摘要:In this study, the application potential of desiccant cooling system with indirect evaporative precooling is analyzed for moderate climatic conditions. Wrocław (Poland) was selected as a representative city. On the base of summer season weather parameters different system running modes were proposed such as cooling and dehumidification mode (Mode 1) and only cooling mode (Mode 2). The average month Thermal and Electrical COP were established for selected climatic conditions. It was concluded that proposed system allows to cool the air without occurrence of condensation in Mode 2 with high average monthly electrical COP (COPel = 62.2 in August). On the other hand when dehumidification is needed, system operates in Mode 1 and obtains relatively high average Thermal COP values (COPth = 2.2).
其他摘要:In this study, the application potential of desiccant cooling system with indirect evaporative precooling is analyzed for moderate climatic conditions. Wrocław (Poland) was selected as a representative city. On the base of summer season weather parameters different system running modes were proposed such as cooling and dehumidification mode (Mode 1) and only cooling mode (Mode 2). The average month Thermal and Electrical COP were established for selected climatic conditions. It was concluded that proposed system allows to cool the air without occurrence of condensation in Mode 2 with high average monthly electrical COP (COPel = 62.2 in August). On the other hand when dehumidification is needed, system operates in Mode 1 and obtains relatively high average Thermal COP values (COPth = 2.2).