摘要:In this paper the authors analysed the impact of the calculation method of the partial load conditions and the accuracy of the energy demand profile on the simulation results of the air/water heat pump operation supplying the heating system. All the analyses results were compared to the results acquired for the real installation of the air/water heat pump located in Poland. The authors assessed the inaccuracy of the unit’s efficiency estimation resulting from the simplified thermal load profile of the air/water heat pump. It has been showed that using the monthly energy demand as the input data gives satisfactory results. Inaccuracy of the monthly simulation results in relation to simulations carried out on the actual hourly energy demand by no more than 7% is acceptable. On average, this deterioration did not exceed 3%.
其他摘要:In this paper the authors analysed the impact of the calculation method of the partial load conditions and the accuracy of the energy demand profile on the simulation results of the air/water heat pump operation supplying the heating system. All the analyses results were compared to the results acquired for the real installation of the air/water heat pump located in Poland. The authors assessed the inaccuracy of the unit’s efficiency estimation resulting from the simplified thermal load profile of the air/water heat pump. It has been showed that using the monthly energy demand as the input data gives satisfactory results. Inaccuracy of the monthly simulation results in relation to simulations carried out on the actual hourly energy demand by no more than 7% is acceptable. On average, this deterioration did not exceed 3%.