  • 标题:Distribution and forecast of air temperature in determining of heat output of the district heating substation with heat storage
  • 本地全文:下载
  • 作者:Michał Turski ; Robert Sekret
  • 期刊名称:E3S Web of Conferences
  • 印刷版ISSN:2267-1242
  • 电子版ISSN:2267-1242
  • 出版年度:2019
  • 卷号:116
  • 页码:1-8
  • DOI:10.1051/e3sconf/201911600094
  • 出版社:EDP Sciences
  • 摘要:The aim of this article was to determine the energetic effect of adapting the control method of district heating substation to a solution using dispersed heat storage. The current control method of district heating substation uses the equations for regulating the temperature distribution of the installation water based on the value of the external temperature. This control method causes a significant amount of heat not consumed by end users. To adapt the control method to a solution using dispersed heat storage the following values were analyzed: the forecast of external temperature and duration of episodes with the lowest external temperatures on the heat output of the district heating substation based on 63 heating seasons. Obtained results were presented for a district heating substation in Poland. The analysis shows that a temperature of -15°C can be adopted as the reference to determine the expected heat output of the district heating substation. On this basis the demand for heat output for central heating purposes was 406 kW instead of 430 kW. The energetic effect of use dispersed heat storage to compensate the reduced heat output of the district heating substation was 24 kW with a compensation time of 24.2 h.
  • 其他摘要:The aim of this article was to determine the energetic effect of adapting the control method of district heating substation to a solution using dispersed heat storage. The current control method of district heating substation uses the equations for regulating the temperature distribution of the installation water based on the value of the external temperature. This control method causes a significant amount of heat not consumed by end users. To adapt the control method to a solution using dispersed heat storage the following values were analyzed: the forecast of external temperature and duration of episodes with the lowest external temperatures on the heat output of the district heating substation based on 63 heating seasons. Obtained results were presented for a district heating substation in Poland. The analysis shows that a temperature of -15°C can be adopted as the reference to determine the expected heat output of the district heating substation. On this basis the demand for heat output for central heating purposes was 406 kW instead of 430 kW. The energetic effect of use dispersed heat storage to compensate the reduced heat output of the district heating substation was 24 kW with a compensation time of 24.2 h.
国家哲学社会科学文献中心版权所有