首页    期刊浏览 2024年07月24日 星期三
登录注册

文章基本信息

  • 标题:Electrical performance analysis of 110 kv GIS terminal extension conducting rod
  • 本地全文:下载
  • 作者:Jianjia Duan ; Sanwei Liu ; Zeyu Zeng
  • 期刊名称:E3S Web of Conferences
  • 印刷版ISSN:2267-1242
  • 电子版ISSN:2267-1242
  • 出版年度:2020
  • 卷号:185
  • 页码:1-5
  • DOI:10.1051/e3sconf/202018501020
  • 出版社:EDP Sciences
  • 摘要:As GIS terminal is in cooperation with GIS switch, the GIS terminal with 470 mm structure is usually equipped with a 757 mm structure GIS switch. In order to study the influence of the extended conductive pole on the electrical performance of GIS cable terminal, the contact resistance of the extended conductive pole is measured. The measurement results show that the contact resistance meets the requirements of conductive flow. Through finite element simulation calculation of the influence of the extended conducting rod on the GIS terminal electric field distribution, it was found that the maximum field strength of the cable terminal of the extended conducting rod increased by 2 kv/mm, which was smaller than the breakdown field strength of sulfur hexafluoride gas, and the extended conducting rod did not affect the safe and stable operation of the GIS terminal. Extend the conductive rod by finite element simulation calculation interface without air gap and 0.1 mm gap, the distribution of electric field in both cases, contact resistance conforms to the requirements under the premise, extend the conductive rod interface is 0.1 mm gap the maximum field strength of 1.4 kv/mm, less than the sulfur hexafluoride gas breakdown voltage, contact air gap does not affect the safe and stable operation of the GIS terminal.
国家哲学社会科学文献中心版权所有