期刊名称:IOP Conference Series: Earth and Environmental Science
印刷版ISSN:1755-1307
电子版ISSN:1755-1315
出版年度:2018
卷号:186
期号:3
页码:012034
DOI:10.1088/1755-1315/186/3/012034
语种:English
出版社:IOP Publishing
摘要:The research and development of the emergency handling device was to deal with sudden pollution incidents of drinking water sources. Kaolin was used to prepwere experimental simulated wastewater, and water turbidity was used as an evaluation index. The effect of stirring methods, rotation speed and agitation time on the diffusion rate of kaolin in the water-coagulation pool in water was investigated by single-factor experiments. Then determine the coagulation pool parameters for the emergency treatment of drinking water sources. The results showed: (1) The best stirring parameters for the coagulation pool during mechanical stirring were: stirring speed 80 r/min, stirring time 30 s. (2) The optimal stirring parameters for the coagulation pool during submersion stirring were: the stirring speed was 100 r/min, and the stirring time was 60 s. (3) The optimal flow parameters of the coagulation pool for the gravity-flow of water were: the flow velocity of the water was 2 m/s and the time was 10 minutes. The research showed: the mechanical stirring method was more conducive to the diffusion of the coagulant in the coagulation pool than the submersible stirring and the water body gravity-flow; the parameters of the coagulation pool in the emergency treatment of drinking water sources were determined as the stirring mode: mechanical stirring, stirring speed: 80 r/min, stirring time: 30 s.