期刊名称:IOP Conference Series: Earth and Environmental Science
印刷版ISSN:1755-1307
电子版ISSN:1755-1315
出版年度:2018
卷号:170
期号:4
页码:042047
DOI:10.1088/1755-1315/170/4/042047
语种:English
出版社:IOP Publishing
摘要:When transmission lines pass through microtopographic area, the acceleration effect of wind speed should be taken into consideration during designing. However, the acceleration ratio coefficient of wind speed should not be selected simply according to mountain slope as specified by standards. In order to comprehensively consider the impact of wind direction and microtopography upon acceleration ratio of wind speed. This paper selects the acceleration ratios of wind speed at the height of 10m-120m in a tower position at 24 angles of direction wind by virtue of CFD simulation analysis. Combined with the line trend, this paper compares and calculates the change rule of wind loads on tower body and lead/ground wires after considering the pre/post-impact of acceleration ratio of wind speed. Through analysis, this paper forms suggestions on wind-resistant design for lead/ground wires in transmission lines in microtopographic area as well as accident analysis for reference.