期刊名称:International Journal on Electrical Engineering and Informatics
印刷版ISSN:2085-6830
出版年度:2012
卷号:4
期号:3
出版社:School of Electrical Engineering and Informatics
摘要:Switching operations in a gas insulated substations generate very fast transient over voltages (VFTO) which are dangerous for the transformer and the system insulation because of their short rise time. Under special circumstances the terminal over voltages can arise close to the transformer BIL. The suppression of VFTO is very important in GIS systems. Different techniques are applied to 245 kV GIS model. The simulation used ATP-EMTP package program to evaluate the VFTO at the sensitive points in GIS. The different results are compared to determine the effective mitigation method. The results show that the wave steepness and the amplitudes of VFTO can be reduced to about 1Pu with less oscillation frequency.
关键词:Gas-insulated substation (GIS); very fast transient overvoltages (VFTOs);very fast transient currents (VFTCs); Mitigation techniques.