses over 60% of the company's
electronic equipment and this equipment must work during the most
difficult times including bad weather conditions. The company had been
plagued with high incidence of electronic equipment failures including
damage to a satellite dish by direct lightning strikes. Direct strike on
the satellite dish had occurred at least once in every two years
resulting in physical damage to the dish. In this study, design of air
termination network with the RSM was undertaken. High earth resistances
were lowered by backfilling critical resistance areas of earth
electrodes. GPR effects were reduced with vertical and horizontal ground
electrode system and finally all the grounding systems and metallic
structures were bonded together to eliminate incidence of potential
differential. Results achieved demonstrated the effectiveness of these
techniques.
Layout of the administration area
Located in the administration area is administration building; an
outdoor power station, a communication tower and a satellite dish. The
area layout is shown in Fig 3
[FIGURE 3 OMITTED]
A 3-phase, 200kVA, 33/0.4 kV, delta-star transformer at the power
station supplies power to the building through an Automatic Voltage
Switcher (AVS) installed at the service entrance of the building. The
AVS feeds a 10kVA interruptible power supply (UPS) and this in turn
supplies power to computers, office equipment and private automatic
business exchange (PABX) (see Fig. 4). Lines from the PABX are protected
by data line protector (DLP). A coaxial cable from the satellite dish
goes to the main internet server in the administration building. Its
sheath, before the study, had been grounded at the base of the satellite
dish where earth resistance reading was 14 ohms. Another coaxial cable
leaves the communication tower for the PABX. A lightning protection
system was provided for the administration building and a separate
protection system for the communication tower was supposed to take care
of the satellite dish. The lightning protection for the administration
building consisted of two Franklin rods, separately grounded via two
down conductors. The tower had one Franklin rod installed with the tower
serving as down conductor and its footings as grounded electrodes. On
the 33-kV side of the transformer is installed a lightning arrestor of
IOkA, 8/20[micro]s rating
[FIGURE 3 OMITTED]
[FIGURE 4 OMITTED]
Applied Changes
The case study was carried out in mid 2004. Before then, the
lightning protection measures in place had not been effective in
checking lightning-related damages to structures and equipment.
Financial statistics available indicate that the existing protection
system resulted in about 10% reductions in the annual maintenance cost
[16]. The ineffectiveness of the existing protection system could be
attributed to improper design of air terminals and grounding systems and
inadequate protection against ground potential rise.
The following steps were taken to improve the effectiveness of the
total lightning protection at the area.
Step I: The satellite dish and the tower, 2m and 30m tall
respectively, are spaced at a distance of 30m. From Eq. (3), the dish
could be considered protected for an assumed striking distance of 60m
which corresponds to a protection level IV (see Table 1). The dish was
relocated 15m from the tower to give it a protection level of II, the
corresponding striking distance being 30m.
Step 2: The lightning protection of the administration building was
improved to level IV by erecting four 12-m masts at corners of the
building. The ridge of the building roof is about 6m above the ground.
Step 3: Earth electrode resistances at various sites were improved
by installing additional earth rod electrodes and backfilling the
critical resistance area of the electrodes with low resistivity soil
[11]. The old and new earth electrode resistance values at the various
sites are given in Table 2.
In addition, the grounding systems at the administration building
and at the tower base were configured as shown in Figs. 5 and 6 to take
advantage of the horizontal nature of lightning discharge into the
ground and to also improve on a ground potential profile and reduce the
GPR effects [10]. A 75 [mm.sup.2] bare conductor was used to ring the
ground electrodes and radials added to the administration grounding
systems, again to reduce the GPR effects.
Step 4: At the transformer station, the arrestor earth, the
transformer tank and the transformer neutral earth were bonded together
resulting in overall earth resistance of 5 ohms and at the service
entrance point, the sheath of the coaxial cables and all earth terminals
of equipment were connected to an earth reference bar which was in turn
bonded to the lightning grounding system at the building.
[FIGURE 5 OMITTED]
[FIGURE 6 OMITTED]
Results and Discussion
Fig. 7 shows the insulation on a 75 [mm.sup.2] copper grounding
conductor burnt by lightning current in one incident of direct lightning
strike on the tower. This was after the redesign of the lightning
protection system. This lightning current was intercepted and discharged
into the ground without any of the electronic equipment suffering
damage. There has also not been any direct strike on the satellite dish.
For a critical evaluation of the protection performance, data on
electronic equipment failure rate before and after the redesign were
taken from the company's maintenance and operations report and
analyzed [16]. The results of the analysis are reported in Table 3 and
Fig. 8. The failure rate of equipment type is defined as the ratio of
the number of times the type has suffered damage to the total number of
the type in place.
[FIGURE 7 OMITTED]
[FIGURE 8 OMITTED]
To quantify the degree of overall protection performance offered by
the protection system, average equipment failure rate for 2002 and 2003
were compared with average failure rate for 2004 and 2005. The results
are reported in Table 4 below. Fig. 9 and 10 below also throws more
light on table above for it to be absorbed easily.
