  • 标题:INCREASING THE EFFICIENCY OF ELECTRICITY SUPPLY BY IMPROVING THE OPERATION OF POWER SYSTEM SUBSTATIONS POWER TRANSFORMERS
  • 其他标题:ПІДВИЩЕННЯ ЕФЕКТИВНОСТІ ПОСТАЧАННЯ ЕЛЕКТРОЕНЕРГІЇ ШЛЯХОМ УДОСКОНАЛЕННЯ РОБОТИ СИЛОВИХ ТРАНСФОРМАТОРІВ ПІДСТАНЦІЙ ЕНЕРГОСИСТЕМИ
  • 本地全文:下载
  • 作者:Anatolii Panchenko ; Andrii Ministerskiy ; Yevhenia Zaricniak
  • 期刊名称:Системи озброєння і військова техніка
  • 印刷版ISSN:1997-9568
  • 电子版ISSN:2518-1580
  • 出版年度:2019
  • 卷号:58
  • 期号:2
  • DOI:10.30748/soivt.2019.58.12
  • 语种:English
  • 出版社:Ivan Kozhedub Kharkiv National Air Force University
  • 摘要:The switching equipment of power substations is made on electromechanical drives (sometimes manual),the duration of the signal passing from the moment of signal supply and the direct response of contacts can take several periods,due to the inertia of mechanical processes. It is impossible to obtain identical electromechanical systems for each phase. Therefore,the moment of switching on,both in relation to the voltage sinusoid,and in relation to the phases is random,which provokes significant current surges,which in a number of cases are perceived as a short circuit and equipment malfunction. Using modern transistor assemblies I J B T makes it possible to create switching equipment for a fixed time,,now the term control commutation is used. Transient processes when triggering switches occur as they are switched on and off. Switching overvoltages can be minimized by using soft switching methods. The periodic component when switched on can be substantially weakened if the circuit of the supply circuits occurs near the maximum voltage,or eliminated altogether,at several times turning on the same load (memory element used). When unlocking a consumer with a low power factor there is a risk of repeated breakdowns of the contacts,in order to eliminate the contact of the contacts should occur far enough from the zero value of the current and until the moment of transition through zero and the arcing of the arc,the distance between the contacts should be sufficient and correspond to a significant strength of the gap between the contacts. In some cases,with the arbitrary switching of an unloaded transformer,there are current jets comparable to short-circuit currents,which provokes a false alarm of relay protection. To eliminate this phenomenon,“memory” is used for phase values of currents and the calculation of residual magnetism in them at the transformer's center,which allows it to choose a time moment that minimizes the transitional aperiodic process when reswitching. In the article the method of determination in automatic mode of the switching moment is offered depending on the size of the load,its nature and the history of the switching off of the transformer. Together,these parameters allow you to find the instant of each phase's activation without initiating the transient process.
  • 其他摘要:В існуючій на цей час споживацькій системі електропостачання відомі випадки необґрунтованого спрацювання аварійної автоматики підстанцій,спровоковані випадковим збігом в часі розрізнених штатних факторів – величини навантаження. Момент комутації масляних
  • 关键词:load parameters;transformer;short circuit;harmonious signal.
  • 其他关键词:параметри навантаження;трансформатор;коротке замикання;гармонічний сигнал.