期刊名称:IOP Conference Series: Earth and Environmental Science
印刷版ISSN:1755-1307
电子版ISSN:1755-1315
出版年度:2018
卷号:108
期号:5
页码:052104
DOI:10.1088/1755-1315/108/5/052104
语种:English
出版社:IOP Publishing
摘要:This paper presents an improved Voltage Droop control strategy, which updates the reference of DC link voltage by adding the difference between reference and actual voltage, which also adopts a dynamic P-V droop coefficient to improve the DC voltage level. By applying this method, we can eliminate the steady-state deviation of DC link voltage caused by ignoring the power loss in converter. In this paper, in order to demonstrate the reduction of deviation of DC link voltage, an improved control strategy is implemented for a three-terminal flexible DC power system modelled in PSCAD/EMTDC.