期刊名称:IOP Conference Series: Earth and Environmental Science
印刷版ISSN:1755-1307
电子版ISSN:1755-1315
出版年度:2018
卷号:186
期号:5
页码:012002
DOI:10.1088/1755-1315/186/5/012002
语种:English
出版社:IOP Publishing
摘要:Energy consumption due to duct resistance accounts for approximately 30–50% of the total energy consumption in central air conditioning systems. Three resistance reduction methods of dividing flow tees in a ventilation and air-conditioning duct are studied. A reasonable position for installing the guide vane is proposed. The form of the guide vane and the cambered surface are optimized. The resistance characteristics of the tee are analyzed. The implementation effect of optimizing a tee is verified through a full-scale experiment. The results show that the resistance reduction rate of the proposed guide vane is 18.3% to 65.1% under different resistance reduction methods. The calculated results are verified by a full-scale experiment and by previous studies, ensuring the accuracy of the present study.