摘要:With the increase of generator running time, the probability of generator rotor problems increases constantly. In this paper, a generator is taken as an example. During maintenance, the generator is found to have the evidence of turn-to-turn short circuit of rotor windings by the repetitive surge oscilloscope method, which is verified by the AC impedance power loss test of the rotor winding. The position of turn-to-turn short circuit is determined by the inter-pole voltage method and the coil voltage method. The accuracy of the test method is further verified by the generator rotor’s return repair.
其他摘要:With the increase of generator running time, the probability of generator rotor problems increases constantly. In this paper, a generator is taken as an example. During maintenance, the generator is found to have the evidence of turn-to-turn short circuit of rotor windings by the repetitive surge oscilloscope method, which is verified by the AC impedance power loss test of the rotor winding. The position of turn-to-turn short circuit is determined by the inter-pole voltage method and the coil voltage method. The accuracy of the test method is further verified by the generator rotor’s return repair.