Protection performance was calculated using the following equation:
Protection performance = [avf.sub.1] - [avf.sub.2]/[avf.sub.1] X
100%
Where,
[avf.sub.1] is the average failure rate between 2002 and 2003
[avf.sub.2] is the average failure rate between 2004 and 2005
As can be noticed in Table 4, there is an overall average
protection performance level of 75%. Financially, a total savings of
$80,000 was recorded in the annual equipment maintenance cost over the
period of 2004 and 2005 [16]. As compared with the previous performance
of 10% [8], the 75% improvement was significant and explains why
diligent application of recognized lightning protection standards still
remains the best.
[FIGURE 9 OMITTED]
[FIGURE 10 OMITTED]
Conclusion
Technical measures implemented in an attempt to check the damages
of electronic equipment and structures of a company have been presented.
Results achieved in terms of the control of equipment failure rate and
the elimination of direct hits on structures to date has proved that the
measures are effective. It is observed that there is still room for
improvement and this may be achieved by appropriate installation of
suitable surge protection devices.
References
[1] Consultants Handbook "Recommendations for the Protection
of Structures against Lightning" W. J. Furse & Co. Ltd, Wilford
Road, Nottingham.
[2] Uman, M. A. & Rakov, V. A.: A critical review of
nonconventional approaches to lightning protection, American
Meteorogical Society, December 2002,1809-1819.
[3] Prof. Bouquegneau C, ICLP 2004: A critical view on the
lightning protection international standard
[4] Ernest M. Duckworth Jr. and W.G. Petersen, May 15, 1995: Be
Alert to Danger posed by Ground Potential Rise. America's Network
(Advanstar Communications Inc.)
[5] Chandima Gomez, ICLP 2004: Interconnection of Different
Earthing Systems of a given Installation
[6] Climatological Data, 2004&2005: Metrological Department
Service of Ghana-Sefwi Bekawai
[7] William Rison: Experimental Validation of Conventional and
Non-Conventional Lightning Protection Systems
[8] Roy B. Carpenter Jr., Mark M. Drabkin: "Total Facility
Lightning Protection". Lightning Eliminators & Consultants,
Inc. 6687 Arapahoe Rd., Boulder, Colorado, USA
[9] Ernest M. Duckworth Jr., P.E. Protection Methods for GPR,
Isolation, Shielding and Grounding from Lightning. Power Pulse.Net (A
Darnell Group Publication).
[10] More, C.B., G.D Aulich and W. Rison: "An Examination of
Lightning-Strike-Grounding Physics".
[11] Okyere, P. Y. & Eduful, G.: Reducing earth electrode
resistance by replacing soil in critical resistance area, International
Journal of Modern Engineering Technology, volume 6, number 2, spring
2006
[12] Lorentzou M.I. and Hatziargyrious N.D, ICLP 2000:
"Effective Dimensioning of Extended Grounding Systems for Lightning
Protection". Pp 435-439
[13] Reyer Venhuizen, May 2000; "Earthing & EMC -A Systems
Approach to Earthing" (Power Quality Application Guide)
[14] Richard Knight Sr. May 5, 2005: "Isolation Protection for
911 Center" (A Power Systems Perspective). Pp 3
[15] Baatz, Stuttgart, Germany: Golde, Lightning Academic Press,
NY, 1977, vol.2, chapter 19 by. Pp 611
[16] Operations and Financial Reports: Anglo gold- Ashanti (Bibiani
Mines)-2002, 2003, 2004 and 2005
P.Y. Okyere and George Eduful *
Kwame Nkrumah University of Science and Technology
Private Mail Bag, Kumasi-Ghana
* Corresponding Author E-mail: georgeeduful@yahoo.com
Table 1: Lightning Protection Level, Efficiency
Protection Rolling Sphere
Protection Level Effectiveness Radius
I 98% 20m
II 95% 30m
III 90% 45m
IV 80% 60m
Table 2: Results of Earth Resistance Improvement
Earth Resistance in ohms
Site Previous Present
Tower 13 5
Building 31 1.7
arrestor 87 5
neutral 110 5
Table 3: Results of Equipment Failure analysis
Failure Rate
Types of equipment 2002 2003 2004 2005
Computers 54% 47% 29% 18.50%
Printers 39% 20% 10% 10%
Photocopier 66% 67% 0% 0%
Fax machine 20% 50% 0% 0%
PABX 120% 88% 50% 37.50%
Internet link device 100% 67% 25% 0%
servers 200% 0% 0% 0%
Phones 55% 41% 50% 21%
Table 4: Overall Protection Performance
Equipment Average Average Protection
failure failure performance (%)
rate for rate for
2002 and 2004 and
2003(%) 2005 (%)
Computers 50.5 23.75 58
Printers 29.5 10 66
Photocopier 66.5 0 100
Fax machine 35 0 100
PABX 104 43.75 60
Phones 48 23 52
Internet link Device 83.3 25 70
Computer server 100 0 100
Average protection performance 75%