期刊名称:IOP Conference Series: Earth and Environmental Science
印刷版ISSN:1755-1307
电子版ISSN:1755-1315
出版年度:2018
卷号:121
期号:4
页码:042017
DOI:10.1088/1755-1315/121/4/042017
语种:English
出版社:IOP Publishing
摘要:This paper presents a novel fault location method by injecting travelling wave current. The new methodology is based on Time Difference Of Arrival(TDOA)measurement which is available measurements the injection point and the end node of main radial. In other words, TDOA is the maximum correlation time when the signal reflected wave crest of the injected and fault appear simultaneously. Then distance calculation is equal to the wave velocity multiplied by TDOA. Furthermore, in case of some transformers connected to the end of the feeder, it's necessary to combine with the transient voltage comparison of amplitude. Finally, in order to verify the effectiveness of this method, several simulations have been undertaken by using MATLAB/SIMULINK software packages. The proposed fault location is useful to short the positioning time in the premise of ensuring the accuracy, besides the error is 5.1% and 13.7%.