期刊名称:International Journal of Innovative Research in Computer and Communication Engineering
印刷版ISSN:2320-9798
电子版ISSN:2320-9801
出版年度:2017
卷号:5
期号:3
页码:6299
DOI:10.15680/IJIRCCE.2017.0503402
出版社:S&S Publications
摘要:in this paper, the specific protection device for Reliability Improvement options has been identified forthis case study.Reliability performance of existing distribution network with and without protection devices has beenevaluated. The economic impact of power interruption to utility and Brewery Factory estimated. The collectedinterruption data analyzed and reliability of existing power distribution system is assessed. Power distribution systemwith protection device along the feeder evaluated using ETAP software. Comparing scenarios using reliabilityperformance and protection coordination simplicity best scenario is selected. The simulation of the power distributionmodels shows that the application of reclosers can improve the reliability of the overall system from 47% to 83%. Thestudy will be useful for power distribution system planners, load forecasting and decision makers since it presents aconcern on how much demand is available at each section of power distribution system and reliability performance ofeach section can beevaluated easily. By minimizing unsold electrical energy EEU will benefits the corporation to earnmore profit.
关键词:Reliability; power distribution system; Reclosers; Reliability indices; TCC curve; ETAP etc.