首页    期刊浏览 2025年02月22日 星期六
登录注册

文章基本信息

  • 标题:Evaluation of Harmonic Content from a Tap Transformer Based Grid Connection System for Wind Power
  • 本地全文:下载
  • 作者:S. Apelfröjd ; S. Eriksson
  • 期刊名称:Journal of Renewable Energy
  • 印刷版ISSN:2314-4386
  • 出版年度:2013
  • 卷号:2013
  • DOI:10.1155/2013/190573
  • 出版社:Hindawi Publishing Corporation
  • 摘要:Simulations done in MATLAB/Simulink together with experiments conducted at the Ångströms laboratory are used to evaluate and discuss the total harmonic distortion (THD) and total demand distortion (TDD) of a tap transformer based grid connection system. The grid connection topology can be used with different turbine and generator topologies and is here applied on a vertical axis wind turbine (VAWT) with a permanent magnet synchronous generator (PMSG) and its operational scheme. The full variable-speed wind conversion system consists of a diode rectifier, DC link, IGBT inverter, LCL-filter, and tap transformer. The full variable-speed operation is enabled by the use of the different step-up ratios of the tap transformer. In the laboratory study, a full experimental setup of the system was used, a clone of the on-site PMSG driven by a motor was used, and the grid was replaced with a resistive load. With a resistive load, grid harmonics and possible unbalances are removed. The results show a TDD and THD below 5% for the full operating range and harmonic values within the limits set up by IEEE-519. Furthermore, a change in tap, going to a lower step-up ratio, results in a reduction in both THD and TDD for the same output power.