摘要:This paper deals with the applications of automatic generation control (AGC) of a hydro —thermal and thermal—thermal systems in a power system deregulated environment and makes an attempt to provide a new practical AGC model to fulfill the needs of a modern restructured hydro-thermal and thermal -thermal power system. Several Distribution Company, distribution Participation Matrix,and area participation factor have been tried out and dynamic responses for frequency, tie line flow and power generations are obtained to examine the performance of the system in deregulated environment considering integral controllers. Investigations have been also carried out to study the effect of generation rate constraint and the importance of APF in deregulated environment. Study also reveals that the conventional integral controllers are quite robust than PI and PID controllers and the optimum integral gains once set for nominal condition need not be changed for +25% variations in system parameters and +20% variations in operating load condition from their nominal values.