首页    期刊浏览 2025年08月14日 星期四
登录注册

文章基本信息

  • 标题:Rationalization of cooling water consumption in extraction system B-811 LSV
  • 本地全文:下载
  • 作者:Budžaki, Sandra ; Čačić, F. ; Miljić, G.
  • 期刊名称:Croatian Journal of Food Science and Technology
  • 印刷版ISSN:1847-3466
  • 出版年度:2014
  • 卷号:6
  • 期号:2
  • 页码:124-130
  • 语种:English
  • 出版社:Prehrambeno-tehnološki fakultet Osijek
  • 摘要:Water (drinkable) is vital natural resource, and during the last few decades it is imperative to reduce its needless consumption. Extraction devices are known for their significant cooling water consumption and laboratory scale devices mainly use drinkable water. Aim of this paper was rationalization of cooling water consumption during extractions in universal extraction system B-811 LSV by recirculating cooling water trough cooling tower. In order to obtain the data for cooling tower design, measurements of cooling water flow, inlet and outlet cooling water temperatures, air humidity and temperature were conducted. Design of cooling tower based on obtained values resulted in cylindrical cooling tower, 81.45 cm height and with base radius of 13.96 cm. Cooling water consumption was reduced 56.87%.
  • 关键词:rationalization; cooling water; extraction; cooling tower
国家哲学社会科学文献中心版权所有