  • 标题:Active Disturbance Rejection Control of Thermal Power Unit Coordinated System based on Frequency Domain Analysis
  • 本地全文:下载
  • 作者:Ruiqing Zhang ; Liangyu Ma ; Yongguang Ma
  • 期刊名称:TELKOMNIKA (Telecommunication Computing Electronics and Control)
  • 印刷版ISSN:2302-9293
  • 出版年度:2016
  • 卷号:14
  • 期号:1
  • 页码:162-170
  • DOI:10.12928/telkomnika.v14i1.2746
  • 语种:English
  • 出版社:Universitas Ahmad Dahlan
  • 摘要:For the multi-input and multi-output, strong-coupling nonlinear features of coordinated system for thermal power unit, it is difficult for traditional PID coordinated control scheme to meet the power grid demand which often participates in peak regulation and frequency modulation. In this paper, Inverse Nyquist array is employed to carry out frequency domain analysis of the plant model. Then Pseudo diagonalization is used to design the static decoupling compensation matrix of the system. Above on these, the linear active disturbance rejection controller of every channel in coordinated system can be designed repectively. Dynamic coupling and system unknown parts are observed by extended state observer of ADRC and is compensated to the system in time. The simulation tests show that the disturbance rejection results of the load and the main steam pressure for the coordinated control system under LADRC is better than that of PID control.
  • 其他摘要:For the multi-input and multi-output, strong-coupling nonlinear features of coordinated system for thermal power unit, it is difficult for traditional PID coordinated control scheme to meet the power grid demand which often participates in peak regulation and frequency modulation. In this paper, Inverse Nyquist array is employed to carry out frequency domain analysis of the plant model. Then Pseudo diagonalization is used to design the static decoupling compensation matrix of the system. Above on these, the linear active disturbance rejection controller of every channel in coordinated system can be designed repectively. Dynamic coupling and system unknown parts are observed by extended state observer of ADRC and is compensated to the system in time. The simulation tests show that the disturbance rejection results of the load and the main steam pressure for the coordinated control system under LADRC is better than that of PID control.
国家哲学社会科学文献中心版权所有