首页    期刊浏览 2024年11月30日 星期六
登录注册

文章基本信息

  • 标题:Design of Close Loop Cooling Water System for Khan Khwar Hydro Power Plant
  • 本地全文:下载
  • 作者:Syed Faheem Ahmed ; Hamza Hafeez ; Balaj Jamal
  • 期刊名称:Lecture Notes in Engineering and Computer Science
  • 印刷版ISSN:2078-0958
  • 电子版ISSN:2078-0966
  • 出版年度:2018
  • 卷号:2237&2238
  • 页码:697-701
  • 出版社:Newswood and International Association of Engineers
  • 摘要:Khan Khwar Hydropower Plant has an installed capacity of 72 MW. It started its commercial operation in November 2010, since then it has added 948.528 MWh of electricity to the national grid (as of 30th September 2017). This national asset is facing numerous unnecessary forced shutdowns due to its cooling water system. Currently installed cooling system is once through open loop cooling water system which pumps the water from tailrace, the water in the tailrace causes the problem of clogging due to sediments inside the cooling tubes responsible for the exchanging heat, it also damages pumps by choking them and may contaminate the lubricating oil because of the puncturing of the cooling coils in turn damaging the bearings. The clogs, sludge or fouling contains ion ferrite is believed to originates from the tailrace. This results in unforeseen plant shutdown. Due to above reasons plant management has given this case study for considering switching from once through open loop cooling water system to closed loop cooling water system. Closed loop cooling water system with tubular heat exchanger is considered. During the designing of the heat exchanger Log Mean Temperature Difference LMTD method is used. The scope of this paper is limited to the theories of thermodynamics.
  • 关键词:Khan Khwar Hydro Power project (kkhpp) in Pakistan; Cooling Water system; LMTD (log mean temperature difference); Nusselt number (Nu); Prandtl number (Pr); Reynold number (Re)
国家哲学社会科学文献中心版权所有