摘要:Failures of transformers in sub-transmission systems not only reduce reliability of power system but also have significant effects on power quality since one of the important components of any system quality is reliability of that system. To enhance utility reliability, failure analysis and its rates, failure origin and physical damage causes must be studied. This paper describes a case study of the reliability of sub-transmission transformers (63/20 KV) installed in Mazandaran province, operated in sub-transmission system. The information obtained from Meandering Regional Electric Company. The results of study and analysis on 60 substation including more than 110 transformers installed in sub-transmission system show that the failure modes of transformers can be represented by Weibull distribution. Weibull statistics have been widely used and accepted as a successful mathematical method to predict the remaining life time of any equipment. Useful conclusions are presented both for power systems operators and manufactures for improving the reliability of transformers.